2-10. E: 39. Indoor unit power supply error for fan motor (Indoor
unit)
Indicator
Wired remote
controller
Error code
E: 39
Detective actuator
Indoor unit main PCB
•
When a momentary power cut off
•
When do not start fan motor
Forecast of cause
External cause
Connector connection failure
Main PCB failure
Check point 1. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 2. Check connection of Connector
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
→ Upon correcting the removed connector or mis-wiring, reset the power.
↓
Check point 3. Replace main PCB
If check point 1 to 2 do not improve the symptom, change main PCB.
↓
End
2-10. E: 39. Indoor unit power supply error for fan motor (Indoor unit)
- (03-14) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABYG18KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AB004EF_03 ...
Page 24: ...2 2 Outdoor unit 01 18 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 25: ...2 TECHNICAL DATA AND PARTS LIST 2020 12 09 SR_CH02_AB004EF_05 ...
Page 71: ...3 TROUBLESHOOTING 2020 07 01 SR_CH03_AB004EF_01 ...
Page 74: ......
Page 138: ...5 2 Outdoor unit 03 64 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 139: ...4 CONTROL AND FUNCTIONS 2020 07 01 SR_CH04_AB004EF_01 ...
Page 141: ...8 8 High temperature and high pressure release control 04 42 CONTENTS continued ...
Page 142: ......
Page 187: ...5 FILED WORKING 2020 07 01 SR_CH05_AB004EF_01 ...