Tapping
screws
Insert
Slide up
Mount the Holder.
1
Set the Remote Control
Unit.
2
To remove the Remote
Control Unit (when use
at hand.)
3
Tapping
screws
Tapping
screw
Insert
Mount the Holder.
1
Set the Remote Control
Unit.
2
Atlach the unit to the
holder as shown.
3
Slide
START
STOP
START/STOP button
TEST RUN button
A B C D
Indoor unit
Coupler heat insulation (large)
Connection pipe (large)
Connection pipe (small)
Coupler heat insulation (small)
Indoor unit
Nylon fastner (large)
Nylon fastner (small)
Coupler heat
insulation
No gap
Arrange the drain pipe
lower than this portion.
Drain pipe
GOOD
Lifted up
BAD
BAD
Wave
End in water
Supporter
5 to 6.5 ft
(1.5 to 2 m)
Indoor unit (drain port)
Insulation for Drain pipe
(To be obtained locally. Length should
be at least 8mm.)
Drain pipe insulation (accessories)
Drain pipe
Duct
Control box
Cover A
Control box
Tapping screw
Indoor unit
10 mm or over
Indoor unit
No gap
Drain pipe insulation
Drain pipe
Indoor unit
For half concealed
installation
Round duct (option parts)
Indoor unit (rear view)
VT wire
Drain hose
Refrigerant pipe
3-way valve
Blank cap
Charging valve
Cap
Service hose with
valve core
Outdoor unit
LO
HI
Gauge manifold
Vacuum pump
Service hose
Cable clip
Cable clip
After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp
3
1
2
Valve
cover
Reinstall the
removed screws.
Accessory
part
Attach the
four fasteners.
Make longer
than the other
wires.
Insulation tube
Insulation tube
Power cord
Ground
Power cord
Terminal board
Control box
Cord clamp
Connection cord
(indoor unit and outdoor
unit connection cord)
Power supply
Power line
Control line
Indoor unit
side terminal
Outdoor unit
side terminal
EARTH
L
N
3
2
(N)
1
3
2
(N)
1
L N 3
2
(N)
1
Cable clip
Control box
Connection cord
Terminal board
Earth screw
Cord clamp
To outdoor unit
Connection cord
Connection cord
Indoor unit
Printed circuit board
JM1
JM2
JM3
AUTORESTART
REMOCON 2
REMOCON 1
SWING SWING
TIMER OPERATION
MANUAL
AUTO
VERTICAL SWING lamp (Orange)
TIMER lamp (Green)
OPERATION lamp (Red)
A B C D
A
B
C
D
Remote control unit
signal selector switch
Remote control unit
ACL button
PART NO. 9361156012-02
WARNING
(1)
(2)
(3)
(4)
(5)
Before starting work, check that power is not being
supplied to the outdoor unit.
Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
Connect the connection cord firmly to the terminal
board. Imperfect installation may cause a fire.
Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
Always connect the ground wire.
CAUTION
When the voltage is low and the air conditioner is diffi-
cult to start, contact the power company the voltage
raised.
CAUTION
(1)
(2)
Check that the indoor unit correctly receives the signal
from the remote control unit, then install the remote
control unit holder.
Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat
from a stove, etc.
WARNING
(1)
(2)
(3)
(4)
(5)
(6)
(7)
The rated voltage of this product is 220-240V AC
50Hz.
Before turning on verify that the voltage is within the
198V to 264V range.
Always use a special branch circuit and install a special
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
matched to the capacity of the air conditioner.
(Fuse/Breaker capacity : 30 A)
The special branch circuit breaker is installed in the per-
manent wiring. Always use a circuit that can trip all the
poles of the wiring and has an isolation distance of at
least 3mm between the contacts of each pole.
Perform wiring work in accordance with standards so
that the air conditioner can be operated safely and
positively.
Install a leakage special branch circuit breaker in
accordance with the related laws and regulations
and electric company standards.
