Fuji Electric RDA36LCTU Service Manual Download Page 21

1. Preparation for pump down

Confirm that the power is off,

and then open the service panel.

2. Pump down procedure

(1) Check the 3-way valves (both at the liquid side and gas 

side) are opened.

(2) Turn the power on.

POWER

MODE

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

(3) Press [PUMP DOWN] switch for 3 seconds or more after

3 minutes after power on.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

LED display lights on as shown in the above figure, and

the fans and the compressor start operating.
If the [PUMP DOWN] switch is pressed while the 

compressor is operating, the compressor will stop, then 

start again in about 3 minutes.

(4) LED display will change as shown below about 3

minutes after the compressor starts. Fully close the 

3-way valve on the liquid pipe side at this stage.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

If the valve on the liquid pipe side is not closed, the 

pump down cannot be performed.

(5) When LED display changes as shown in the below

figure, close the 3-way valve on the gas pipe side tightly.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

If the valve on the gas pipe side is not closed, refrigerant 

may flow into the piping after the compressor stops

Step (5)

Closing direction

Step (4)

Hexagon wrench

Liquid pipe

Gas pipe

Closing direction

(6) LED display changes after 1 minute as shown in the

figure below

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

Fans and compressor stop automatically.
If the pump down is successfully completed (the above 

LED display is shown), the outdoor unit remains stopped 

until the power is turned off.

(7) Turn the power off.

ERROR

TEST

RUN

PUMP

DOWN

LOW NOISE

PEAK CUT

POWER

MODE

(L1) (L2) (L3) (L4) (L5) (L6) (L7)

PUMP DOWN is completed.

(Note)

To stop pump down, press the [PUMP DOWN] switch 

 

again.
To start the pump down again after the compressor is 

automatically stopped due to an error, turn the power 

off and open the 3-way valves. Wait 3 minutes, turn the 

power on and start the pump down again.

When starting the operation after completion of the pump 

down, turn the power off, and then open the 3-way valves. 

Wait 3 minutes, turn the power on and perform a test run 

in the “COOL” operation mode.

PUMP DOWN (Refrigerant collecting operation)

OUTDOOR UNIT

SPECIAL INSTALLATION

SETTING

Perform the following procedures to collect the

refrigerant when moving the indoor unit or outdoor unit

2008.11.21

20

 

WARNING

Never touch electrical components such as the terminal 

blocks or reactor except the switch on the display board. 

It may cause a serious accident such as electric shock.

 

CAUTION

Perform the pump down operation before disconnecting 

any refrigerant pipe or electric cable.

Collect refrigerant from the service port or the 3-way 

valve if pump down cannot be performed.

In case of a group control system installation, do not turn 

the power off pump down is completed in all outdoor 

units.

(Group control system installation described in “SPECIAL

INSTALLATION METHODS” in the installation manual of 

the indoor unit.)

Operate [PUMP DOWN] switch on the display board in 

the manner described below.

LED display part

PUMP DOWN

switch

Service port

Service port cap

Service hose

Reactors

Charging port

Charging port cap

3-way valve

Service hose

Terminal blocks

Summary of Contents for RDA36LCTU

Page 1: ...it RDA36LCTU RDA45LCTU ROD36LATT ROD45LATT CONTENTS SPECIFICATIONS 1 DIMENSIONS 2 REFRIGERANT SYSTEM DIAGRAM 4 CIRCUIT DIAGRAM 5 ERROR DETECTION 6 INDOOR PCB CIRCUIT DIAGRAM 9 OUTDOOR PCB CIRCUIT DIAG...

Page 2: ...RENT 9 5 A 8 5 A 3 0 L hr 6 200 m3 h AIRCIRCULATION INDOOR 2 100 m3 h 1 850 m3 h 6 200 m3 h 6 900 m3 h 400 V 50 Hz 3 4 W 1 200 r p m 1 020 r p m 840 r p m 750 r p m MFG 45RVN 1 350 r p m 1 150 r p m 9...

Page 3: ...DIMENSIONS Unit mm INDOOR UNIT 1 135 1 177 1 015 139 264 264 264 107 32 114 66 32 54 240 281 168 283 477 700 173 161 40 39 240 132 240 16 121 270 2008 11 20 2...

Page 4: ...2008 11 20 3 31 12 330 900 1290 9 21 OUTDOOR UNIT unit mm 650 400 370 air flow...

Page 5: ...ner Expansion Valve Strainer 3 Way Valve 3 Way Valve Accumulator Refrigerant Pipe 9 52mm 3 8 Refrigerant Pipe 15 88mm 5 8 Thermistor Discharge Thermistor Room Heat Exchanger Heat Exchanger Thermistor...

Page 6: ...TH 1 2 3 L1 L2 L3 N COMPRESSOR CM S C R THERMISTOR HEATSINK INV TEMP CAPACITOR PCB ASSY REACTOR x 3 EV FM FM 4WV PS THERMISTOR HEAT EXCHANGER MID THERMISTOR HEATSINK P F C TEMP THERMISTOR DISCHARGE TE...

Page 7: ...CN14 3 CN13 1 CN13 2 CN13 3 CN13 4 CN13 5 CN13 6 CN5 1 CN5 2 CN13 7 CN7 1 CN7 2 CN8 1 CN8 2 CN6 1 CN6 2 CN10 1 CN10 2 THERMISTOR ROOM TEMP THERMISTOR PIPE MID TEMP REMOTE CONTROL UNIT TERMINAL BOARD 1...

Page 8: ...10K 1 10W 1 2 3 C37 0 1 F 1000P R x 3 C35 C12 C11 R67 1 0K 1 10W 5V 1 0K 1 10W X 3 R63 R64 R65 10K 1 10W x 3 R66 R32 R23 R24 13 5V R26 10K 1 10W R25 1 0K 1 10W 5V C14 1000P R C16 0 01 F R29 390 1 10W...

Page 9: ...G5NB 1A 13 5V RC101 120 0 2 CN106 B2P3 VH B E DRAIN PUMP 2 1 IC26 10 IC26 14 1 3 4 2 2 1 3 2 1 C116 0 01 B 5V R112 330 1 10W L102 BLm18 AG601 I C101 TLP621 GB L103 BLm18 AG601 4 3 1 2 4 2 3 1 K101 G5...

Page 10: ...1747052 4 G I C7 92 2P YELLOW CN801 MAIN PCB COM 1971032 8 G I C2 0 8P WHITE 1 2 3 4 5 6 7 8 1 2 3 4 5 6 CN800 FLASH B06B PASK WHITE CN803 HEATSINK TH 1971032 2 G I C2 0 2P RED 1 2 CN802 CT OUT 2 187...

Page 11: ...P_LED2 P_LED3 I C3 uLN2003ADR C51 0 022 F 5V C31 0 1 F 12V CR1 CR2 RE1202 0 2 120 x 2 12V 12V K1 K2 G5NB 1A x 2 3 1 2 4 3 1 2 4 16 15 14 13 12 11 10 9 1 2 3 4 5 6 7 8 1C 2C 3C 4C 5C 6C 7C COM 1B 2B 3...

Page 12: ...9 0 1 F Overcurrent Detection PFC Control Hysteresis Comparator C385 1000P B R382 1 0K R385 4 7K R388 10K R391 3 9K 1 R394 100K 1 R397 1 0K 1 I C380 2 BA2901F R398 10K 1 R399 10K 1 R393 100K 1 C384 10...

Page 13: ...7U I C470 2 BA2902F I C470 1 BA2902F I C470 4 BA2902F 15V 3 1 2 D473 DAN217U 5V C633 100 25V C632 0 1 F C631 0 1 F 15V C630 330 35V C634 0 1 F D630 1SS355 I C630 NJM7805 1 2 3 I O G 3 2 1 2 1 3 4 2 1...

Page 14: ...11 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 VUFS P VUFB VP1 UP VVFS U VVFB VP1 VP VWFS VWFB VP1 VPC V W WP NU VN1 VNC C I N NV CFO FO UN NW VN WN R940 R944 0 08 5W x 5 D908 US1J C858 4 7 50V R...

Page 15: ...TNR P202 NSHV4 15A FH204 FH205 P201 NSHV4 15A FH202 FH203 FH200 FH201 P200 NSHV4 15A VA201 820V TNR VA200 820V TNR VA202 820V TNR TM203 TM204 TM205 L3 OUT BLACK L2 OUT WHITE L1 OUT RED 5 6 3 4 1 2 5 6...

Page 16: ...V C700 660 450V C701 660 450V R703 68K RS 5W R702 68K RS 5W R701 68K RS 5W R700 68K RS 5W W700 P I N ORANGE PURPLE N I N W701 W702 P OUT YELLOW W703 N OUT BLUE 2008 10 21 15 OUTDOOR UNIT CAPACITOR PCB...

Page 17: ...ture sensor outlet error 0A Outdoor temperature sensor error 0E Heat sink thermistor Inverter error 15 Compressor temperature sensor error 1d 2 way valve temperature sensor error 1E 3 way valve temper...

Page 18: ...s 5 times Heat sink thermistor P F C error 4 times 2 times Indoor manual auto switch abnormal 4 times 4 times Power supply frequency detection error 5 times 2 times IPM protection 5 times 3 times CT e...

Page 19: ...manual of the indoor unit Operate ENTER TEST RUN switch on the display board by the following procedure LED display Controller PCB Assy of control unit part Operation mode Upper HEAT Lower COOL ENTER...

Page 20: ...or For details refer to the right table 2 Error code check table Number of blinks LED Error type 1 Serial forward transfer error 2 Discharge thermistor error 3 Heat exchange thermistor outlet error 4...

Page 21: ...pump down is successfully completed the above LED display is shown the outdoor unit remains stopped until the power is turned off 7 Turn the power off ERROR TEST RUN PUMP DOWN LOW NOISE PEAK CUT POWER...

Page 22: ...Evaporator Assy 3 Drain Pan Sub Assy 2 Main Panel Sub Assy 10 Intake Frame Assy 4 Drain Cap Thermistor Spring A Ref Description Part number 9374516018 9374509010 9374508020 9374512010 9374510016 Seal...

Page 23: ...e Wall Assy 29 Bracket Eva R 28 Fan Motor Motor Band Ref Description Part number 9374230013 9356531046 9374504015 21 Casing B Bracket Eva L Panel Control Box 27 Motor Mount 25 Casing A 9374234011 9374...

Page 24: ...ox A 9374219018 49 Control Cover B 9374222018 44 One Touch Bush 9374407019 45 Terminal 3P 9703345012 46 Terminal 3P 9306489045 42 Power Supply PCB Assy 9707398151 47 Reactor Assy 9707457018 Room Therm...

Page 25: ...rd Cover 9378111011 7 Right Panel Sub Assy 9374416158 8 Pipe Cover Rear 9378862012 Protective Net 9375381042 6 Pipe Cover Front 9378861015 5 Sevice Panel Sub Assy 9374415076 4 Grip Side 9374173013 3 F...

Page 26: ...n Assy Motor DC Brushless Condenser A Assy Condenser B Assy Separate Wall Sub Assy Reactor Assy Reactor Holder Sub Assy Base Assy Valve Plate Compressor Cover A Compressor Cover B 9366378020 13 Motor...

Page 27: ...008 11 06 26 Coil Expansion Valve Expansion Valve Assy 4 way Valve Assy Solenoid OUTDOOR UNIT Accumulator 3 way Valve Assy 3 way Valve Assy Compressor Assy Accumulator Holder Comp Plate Assy Strainer...

Page 28: ...n PCB Assy 36 51 9707627022 Main PCB Assy 45 Ref OUTDOOR UNIT Parts number Description PFC PCB Assy Capacitor PCB Assy Inverter PCB Assy Reactor Assy Terminal 59 58 60 61 62 63 64 Thermistor Discharge...

Page 29: ...1 small 1 For fixing the drain hose Fixing the remote cord Insulates the drain hose and vinyl hose 2007 10 25 28 Name and Shape Q ty Part number Part number Application 1 2 OUTDOOR UNIT For drain pipi...

Page 30: ...0811G3562...

Reviews: