4.  TEST RUN

4.1. Pre-test run check items

Check items

 Is the outdoor unit securely installed?

  Have you performed gas leakage inspection?

 

(Connection joints of various pipes (flange connection, brazing))

  Is the heat insulation done completely? 

(Gas pipe, liquid pipe, drain hose extension on indoor unit side etc.)

 Is the water discharging from drain without any problems?

 Are the cables connected correctly?

 Are the cables as per specifications?

 Is the ground (earth) wire connected accurately?

  Are there any obstacles blocking the suction gate, and outlet of 

 

the indoor/outdoor units?

 Have you filled the specified amount of refrigerant?

 Are the stop valves of gas pipe and liquid pipe fully open?

 Has the power been supplied to crankcase heater for more than 6 hours?

 After checking that the above items are all in order, refer to “4.2. Test operation method”

 to 

test operation the unit. If there are problems, adjust immediately and recheck.

4.2. Test operation method

Be sure to configure test run settings only when the outdoor unit has stopped oper

-

ating.

Test operation setting method (It can be performed in the following two ways)

•  Set with test operation setting (refer to the installation manual of indoor unit for further 

details) available in the remote controller.

•  Cooling operation and Heating operation can be set using [SELECT] button (S133) 

and [ENTER] button (S132) available on the board of display unit. 

 

(Make sure to perform the first test operation with cooling operation.) 

 

Set as per the following procedure.

6

6

6

6

6

LED display part

Button part

•  Depending on the communication status between the indoor and outdoor units, 

it may take several minutes for the system to start operating after settings for the 

test run are complete.

• 

After the test run settings are complete, the outdoor units and the connected 

indoor units will start operating. Room temperature control will not activate during 

test operation (continuous operation).

•  If a knocking sound can be heard in the liquid compression of the compressor, 

stop the unit immediately and then energize the crank case heater for a sufficient 

length of time before restarting the operation.

4.2.1. Setting method on outdoor unit board

(1)    Turn on the power of the outdoor unit and enter standby mode. 

 

“POWER/MODE” display lights on.

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

(2)  Press the [ENTER] button (S132) for more than 3 seconds.

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

(3)  Press the [SELECT] button (S133), LED of the test run mode switched between 

Cooling and Heating.

 

Cooling test mode

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

Heating test mode

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Blink

Sign “

”: Lights off, “

”: Lights on

(4)  After confirming the operation mode, press [ENTER] button (S132).

 

The display changes as follows, and the air conditioner starts operation.

 

Cooling test mode

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Sign “

”: Lights off, “

”: Lights on

Heating test mode

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Blink

Sign “

”: Lights off, “

”: Lights on

(5)  Press [ENTER] button (S132).

 

Air conditioner stops operation.

POWER/

MODE

ERROR

PUMP 

 

DOWN

LOW NOISE

PEAK CUT

(L1)

(L2)

(L3)

(L4)

(L5)

(L6)

Sign “

”: Lights off, “

”: Lights on

4.3. Checklist

Check items during test operation.

 Is the outdoor unit making any abnormal noise or vibrating significantly?

  Is the cold air or hot air blowing from indoor unit according to the operation 

mode?

 

Check that the “ERROR” LED blinks

If, it has displayed, check the error content as per the “10.2. Error code check 
table”

 described later.

  Operate the unit according to the operation manual provided with the indoor 

unit, and check that it is operating normally.

9379113069-02_IM.indb   11

6/11/2021   10:26:47 AM

Summary of Contents for 24LMAS1

Page 1: ... a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run ins...

Page 2: ...her than as liquid or gas When Servicing Turn the power OFF at the main circuit breaker panel before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Clean up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced After installation explain correct o...

Page 3: ...re and dust Especially pay attention when passing the pipes through a hole or connecting the end of a pipe to the outdoor unit Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 4 Power source WARNING Always use a special branch circuit and install a special receptacle to supply power to the room air cond...

Page 4: ...e risk of the leakage of flammable gas in the vicinity Area where small animals may live It may cause failure smoke or fire if small animals enter and touch internal electrical parts Area where animals may urinate on the unit or ammonia may be generated Do not tilt the outdoor unit more than 3 degrees However do not install the unit with it tilted towards the side containing the compressor Install...

