2-13. E: 51. Indoor unit fan motor error (Indoor unit)
Indicator
Wired remote
controller
Error code
E: 51
Detective actuator
Indoor unit
main PCB
When the condition that actual frequency of indoor fan is
below 1/3 of target frequency is continued more than 56
seconds.
Fan motor
Forecast of cause
Fan rotation failure
Fan motor winding open
Motor protection by surrounding temperature rise
Control PCB failure
Indoor unit fan motor failure
Check point 1. Check rotation of fan
Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check Indoor unit fan motor. (Refer to indoor unit fan motor in
03-49.)
→ If Indoor unit fan motor is abnormal, replace Indoor unit fan motor.
↓
Check point 4. Replace main PCB
If Check Point 1 to 3 do not improve the symptom, replace main PCB.
↓
End
2-13. E: 51. Indoor unit fan motor error (Indoor unit)
- (03-18) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG36KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB009EF_02 ...
Page 14: ...2 2 Outdoor unit 01 8 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 15: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB009EF_02 ...
Page 37: ...3 TROUBLESHOOTING 2020 07 21 SR_CH03_AB009EF_01 ...
Page 40: ......
Page 102: ...5 2 Outdoor unit 03 62 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 103: ...4 CONTROL AND FUNCTIONS 2020 07 21 SR_CH04_AB009EF_01 ...
Page 105: ...8 8 High temperature and high pressure release control 04 31 CONTENTS continued ...
Page 106: ......
Page 139: ...5 FILED WORKING 2020 07 21 SR_CH05_AB009EF_01 ...