WARNING
(1)
(2)
(3)
(4)
(5)
Before starting work, check that power is not being
supplied to the outdoor unit.
Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
Connect the connection cord firmly to the terminal
board. Imperfect installation may cause a fire.
Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)
Always connect the ground wire.
CAUTION
(1)
(2)
When removing the cabinet (iron plate), be careful not
to damage the indoor unit internal parts and surround-
ing area (outer case).
When processing the cabinet (iron plate), be careful
not to injure yourself with burrs, etc.
CAUTION
After connecting the piping, check the joints for gas
leakage with gas leak detector.
CAUTION
Use 1.0 mm
2
to 1.5 mm
2
H07RN-F or equivalent as the
connection cord.
Select power cable matched to the fuse capacity.
(Install in accordance with standard.)
Use VW-1, 12 mm diameter, 0.5 to 1.0 mm thick, PVC
tube as the insulation tube.
(1)
(2)
(3)
Error display
OPERATION
lamp
TIMER
lamp
VERTICAL
SWING lamp
Error contents
Model information abnormal
(permanent type)
Drain abnormal (permanent
type)
Indoor fan abnormal
Room air temperature
thermistor open circuit
Room air temperature
thermistor short circuit
Piping thermistor open
circuit
Piping thermistor short
circuit
Serial communications
abnormal
Reverse phase wire
connection abnormal
Outdoor heat exchange
thermistor open circuit
Outdoor heat exchange
thermistor short circuit
High pressure abnormal
Outdoor discharge
thermistor open circuit
Outdoor discharge
thermistor short circuit
Discharge temperature
abnormal
Outdoor air temperature
thermistor open circuit
Outdoor air temperature
thermistor short circuit
Goes off
Goes off
Goes off
Goes off
Blinks
Goes off
Blinks
Goes off
Goes off
Goes off
Blinks
Goes off
Goes off
Blinks
Goes off
Goes off
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Pulses
2 times
Pulses
3 times
Pulses
6 times
Pulses
5 times
Pulses
7 times
Pulses
4 times
Blinks
Pulses
4 times
Pulses
6 times
Pulses
2 times
Pulses
3 times
Pulses
5 times
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
(1)
POWER
To end test operation, press the remote control unit START/STOP
button.
(When the air conditioner is run by pressing the remote control
unit TEST RUN button, the OPERATION and TIMER lamps will
simultaneously flash slowly.)
1. INDOOR UNIT
Is operation of each button on the remote control unit nor-
mal?
Does each lamp light normally?
Do not air flow direction flap and louvers operate normally?
Is the drain normal?
2. OUTDOOR UNIT
Is there any abnormal noise and vibration during operation?
Will noise, wind, or drain water from the unit disturb the
neighbors?
Is there any gas leakage?
•
•
•
(1)
(2)
(3)
(4)
(1)
(2)
(3)
CUSTOMER GUIDANCE
FINISHING
Explain the following to the customer in accordance with the operating
manual:
Starting and stopping method, operation switching, temperature
adjustment, timer, air flow adjustment, and other remote control
unit operations.
Air filter removal and cleaning.
Give the operating and installation manuals to the customer.
(1)
(2)
(3)
REMOTE CONTROL UNIT
INSTALLATION
FRESH-AIR INTAKE
A ERROR DISPLAY
ELECTRICAL WIRING
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
GAS LEAKAGE INSPECTION
INSTALLING THE COUPLER HEAT
INSULATION
After checking for gas leaks, insulate by wrapping insulation around the
two parts (large and small) of the indoor unit coupling, using the coupler
heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl
tape so that there is no gap.
Secure both ends of the heat insulation material using nylon fasteners.
Fig. 29
When using an auxiliary pipe, make sure that the fastener
used is insulated in the same way.
DRAIN PIPING
Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 38
mm].
During installation of the drain pipe, be careful to avoid applying
pressure to the drain port of the indoor unit.
