background image

Tapping
screws

Insert

Slide up

Mount the Holder.

1

 Set the Remote Control
 Unit.

2

To remove the Remote
Control Unit (when use
at hand.)

3

Tapping
screws

Tapping
screw

Insert

Mount the Holder.

1

 Set the Remote Control
 Unit.

2

Atlach the unit to the
holder as shown.

3

Slide

START

STOP

START/STOP button

TEST RUN button

A B C D

Indoor unit

Coupler heat insulation (large)

Connection pipe (large)

Connection pipe (small)

Coupler heat insulation (small)

Indoor unit

Nylon fastner (large)

Nylon fastner (small)

Coupler heat
insulation

No gap

Arrange the drain pipe
lower than this portion.

Drain pipe

GOOD

Lifted up

BAD

BAD

Wave

End in water

Supporter

5 to 6.5 ft

(1.5 to 2 m)

Indoor unit (drain port)

Insulation for Drain pipe
(To be obtained locally. Length should
be at least 8mm.)

Drain pipe insulation (accessories)

Drain pipe

Duct

Control box

Cover A

Control box

Tapping screw

Indoor unit

10 mm or over

Indoor unit

No gap

Drain pipe insulation

Drain pipe

Indoor unit

For half concealed
installation

Round duct (option parts)

Indoor unit (rear view)

VT wire

Drain hose

Refrigerant pipe

3-way valve

Blank cap

Charging valve

Cap

Service hose with
valve core

Outdoor unit

LO

HI

Gauge manifold

Vacuum pump

Service hose

Cable clip

Cable clip

After passing the connection 
cord through the insulation 
tube, fasten it with the cord 
clamp

3

1

2

Valve
cover

Reinstall the 
removed screws.

Accessory
part

Attach the 
four fasteners.

Make longer 
than the other 
wires.

Insulation tube

Insulation tube

Power cord

Ground

Power cord

Terminal board

Control box

Cord clamp

Connection cord
(indoor unit and outdoor
unit connection cord)

Power supply

Power line

Control line

Indoor unit
side terminal

Outdoor unit
side terminal

EARTH

L

N

3

2

(N)

1

3

2

(N)

1

L N 3

2

(N)

1

Cable clip

Control box

Connection cord

Terminal board

Earth screw

Cord clamp

To outdoor unit

Connection cord

Connection cord

Indoor unit
Printed circuit board

JM1

JM2

JM3

AUTORESTART
REMOCON 2
REMOCON 1

SWING SWING

TIMER OPERATION

MANUAL

AUTO

VERTICAL SWING lamp (Orange)

TIMER lamp (Green)

OPERATION lamp (Red)

A B C D

A

B

C

D

Remote control unit
signal selector switch

Remote control unit

ACL button

PART NO. 9361156012-02

WARNING

(1)

(2)

(3)

(4)

(5)

Before starting work, check that power is not being 
supplied to the outdoor unit.

Match the terminal board numbers and connection 
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric 
parts.

Connect the connection cord firmly to the terminal 
board. Imperfect installation may cause a fire.

Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is 
chafed, electric leakage may occur.)

Always connect the ground wire.

CAUTION

When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage 
raised.

CAUTION

(1)

(2)

Check that the indoor unit correctly receives the signal 
from the remote control unit, then install the remote 
control unit holder.

Select the remote control unit holder selection site by 
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat 
from a stove, etc.

WARNING

(1)

(2)

(3)

(4)

(5)

(6)

(7)

The rated voltage of this product is 220-240V AC 
50Hz.

Before turning on verify that the voltage is within the 
198V to 264V range.

Always use a special branch circuit and install a special 
receptacle to supply power to the air conditioner.

Use a special branch circuit breaker and receptacle 
matched to the capacity of the air conditioner.
(Fuse/Breaker capacity : 30 A)

The special branch circuit breaker is installed in the per-
manent wiring. Always use a circuit that can trip all the 
poles of the wiring and has an isolation distance of at 
least 3mm between the contacts of each pole.

Perform wiring work in accordance with standards so 
that the air conditioner can be operated safely and 
positively.

Install a leakage special branch circuit breaker in 
accordance with the related laws and regulations 
and electric company standards.

