![FujiFilm FRENIC HVAC Series Quick Start Manual Download Page 10](http://html1.mh-extra.com/html/fujifilm/frenic-hvac-series/frenic-hvac-series_quick-start-manual_2342490010.webp)
Ph: 1800 987 616 Email: [email protected] Website: www.cse-
4.1.1 Application Parameters for Terminal Control with
0-10Vdc Speed Reference
F 11
Minimum requires function code setting:
Code
Name
Description
Set
F 01
Frequency command
0-10Vdc voltage input to
terminal 12
1
F 02
Operation method
External signals—Terminal
forward
1
F 03
Maximum frequency
50Hz
F 04
Base frequency
50Hz
F 05
Rated voltage at base frequency
415V
F 06
Maximum output voltage
415V
F 07
Acceleration time
30 Sec
F 08
Deceleration time
30 Sec
F 11
Overload level
Motor current rating plate
Amps
F 37
Load selection
Variable torque load
0
F 43
Current limiter
Disabled
0
P 01
Number of poles
As per motor rating plate
4
P 02
Motor rated capacity
As per motor rating plate
kW
P 03
Motor rated current
As per motor rating plate
Amps
P 99
Motor selection
Other motors
4