2-16. E: 63. Inverter error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 63
Detective actuator
Outdoor unit
Inverter PCB
Error information received from inverter PCB
Forecast of cause
External cause
Power supply to inverter PCB wiring disconnection or
open
Inverter PCB failure
Check point 1. Turn the power on again?
Error displayed again?
↓
Check point 2. Check the wiring (power supply to inverter PCB)
•
Connector and wiring connection state check
•
Cable open check
↓
Check point 3. Replace inverter PCB
Replace inverter PCB
↓
End
Check point 1-2. Check external cause
•
Check if temporary voltage drop was not generated.
•
Check if momentary open was not generated.
•
Check if ground is connection correctly or there are no related cables near the power line.
↓
End
2-16. E: 63. Inverter error (Outdoor unit)
- (03-21) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for ABHG54KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Page 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Page 34: ......
Page 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Page 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Page 98: ......
Page 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...