WARNING

(1)

(2)

(3)

(4)

(5)

Before starting work, check that power is not being 
supplied to the outdoor unit.

Match the terminal board numbers and connection 
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric 
parts.

Connect the connection cord firmly to the terminal 
board. Imperfect installation may cause a fire.

Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is 
chafed, electric leakage may occur.)

Always connect the ground wire.

CAUTION

(1)

(2)

When removing the cabinet (iron plate), be careful not 
to damage the indoor unit internal parts and surround-
ing  area (outer case).

When processing the cabinet (iron plate), be careful 
not to injure yourself with burrs, etc.

CAUTION

After connecting the piping, check the joints for gas 
leakage with gas leak detector.

CAUTION

Use 1.0 mm

2

 to 1.5 mm

2

 H07RN-F or equivalent as the 

connection cord.

Select power cable matched to the fuse capacity. 
(Install in accordance with standard.)

Use VW-1, 12 mm diameter, 0.5 to 1.0 mm thick, PVC 
tube as the insulation tube.

(1)

(2)

(3)

Error display

OPERATION

lamp

TIMER

lamp

VERTICAL

SWING lamp

Error contents

Model information abnormal
(permanent type)

Drain abnormal (permanent 
type)

Indoor fan abnormal

Room air temperature 
thermistor open circuit

Room air temperature 
thermistor short circuit

Piping thermistor open
circuit

Piping thermistor short
circuit

Serial communications

abnormal

Reverse phase wire
connection abnormal

Outdoor heat exchange
thermistor open circuit

Outdoor heat exchange
thermistor short circuit

High pressure abnormal

Outdoor discharge
thermistor open circuit

Outdoor discharge
thermistor short circuit

Discharge temperature
abnormal

Outdoor air temperature
thermistor open circuit

Outdoor air temperature
thermistor short circuit

Goes off

Goes off

Goes off

Goes off

Blinks

Goes off

Blinks

Goes off

Goes off

Goes off

Blinks

Goes off

Goes off

Blinks

Goes off

Goes off

Blinks

Blinks

Blinks

Blinks

Blinks

Blinks

Blinks

Pulses
2 times

Pulses
3 times

Pulses
6 times

Pulses
5 times

Pulses
7 times

Pulses
4 times

Blinks

Pulses
4 times

Pulses
6 times

Pulses
2 times

Pulses
3 times

Pulses
5 times

Blinks

Blinks

Blinks

Blinks

Blinks

Blinks

(1)

POWER

To end test operation, press the remote control unit START/STOP 
button.
(When the air conditioner is run by pressing the remote control 
unit TEST RUN button, the OPERATION and TIMER lamps will 
simultaneously flash slowly.)

1. INDOOR UNIT

Is operation of each button on the remote control unit nor-
mal?
Does each lamp light normally?
Do not air flow direction flap and louvers operate normally?
Is the drain normal?

2. OUTDOOR UNIT

Is there any abnormal noise and vibration during operation?
Will noise, wind, or drain water from the unit disturb the 
neighbors?
Is there any gas leakage?

(1)

(2)
(3)
(4)

(1)
(2)

(3)

CUSTOMER GUIDANCE

FINISHING

Explain the following to the customer in accordance with the operating 
manual:

Starting and stopping method, operation switching, temperature 
adjustment, timer, air flow adjustment, and other remote control 
unit operations.
Air filter removal and cleaning.
Give the operating and installation manuals to the customer.

(1)

(2)
(3)

REMOTE CONTROL UNIT

INSTALLATION

FRESH-AIR INTAKE

A  ERROR DISPLAY

ELECTRICAL WIRING

(1)

(2)

(3)

(4)

(1)

(2)

(3)

(4)

GAS LEAKAGE INSPECTION

INSTALLING THE COUPLER HEAT 

INSULATION

After checking for gas leaks, insulate by wrapping insulation around the 
two parts (large and small) of the indoor unit coupling, using the coupler 
heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl 
tape so that there is no gap.
Secure both ends of the heat insulation material using nylon fasteners.

Fig. 29

When using an auxiliary pipe, make sure that the fastener 
used is insulated in the same way.

DRAIN PIPING

Install the drain pipe with downward gradient (1/50 to 1/100) and so 
there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 38 
mm].
During installation of the drain pipe, be careful to avoid applying 
pressure to the drain port of the indoor unit.
When the pipe is long, install supporters (Fig. 30).
Do not perform air bleeding.
Always heat insulate (8mm or over thick) the indoor side of the drain 
pipe.

Fig. 30

Install insulation for the drain pipe. (See Figs. 31 and 32.) 
Cut the included insulation material to an appropriate size and 
adhere it to the pipe.

Fig. 31

Fig. 32

 

If "

1

 Right rear piping": fasten the drain pipe with VT wire so 

that the pipe slopes correctly within the indoor unit. (Fig. 33)

Fig. 33

••

(2)

1. INDOOR UNIT SIDE

Remove the two tapping screws and pull the control box down-
ward. (Fig. 35)

Fig. 35

Remove the Cover A and install the Connection cord (Fig. 36 and 
37)
After wiring is complete, clamp the Connection cord with the 
Cord clamp (Fig. 37)
Reattach Cover A. Then fasten the control box back into its 
original position using the two tapping screws.
Attach the connection cord and cable clips. Make sure that they 
are positioned so that they will not interfere with opening and 
closing of the intake grille or with removal and installation of 
the air filters. (Fig. 37)

Fig. 36

Fig. 37

(1)

2. OUTDOOR UNIT SIDE

(2)

(3)

(4)

(5)

1. REMOTE CONTROL UNIT HOLDER INSTALLATION

Install the remote control unit holder to a wall or pillar with the 
tapping  screws.

Fig. 43

For use as Handy Type

For use as Wall Fixing Type

TEST RUNNING

Perform test operation and check items 1 and 2 below.
For the operation method, refer to the operating manual.
The outdoor unit may not run, depending on the room 
temperature. In this case, press the TEST RUN button while the 
air conditioner is running.
(With the transmit section of the remote control unit facing the 
body, press the TEST RUN button with the tip of a ball point pen.)

Fig. 42

Open up the knockout hole for the fresh-air intake, as shown in 
Fig. 45. (If using half-concealed installation, open up the top 
knockout hole instead.)

Fig. 45

(1)

Fasten the round flange (optional) to the fresh-air intake, as 
shown in Fig. 46. (If using half-concealed installation, attach to 
the top.)

Fig. 46

[After completing "

2

 INDOOR UNIT INSTALLATION"…]

Connect the duct to the round flange.
Seal with a band and vinyl tape, etc. so that air does not leak 
from the connection.

Fig. 47

(2)

(3)
(4)

HOW TO CONNECT WIRING TO THE TERMINALS

A. For solid core wiring (or F-cable)

Cut the wire and with a wire cutter or wire-cutting pliers, 
then strip the insulation to about 15/16” (25 mm) of 
expose the solid wire.
Using a screwdriver, remove the terminal screw(s) on 
the terminal board.
Using pliers, bend the solid wire to form a loop suitable 
for the terminal screw.
Shape the loop wire properly, place it on the terminal 
board and tighten securely with the terminal screw 
using a screwdriver.

B. For strand wiring

Cut the wire and with a wire cutter or wire-cutting 
pliers, then strip the insulation to about 3/8” (10 mm) of 
expose the strand wiring.
Using a screwdriver, remove the terminal screw(s) on 
the terminal board.
Using a round terminal fastener or pliers, securely 
clamp a round terminal to each stripped wire end.
Position the round terminal wire, and replace and 
tighten the terminal screw using a screwdriver.

Fig. 34

Install the filter guide.
Install the intake grills.
Install side covers A and B (if the unit is installed in a half-
concealed orientation, only install side cover A).
Install the air filters.

(1)
(2)
(3)

(4)

When moving and installing the air conditioner, do not 
mix gas other than the specified refrigerant (R22) 
inside the refrigerant cycle.

When adding refrigerant, add the refrigerant from the 
charging valve at the completion of work.

If the units are further apart than the maximum pipe 
length, correct operation can not be guaranteed.

