Fuji Electric OPC-E1-RS Installation Manual Download Page 2

 

 

Installation Manual

RS-485 Communications Card "OPC-E1-RS"

 

 

 

Thank you for purchasing this RS-485 communications card "OPC-E1-RS." Installing this card to your FRENIC-Multi enables 
RS-485 communication.

 

1. Check that:

 

(1)  An RS-485 communications card is contained in the package.

 

(2)  The RS-485 communications card is not damaged during transportation--no 

defective devices, dents or warps.

 

(3)  The model name "OPC-E1-RS" is printed on the RS-485 communications 

card. (See Figure 1.)

 

If you suspect the product is not working properly or if you have any questions 

about your product, contact the shop where you bought the product or your local 

Fuji branch office.

 

 

Figure 1                 Figure 2 

Hooks 

CN3

Model 
name 

SW9 

SW10 

 

 

 

 

Figure 3 

 

2. Installation

 

When handling the RS-485 communications card and interface PCB, take any 

antistatic measure or hold their hooks taking care not to directly touch their 

circuit boards; otherwise, the static electricity charged in your body may damage 

them. 
(1)  If more than one inverter is connected in your system and you will install 

the RS-485 communications card to the terminal inverter, then be sure to 

turn SW9 (shown in Figure 1) on the card to the ON position.

 

(2)  If the terminal cover is installed, insert your finger into the opening (next to 

"PULL") provided in the bottom of the terminal cover and pull the cover 

towards you. 

 

 For details on how to remove the 

terminal cover

, refer to the 

FRENIC-Multi Instruction Manual (INR-SI47-1094-E), Chapter 2, Section 
2.3 "Wiring."

 

(3)  If the interface printed circuit board (interface PCB) is installed, push the 

hooks provided on both ends of the PCB and pull it up with both hands as 

shown in Figure 3. (Store the removed interface PCB for future use.) 

(4) Connect the CN3 connector (shown in Figure 2) on the RS-485 

communications card to the connector on the inverter until it clips into 

place. 

(5) For 

inverters 

of 

less than 5.5 kW

: Before reinstalling the terminal cover, cut 

off the two barriers (see Figure 4) of the RS-485 communications cable 

outlets on the main circuit terminal block cover. 

(6)  Fit the latches provided on the upper end of the terminal cover into the 

openings in the inverter, then close the terminal cover, taking care not to 

pinch control signal lines. 

 

 When  reinstalling  the 

terminal cover

, refer to the FRENIC-Multi 

Instruction Manual (INR-SI47-1094-E), Chapter 2, Section 2.3 "Wiring."

 

 

 

For inverters of less than 5.5 kW: When performing the wiring for the 

main circuit terminals, remove the RS-485 communications card 

beforehand.

 

 

 

Figure 4 

 

 

When replacing the conventional FVR-E11S series with the FRENIC-Multi series, be sure to turn signal switch SW10 to the

"2" position (in Figure 1). The pin assignment of this RS-485 communications card is different from that of the FVR-E11S's 

RJ-45 connector used for RS-485 communication. For details, refer to the RS-485 Communication User's Manual

(MEH448b). 

•  If a communications error occurs due to a communications cable too long and the transmission speed too high, wind 3 turns 

of a communications cable through a noise reduction core (e.g., MA055 38.1/19/12.7A manufactured by JFE Ferrite 

Corporation).

 

Hooks

Interface PCB 

RS-485 communications 
card 

Main circuit terminal 
block cover 

Barriers of the RS-485 
communications cable 
outlets 

 

 

Fuji Electric FA Components & Systems Co., Ltd.

 

 

Mitsui Sumitomo Bank Ningyo-cho Bldg., 5-7, Nihonbashi, Odemma-cho, Chuo-ku, Tokyo, 103-0011, Japan 
Phone: +81 3 5847 8011        Fax: +81 3 5847 8172 
URL: 

http://www.fujielectric.co.jp/fcs/

 

 

 

INR-SI47-1089

 