![Fuji Electric OPC-PRT Instruction Manual Download Page 103](http://html1.mh-extra.com/html/fuji-electric/opc-prt/opc-prt_instruction-manual_2341941103.webp)
102
Frequency
Max
0x4000
x
Speed
Running
NIST_A
=
Equation 9
The “Max Frequency” term which appears in Equation 8 and Equation 9 is obtained from the setting of
inverter function code F03 (maximum frequency 1).
A normalized value of 0x4000 corresponds to 100% of the maximum frequency. A positive normalized
value indicates forward rotation and a negative normalized value indicates reverse rotation.
The value of F03 is read by the interface card only at boot-up. If the value of this function
code is changed, then the interface card must be rebooted in order for it to read the new
value from the inverter.
9.5.5.4
PROFIdrive State Diagram
The state diagram is displayed in Figure 88.
Figure 88: PROFIdrive State Diagram