When the pipe is long, install supporters (Fig. 30).
Do not perform air bleeding.
Always heat insulate (8mm or over thick) the indoor side of the drain
pipe.
Fig. 30
Install insulation for the drain pipe. (See Figs. 31 and 32.)
Cut the included insulation material to an appropriate size and
adhere it to the pipe.
Fig. 31
Fig. 32
If "
1
Right rear piping": fasten the drain pipe with VT wire so
that the pipe slopes correctly within the indoor unit. (Fig. 33)
Fig. 33
••
•
•
•
•
•
(2)
1. INDOOR UNIT SIDE
Remove the two tapping screws and pull the control box down-
ward. (Fig. 35)
Fig. 35
Remove the Cover A and install the Connection cord (Fig. 36 and
37)
After wiring is complete, clamp the Connection cord with the
Cord clamp (Fig. 37)
Reattach Cover A. Then fasten the control box back into its
original position using the two tapping screws.
Attach the connection cord and cable clips. Make sure that they
are positioned so that they will not interfere with opening and
closing of the intake grille or with removal and installation of
the air filters. (Fig. 37)
Fig. 36
Fig. 37
(1)
2. OUTDOOR UNIT SIDE
(2)
(3)
(4)
(5)
1. REMOTE CONTROL UNIT HOLDER INSTALLATION
Install the remote control unit holder to a wall or pillar with the
tapping screws.
Fig. 43
For use as Handy Type
For use as Wall Fixing Type
TEST RUNNING
Perform test operation and check items 1 and 2 below.
For the operation method, refer to the operating manual.
The outdoor unit may not run, depending on the room
temperature. In this case, press the TEST RUN button while the
air conditioner is running.
(With the transmit section of the remote control unit facing the
body, press the TEST RUN button with the tip of a ball point pen.)
Fig. 42
•
•
•
Open up the knockout hole for the fresh-air intake, as shown in
Fig. 45. (If using half-concealed installation, open up the top
knockout hole instead.)
Fig. 45
(1)
Fasten the round flange (optional) to the fresh-air intake, as
shown in Fig. 46. (If using half-concealed installation, attach to
the top.)
Fig. 46
[After completing "
2
INDOOR UNIT INSTALLATION"…]
Connect the duct to the round flange.
Seal with a band and vinyl tape, etc. so that air does not leak
from the connection.
Fig. 47
(2)
(3)
(4)
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
Cut the wire and with a wire cutter or wire-cutting pliers,
then strip the insulation to about 15/16” (25 mm) of
expose the solid wire.
Using a screwdriver, remove the terminal screw(s) on
the terminal board.
Using pliers, bend the solid wire to form a loop suitable
for the terminal screw.
Shape the loop wire properly, place it on the terminal
board and tighten securely with the terminal screw
using a screwdriver.
B. For strand wiring
Cut the wire and with a wire cutter or wire-cutting
pliers, then strip the insulation to about 3/8” (10 mm) of
expose the strand wiring.
Using a screwdriver, remove the terminal screw(s) on
the terminal board.
Using a round terminal fastener or pliers, securely
clamp a round terminal to each stripped wire end.
Position the round terminal wire, and replace and
tighten the terminal screw using a screwdriver.
Fig. 34
•
Install the filter guide.
Install the intake grills.
Install side covers A and B (if the unit is installed in a half-
concealed orientation, only install side cover A).
Install the air filters.
(1)
(2)
(3)
(4)
When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant (R22)
inside the refrigerant cycle.
When adding refrigerant, add the refrigerant from the
charging valve at the completion of work.
If the units are further apart than the maximum pipe
length, correct operation can not be guaranteed.
(1)
(2)
(3)
CAUTION
AIR PURGE
1. AIR PURGE
Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
Vacuum the indoor unit and the connecting pipes until the pres-
sure in them lowers to below 1.5 mmHg.
