CONTENTS OF FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in
•
accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
•
Settings will not be changed if invalid numbers or setting values are selected.
•
1-1
Filter sign
1-2
Ceiling height
1-3
Cooler room temperature correction
1-4
Heater room temperature correction
1-5
Auto restart
1-6
Indoor Room Temperature Sensor Switching Function
1-1.Settingthefiltersign
The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting
for the filter sign display interval in the table below according to the amount of dust or debris in the
room. If you do not wish the filter sign to be displayed, select the setting value for "No indication".
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
"Standard
(2,500 hours)"
11
00
"Long interval
(4,400 hours)"
01
"Short interval
(1,250 hours)"
02
No indication
03
1-2. Setting the ceiling height
Select the setting values in the table below according to the height of the ceiling.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
(2.5m to 3.0m)
20
00
High ceiling
(3.0m or more)
01
1-3. Setting the Cooler Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
30
00
Lower control
01
1-4. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
Summary of Contents for AB A45LCT Series
Page 2: ...1 INDOOR UNIT D2D_AB031E 02 2011 03 01 CEILING TYPE AB A45LCT ...
Page 12: ... 01 09 CEILING TYPE AB A45LC CEILING TYPE AB A45LC WIRING DIAGRAMS 555 MODEL AB A45LC ...
Page 31: ...D2D_AO052E 01 2009 04 30 SINGLE TYPE AO A45LBTL 2 OUTDOOR UNIT ...
Page 35: ... 02 03 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L REFRIGERANT CIRCUIT 22222 MODEL AO A45L ...
Page 36: ... 02 04 OUTDOOR UNIT AO A45L OUTDOOR UNIT AO A45L WIRING DIAGRAMS 22222 MODEL AO A45L ...
Page 44: ...DTR_AO081E_01 2011 03 01 SINGLE TYPE AO A45LCTL AO A54LCTL 2 OUTDOOR UNIT ...