2-22. E: 74. Outdoor temperature thermistor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 74
Detective actuator
Outdoor unit main PCB
When outdoor temperature thermistor open or short
circuit is detected at power on or while running the
compressor
Outdoor temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the outdoor temperature thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-13.
If the voltage does not appear, replace main PCB.
↓
End
2-22. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- (03-27) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...