Disconnect the service hoses and fit the cap to the charging valve
(Tightening torque : 70 to 90 kgf • cm).
Remove the blank caps, and fully open the spindles of the 2-way
and 3-way valves with a hexagon wrench (Torque : 2-way valve:
70 to 90 kgf • cm, 3-way valve: 100 to 120 kgf • cm).
Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque (200 to 250 kgf • cm).
Fig. 27
Fig. 28
(1)
(2)
(3)
(4)
(5)
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 5 m is charged in the outdoor
unit at the factory.
When the piping is longer than 5 m, additional charging is necessary.
For the additional amount, see the table below.
Between 5 m and 30 m, when using a connection pipe other than that in
the table, charge additional refrigerant with 1.8 oz (40 g) / 3.3 ft (1 m) (Re-
verse cycle model), 0.6 oz (17 g) / 3.3 ft (1 m) (Cooling model) as the cri-
teria.
Additional
refrigerant
Table 6
Heat & Cool
(Reverse cycle)
Cooling
model
16 ft
(5 m)
None
None
33 ft
(10 m)
7.1 oz
(200 g)
3.0 oz
(85 g)
49 ft
(15 m)
14.1 oz
(400 g)
6.0 oz
(170 g)
66 ft
(20 m)
21.2 oz
(600 g)
9.0 oz
(255 g)
99 ft
(30 m)
15.0 oz
(425 g)
82 ft
(25 m)
28.2 oz
(800 g)
12.0 oz
(340 g)
Pipe length
Remove outdoor unit valve cover and connect the power cord and
the outdoor unit connection cord wired at the indoor unit.
Fasten the sheath with a cord clamp.
Fasten the power cord and connection cord with cable clip and
binders as shown in (Fig. 40)
Fig. 38
Fig. 39
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Fig. 40
Install the valve cover.
Fig. 41
(4)
(1)
(2)
(3)
2. REMOTE CONTROL UNIT CODE SWITCHING
Fig. 44
Confirm the remote control unit signal selector switch selection and
printed
circuit board setting.
If these are not confirmed, the remote control unit cannot be operat-
ed for the air conditioner.
Table 7
1. INDOOR UNIT
Operation can be checked by lighting and flashing of the display
section OPERATION, TIMER and VERTICAL SWING lamps.
Perform judgment in accordance with the following.
Fig. 48
Test running
When the air conditioner is run by pressing the remote
control unit test run button, the OPERATION, TIMER and
VERTICAL SWING lamps flash slowly at the same time.
Error
The OPERATION, TIMER and VERTICAL SWING lamps operate
as follows (Table 8) according to the error contents.
Table 8
2. OUTDOOR UNIT
Error
The LED lamps operate as follows (Table 9) according to the
error contents.
Table 9
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high
pressure abnormal, the LED lamp lights continuously for 24 hours,
as long as the power is not turned off.
Jumper wire
Remote control unit
signal selector switch
JM 2
JM 3
Connect
Connect
Connect
Disconnect
Disconnect
Connect
Disconnect
Disconnect
A (Primary setting)
B
C
D
•
•
•
Error display
Error contents
LED
No. 1
Lamp
LED
No. 2
Lamp
Discharge pipe
temperature
abnormal
Discharge pipe
temperature
sensor abnormal
High pressure
abnormal
Outdoor heat
exchanger tem-
perature sensor
abnormal
Outdoor tem-
perature sensor
abnormal
OFF
ON
Lighting
continue
OFF
ON
Lighting
continue
0.5 sec
5 sec
OFF
ON
Puls 1 time
repeated
0.5 sec
0.5 sec
5 sec
OFF
ON
Pulses 2 times
repeated
0.5 sec
0.5 sec
5 sec
OFF
ON
Pulses 3 times
repeated
After setting the remote control unit signal selector
switch, press the ACL button.
6
9
7
5
8
10
11
16
12
15
13
14