Page 5: ... 500 or more 10 250 or more 3 Obstacles at front and rear 20 500 or more 60 1 500 or more 10 250 or more When an obstruction is present also in the upward area Unit in mm 1 Obstacles at rear and above Up to 3 units can be installed side by side When 4 units or more are arranged in a line provide the space as shown below 60 1 500 or more 20 500 or more 10 250 or more Max 11 300 60 1 500 or more 3 1...

Page 6: ...cing is recommended when blowing and drifting snow is common to the region 3 4 Drain installation CAUTION Perform drain work in accordance with this Manual and ensure that the drain water is properly drained If the drain work is not carried out correctly water may drip down from the unit wetting the furniture When the outdoor temperature is 32 F 0 C or less do not use the accessory drain pipe If t...

Page 7: ...s Bend the pipe with a radius of curvature of 3 15 16 in 100 mm to 5 7 8 in 150 mm If the pipe is bent repeatedly at the same place it will break If pipes are shaped by hand be careful not to collapse them Do not bend the pipes at an angle of more than 90 When pipes are repeatedly bent or stretched the material will harden making it difficult to bend or stretch them anymore Do not bend or stretch ...

Page 8: ...he valves Use a hexagon wrench size 4 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclockwise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening direction Hexagon wrench Seal blank ...

Page 9: ... amperage at which the breaker cuts out may decrease When using an earth leakage breaker that has been designed solely for ground fault protection be sure to install a fuse equipped switch or circuit breaker This system uses an inverter which means that it must be used an earth leakage breaker that can handle harmonics in order to prevent malfunctioning of the earth leakage breaker itself Do not u...

Page 10: ... supply matches with the phase of the terminal board If the phases do not match the compressor will rotate in reverse and will not be able to compress Connection diagrams L1 L2 Power supply Outdoor unit side terminal Indoor unit side terminal Power line Ground Earth Ground Earth Cable preparation Keep the ground earth wire longer than the other wires Ground Earth wire 1 9 16 in 40 mm Power supply ...

Page 11: ...s will start operating Room temperature control will not activate during test operation continuous operation If a knocking sound can be heard in the liquid compression of the compressor stop the unit immediately and then energize the crank case heater for a sufficient length of time before restarting the operation 4 2 1 Setting method on outdoor unit board 1 Turn on the power of the outdoor unit a...

Page 12: ...Y UNIT 6 1 Display unit position WARNING Never touch electrical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock CAUTION Once refrigerant charging is completed be sure to open the valve prior to performing the local settings Otherwise the compressor may fail Discharge any static electricity from your body before to...

Page 13: ...ting performance may decrease Depending on the operating condition the noise level may not decrease even if the Low noise mode is on Level 2 Blink 9 times 2 Peak cut mode setting Level 1 Blink 9 times The capacity limit can be selected when operating with the Peak cut mode The operation selection can be done by external input connector PA580 The lower the level the more the effect of energy saving...

Page 14: ... beginning of operation procedure after returning to Operation status displays normal operation by pressing the EXIT button once 8 EXTERNAL INPUT AND OUTPUT 8 1 External input 8 1 1 Wiring of connector On Off of the Low noise mode and Peak cut mode functions can be enabled with an external field device When installing connection cable specified part optional parts must be used Refer to section 7 2...

Page 15: ...ical components such as the terminal blocks except the button on the display board It may cause a serious accident such as electric shock During the pump down operation make sure that the compressor is turned off before you remove the refrigerant piping Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open This may cause abnormal pressure in the refr...

Page 16: ...L5 L6 Sign Lights off Lights on 3 Press PUMP DOWN button S130 for 3 seconds or more after 3 minutes after power on POWER MODE ERROR PUMP DOWN LOW NOISE PEAK CUT L1 L2 L3 L4 L5 L6 Sign Lights off Lights on LED display lights on as shown in the above table and the fans and the compressor start operating If the PUMP DOWN button S130 is pressed while the compressor is operating the compressor will sto...

Page 17: ...Outdoor temp sensor error Outdoor temp sensor error Blink 2 times Blink 7 times Blink 4 times Heat sink temp sensor error Heat sink temp sensor error Blink 2 times Blink 7 times Blink 7 times Current sensor error Current sensor 1 error stoppage permanently Blink 2 times Blink 8 times Blink 4 times Pressure sensor error High pressure switch 1 error Blink 2 times Blink 8 times Blink 6 times Pressure...

Reviews: