PART No. 9378782051
STEP 2
Selecting the Function Number and Setting Value
①
Press the SET TEMP. ( ) ( ) buttons to select the func-
tion number.
(Press the MODE button to switch between the left and
right digits.)
②
Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function num-
ber selection.)
③
Press the SET TEMP. ( ) ( ) buttons to select the set-
ting value.
(Press the MODE button to switch between the left and
right digits.)
④
Press the TIMER MODE button, and START/STOP button,
in the order listed to confi rm the settings.
⑤
Press the RESET button to cancel the function setting
mode.
⑥
After completing the FUNCTION SETTING, be sure to turn
off the power and turn it on again.
Function number
Setting value
CAUTION
After turning off the power, wait 30 seconds or more before
turning on it again.
The FUNCTION SETTING doesn’t become effective if it
doesn’t do so.
Filter sign
The indoor unit has a sign to inform the user that it is time to
clean the fi lter. Select the time setting for the fi lter sign display
interval in the table below according to the amount of dust
or debris in the room. If you do not wish the fi lter sign to be
displayed, select the setting value for “No indication”.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
Standard (2,500 hours)
11
00
Long interval (4,400 hours)
01
Short interval (1,250 hours)
02
◆
No indication
03
CHECK ITEMS
(1) Is operation of each button on the remote controller
normal?
(2) Does each lamp light normally?
(3) Is the drain normal?
(4) Is there any error noise and vibration during operation?
• Do not operate the air conditioner in the running state for a
long time.
• Test running
When the air conditioner is run by pressing the remote
controller TEST RUN button, the OPERATION and TIMER
lamps fl ash slowly at the same time.
[OPERATION METHOD]
• For the operation method, refer to the operating manual.
• The outdoor unit may not operate depending on the room
temperature. In this case, press the TEST RUN button on
the remote controller while the air conditioner is running.
(Point the transmitter section of the remote controller toward
the air conditioner and press the TEST RUN button with the
tip of a ball-point pen, etc.)
Transmitter section
TEST RUN button
• To end test operation, press the remote controller START/
STOP button.
(When the air conditioner is run by pressing the TEST RUN
button, the OPERATION indicator lamp and TIMER indica-
tor lamp will simultaneously fl ash slowly.)
[ERROR CONTENTS]
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
●(1)
●(1)
◊
Serial communication
error
●(1)
●(2)
◊
Wired remote controller
communication error
●(1)
●(5)
◊
Check run unfi nished
●(2)
●(1)
◊
R.C. address or
Refrigerant circuit address
setting error
[Simultaneous Multi]
●(2)
●(2)
◊
Indoor unit capacity error
●(2)
●(3)
◊
Combination error
●(2)
●(4)
◊
• Connection R.C. address
error (indoor secondary
unit)
[Simultaneous Multi]
• Connection R.C. address
error
(indoor unit or branch unit)
[Flexible Multi]
●(2)
●(7)
◊
Primary unit, secondary
unit setup error
[Simultaneous Multi]
●(3)
●(1)
◊
Power supply interruption
error
8
TEST RUN
The air conditioner signal code is set to A prior to ship-
ment. Contact your retailer to change the signal code.
The remote controller resets to signal code A when the
batteries in the remote controller are replaced. If you use a
signal code other than signal code A, reset the signal code
after replacing the batteries.
If you do not know the air conditioner signal code setting,
try each of the signal codes (
) until you fi nd
the code which operates the air conditioner.
When two or more air conditioners are installed in a room and
the remote controller is operating an air conditioner other than
the one you wish to set, change the signal code of the remote
controller to operate only the air conditioner you wish to set (four
selections possible).
When two or more air conditioners are installed in a room,
please contact your retailer to set the individual air conditioner
signal codes.
• Confi rm the setting of the remote controller signal code and
the printed circuit board setting.
If these are not confi rmed, the remote controller cannot be
used to operate for the air conditioner.
Selecting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote
controller. (Note that the air conditioner cannot
receive a signal code if the air conditioner has
not been set for the signal code.)
①
Press the START/STOP button until only
the clock is displayed on the remote con-
troller display.
②
Press the MODE button for at least five
seconds to display the current signal code
(initially set to ).
③
Press the SET TEMP. (
) (
) but-
ton to change the signal code between
.
Match the code on the display to the air
conditioner signal code.
④
Press the MODE button again to return to
the clock display. The signal code will be
changed.
7
SELECTING THE REMOTE CONTROLLER SIGNAL CODE
6
FUNCTION SETTING
• This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect
settings can cause the indoor unit malfunction.
• After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote
controller.
• The settings may be selected between the following two: Function Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
Entering the Function Setting Mode
• While pressing the FAN button and SET TEMP. ( ) simultaneously, press the RESET button to enter the function setting
mode.
STEP 1
Setting the Remote Controller Signal Code
Use the following steps to select the signal code of the remote controller. (Note that the air con-
ditioner cannot receive a signal code if the air conditioner has not been set for the signal code.)
The signal codes that are set through this process are applicable only to the signals in the
FUNCTION SETTING. For details on how to set the signal codes through the normal process,
refer to SELECTING THE REMOTE CONTROLLER SIGNAL CODE.
①
Press the SET TEMP. ( ) ( ) button to change the signal code between
.
Match the code on the display to the air conditioner signal code. (initially set to )
(If the signal code does not need to be selected, press the MODE button and proceed to
STEP 2.)
②
Press the TIMER MODE button and check that the indoor unit can receive signals at the dis-
played signal code.
③
Press the MODE button to accept the signal code, and proceed to STEP 2.
The air conditioner signal code is set to A prior to shipment.
Contact your retailer to change the signal code.
The remote controller resets to signal code A when the batteries in the remote controller are replaced. If you use a signal
code other than signal code A, reset the signal code after replacing the batteries.
If you do not know the air conditioner signal code setting, try each of the signal codes (
) until you fi nd the code
which operates the air conditioner.
Heating room temperature correction
Depending on the installed environment, the room temperature
sensor may require a correction.
The settings may be changed as shown in the table below.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
Auto restart
Enable or disable automatic system restart after a power
outage.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
Yes
40
00
No
01
* Auto restart is an emergency function such as for power
failure etc. Do not start and stop the indoor unit by this
function in normal operation. Be sure to operate by the
control unit, or external input device.
Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless
remote controllers.
If no buttons are pressed within 30 seconds after the signal
code is displayed, the system returns to the original clock
display. In this case, start again from step 1.
●(3)
●(2)
◊
Indoor unit PCB model
information error
●(3)
●(5)
◊
Manual auto switch error
●(4)
●(1)
◊
Inlet air temp. sensor error
●(4)
●(2)
◊
Indoor unit Heat Ex.
Middle temp. sensor error
●(5)
●(1)
◊
Indoor unit fan motor error
●(5)
●(3)
◊
Drain pump error
●(5)
●(7)
◊
Damper error
●(5)
●(15)
◊
Indoor unit error
●(6)
●(2)
◊
Outdoor unit main PCB
model information error or
communication error
●(6)
●(3)
◊
Inverter error
●(6)
●(4)
◊
Active fi lter error, PFC
circuit error
●(6)
●(5)
◊
Trip terminal L error
●(6)
●(10)
◊
Display PCB
microcomputers
communication error
●(7)
●(1)
◊
Discharge temp. sensor
error
●(7)
●(2)
◊
Compressor temp. sensor
error
●(7)
●(3)
◊
Outdoor unit Heat Ex.
liquid temp. sensor error
●(7)
●(4)
◊
Outdoor temp. sensor
error
●(7)
●(5)
◊
Suction Gas temp. sensor
error
●(7)
●(6)
◊
• 2-way valve temp.
sensor error
• 3-way valve temp.
sensor error
●(7)
●(7)
◊
Heat sink temp. sensor
error
●(8)
●(2)
◊
• Sub-cool Heat Ex. gas
inlet temp. sensor error
• Sub-cool Heat Ex. gas
outlet temp. sensor error
●(8)
●(3)
◊
Liquid pipe temp. sensor
error
●(8)
●(4)
◊
Current sensor error
●(8)
●(6)
◊
• Discharge pressure
sensor error
• Suction pressure sensor
error
• High pressure switch
error
●(9)
●(4)
◊
Trip detection
●(9)
●(5)
◊
Compressor rotor position
detection error (permanent
stop)
●(9)
●(7)
◊
Outdoor unit fan motor 1
error
●(9)
●(8)
◊
Outdoor unit fan motor 2
error
●(9)
●(9)
◊
4-way valve error
●(9)
●(10)
◊
Coil (expansion valve )
error
●(10)
●(1)
◊
Discharge temp. error
●(10)
●(3)
◊
Compressor temp. error
●(10)
●(4)
◊
High pressure error
●(10)
●(5)
◊
Low pressure error
●(13)
●(2)
◊
Branch boxes error
[Flexible Multi]
Display mode ● : 0.5s ON / 0.5s OFF
◊ : 0.1s ON / 0.1s OFF
( ) : Number of fl ashing
5
REMOTE CONTROLLER SETTING
2. REMOTE CONTROLLER HOLDER INSTALLATION
CAUTION
①
Check that the indoor unit correctly receives the signal from the remote controller, then install the remote controller holder.
②
Select the remote controller holder selection site by paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from a stove, etc.
• Install the remote controller with a distance of 7 m between the remote controller and the signal receiver as the criteria. How-
ever, when installing the remote controller, check that it operates positively.
• Install the remote controller holder to a wall, pillar, etc. with the tapping screw
①
Mount the Holder.
②
Set the remote controller.
③
To remove the remote controller
(when use at hand).
Screws
Insert
Press in
Slide up
Pull out
Ceiling height
Select the setting values in the table below according to the
height of the ceiling.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
Standard (3.2m)
20
00
High ceiling (4.2m)
( 30 model : 3.6m )
01
Low ceiling (2.7m )
02
The ceiling height values are for the 4-way outlet. Do not
change this setting in the 3-way outlet mode.
Outlet directions
Select the setting values in the table below for using a 3-way
outlet.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
4-way
22
00
3-way
01
Vertical direction adjusting scope
To prevent from draft, we recommend using “upward mode”.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
Standard
23
00
Upward
01
Outlet cross section
Cooling room temperature correction
Depending on the installed environment, the room tempera-
ture sensor may require a correction.
The settings may be selected as shown in the table below.
(
◆
... Factory setting)
Setting description
Function
number
Setting value
◆
Standard
30
00
Slightly lower control
01
Lower control
02
Warmer control
03
(
◆
.. Factory setting)
Setting description
Function
number
Setting value
◆
A
44
00
B
01
C
02
D
03
External input control
“Operation/Stop” mode or “Forced stop” mode can be
selected.
(
◆
.. Factory setting)
Setting description
Function
number
Setting value
◆
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
Setting record
• Record any changes to the settings in the following table.
Setting
Setting value
(1) Filter sign
(2) Ceiling height
(3) Outlet directions
(4) Vertical direction adjusting scope
(5) Cooler room temperature correction
(6) Heater room temperature correction
(7) Auto restart
(8) Wireless remote controller signal code
(9) External input control
After completing the FUNCTION SETTING, be sure to turn off
the power and turn it on again.
UTY-LRHYA2_0521.indd 2
2012/05/21 14:35:07