(1)

(2)

(3)

CAUTION

AIR PURGE

1. AIR PURGE

Remove the cap, and connect the gauge manifold and the vacuum 
pump to the charging valve by the service hoses.
Vacuum the indoor unit and the connecting pipes until the pres-
sure in them lowers to below 1.5 mmHg.
Disconnect the service hoses and fit the cap to the charging valve 
(Tightening torque : 70 to 90 kgf • cm).
Remove the blank caps, and fully open the spindles of the 2-way 
and 3-way valves with a hexagon wrench (Torque : 2-way valve: 
70 to 90 kgf • cm, 3-way valve: 100 to 120 kgf • cm).
Tighten the blank caps of the 2-way valve and 3-way valve to the 
specified torque (200 to 250 kgf • cm).

Fig. 27

Fig. 28

(1)

(2)

(3)

(4)

(5)

2. ADDITIONAL CHARGE

Refrigerant suitable for a piping length of 5 m is charged in the outdoor 
unit at the factory.
When the piping is longer than 5 m, additional charging is necessary.
For the additional amount, see the table below.

Between 5 m and 30 m, when using a connection pipe other than that in 
the table, charge additional refrigerant with 1.8 oz (40 g) / 3.3 ft (1 m) (Re-
verse cycle model), 0.6 oz (17 g) / 3.3 ft (1 m) (Cooling model) as the cri-
teria.

Additional
refrigerant

Table 6

Heat & Cool 

(Reverse cycle)

Cooling

model

16 ft

(5 m)

None

None

33 ft

(10 m)

7.1 oz

(200 g)

3.0 oz
(85 g)

49 ft

(15 m)

14.1 oz
(400 g)

6.0 oz

(170 g)

66 ft

(20 m)

21.2 oz
(600 g)

9.0 oz

(255 g)

99 ft

(30 m)

15.0 oz
(425 g)

82 ft

(25 m)

28.2 oz

(800 g)

12.0 oz
(340 g)

Pipe length

Remove outdoor unit valve cover and connect the power cord and 
the outdoor unit connection cord wired at the indoor unit.
Fasten the sheath with a cord clamp.
Fasten the power cord and connection cord with cable clip and 
binders as shown in (Fig. 40)

Fig. 38

Fig. 39

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

Fig. 40

Install the valve cover.

Fig. 41

(4)

(1)

(2)
(3)

2. REMOTE CONTROL UNIT CODE SWITCHING

Fig. 44

Confirm the remote control unit signal selector switch selection and 
printed

 

circuit  board setting.

If these are not confirmed, the remote control unit cannot be operat-
ed for the air conditioner.

Table 7

1. INDOOR UNIT

Operation can be checked by lighting and flashing of the display 
section OPERATION, TIMER and VERTICAL SWING lamps.
Perform judgment in accordance with the following.

Fig. 48

Test running

When the air conditioner is run by pressing the remote 
control unit test run button, the OPERATION, TIMER and 
VERTICAL SWING lamps flash slowly at the same time.

Error

The OPERATION, TIMER and VERTICAL SWING lamps operate 
as follows (Table 8) according to the error contents.

Table 8

2. OUTDOOR UNIT

Error

The LED lamps operate as follows (Table 9) according to the 
error contents.

Table 9

When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high 
pressure abnormal, the LED lamp lights continuously for 24 hours, 
as long as the power is not turned off.

Jumper wire

Remote control unit

signal selector switch

JM 2

JM 3

Connect

Connect

Connect

Disconnect

Disconnect

Connect

Disconnect

Disconnect

A (Primary setting)

B

C

D

Error display

Error contents

LED

No. 1
Lamp

LED

No. 2
Lamp

Discharge pipe
temperature
abnormal

Discharge pipe
temperature
sensor abnormal

High pressure
abnormal

Outdoor heat
exchanger tem-
perature sensor
abnormal

Outdoor  tem-
perature sensor
abnormal

OFF

ON

Lighting
continue

OFF

ON

Lighting
continue

0.5 sec

5 sec

OFF

ON

Puls 1 time
repeated 

0.5 sec

0.5 sec

5 sec

OFF

ON

Pulses 2 times
repeated

0.5 sec

0.5 sec

5 sec

OFF

ON

Pulses 3 times
repeated

After setting the remote control unit signal selector 
switch, press the ACL button. 

6

9

7

5

8

10

11

16

12

15

13

14

Reviews: