![Fuji Electric OPC-PRT Instruction Manual Download Page 72](http://html1.mh-extra.com/html/fuji-electric/opc-prt/opc-prt_instruction-manual_2341941072.webp)
71
Figure 60: Configure Generic Default AOI
11) The program is now complete.
12) Save, download and run the program.
9.2.12.2 ControlLogix Example: AC/DC Drive Profile Add-On Instruction
The AC/DC drive profile add-on instruction is a simple interface to command and monitor the inverter. It
is based on the assembly instances 21 & 71. The add-on instruction is optional and provided for user
convenience.
1)
Complete all the steps in section 9.2.11. Please note that the Assembly Input Instance must be
changed to 71 and the Assembly Output Instance must be changed to 21. Refer to Figure 61.
Figure 61: AC/DC Drive Profile Generic Ethernet Module Configuration
2)
Right click on “Add-On Instructions” in the controller organizer
view and select “Import Add-On Instruction”. Browse and import
the AC/DC drive profile add-on instruction. Refer to Figure 62.
3)
Double click “Controller Tags” in the controller organizer view and
select the “Edit Tags” tab at the bottom.
4)
Create the tags in Figure 63.
Figure 62: AC/DC Drive
Profile Add-On Instruction