background image

 

 

PID SET UP WITH FRENIC Eco series inverter. 

9

 
J17. PID Control (Starting frequency).  
Specifies the starting frequency. Select a frequency higher than the slow flowrate 
level stop frequency. If the specified starting frequency is lower than the slow flowrate 
level stop frequency, the later stop frequency is ignored; the slow flowrate level stop 
is triggered when the output of the PID processor drops below the specified starting 
frequency. 
Factory setting is 0 Hz. 

 

 
3

rd

 Step: 

Tuning of the System

 

 
 

  Set acceleration (function F07) and deceleration times (function F08) of the  

inverter as small as possible. Use 1.00 second as starting point. 

  Check that the Frequency Limiter (functions F15, F16) do not obstruct the 

operation of the PID controller or the system. 

  Check if the sensor levels and responses are fitted for the application. When 

controlling a process up to 8 Bar do not use an 8 Bar sensor but for example a 
12 Bar sensor. 

  Try to keep the set-point of the PID to a lower value of its operating range. 

This means for example when using 0-10V input, choose a source that has an 
output value of 8 Volt at the set value. 

  When setting up a control system make sure the motor has sufficient capacity. 

There is no good control when the set value of a compressor is set to 4 Bar 
when the maximum achievable pressure of the system is 4 Bar. 

  Measure or estimate the time lag between the process control and the 

feedback signal of the process. It is important to anticipate on the time lag of 
the process or instability can easily occur. It is important to know this time. 
One can determine this time in many ways. One way can be to change the 
set-point of the controller and monitor the feedback value for a change. The 
time it takes is the time lag of the control loop. 

 

When setting up a PID, we start disabling the I and D action by programming them to 
0. Then we set a P value of 1.000 and we operate the inverter. When the process 
oscillates we lower the gain of P. When the process does not reach the set-point but 
only goes half way of the set-point we can slowly increase the P gain until 80-90% is 
achieved. We have to test the response of the system by adding different loads. 
When the process starts to oscillate we have to lower the P gain again until a stable 
control is achieved. It may be possible that the feedback does not reach the set-point. 
This will be solved with the I action of the PID controller. At this moment it is only 
important that no oscillation occurs when the load of the process is changed.  
 
When we are sure that the system does not oscillate with the P setting we can start 
to optimise the control loop by adding some I action. We could start by entering the 
value of the time lag of the process as the I parameter. After this, we have to test if 
the system is stable when applying different loads. 
 

Summary of Contents for Frenic Eco Series

Page 1: ...ng more Preferably 1 5 times more i e 3 Bar Does it have an output signal that can be connected directly to the FRENIC Eco input FRENIC Eco has inputs for 0 10 V and 4 20 mA signals 3 PID Basics 3 1 P...

Page 2: ...P part only depends on the momentary difference error between the set value and the feedback The drawback using only a P controller is that the more the feedback signal approaches the set value the sm...

Page 3: ...t Base frequency 1 This function sets the rated value of the voltage output to motor 1 in volts Note that a voltage greater than the supply input voltage cannot be output Factory setting is 400 V F06...

Page 4: ...miter Low This function sets the lower limit for the setting frequency in Hz Recommended value for PID control is zero or at least very low Factory setting is 0 Hz Motor parameters P01 Number of motor...

Page 5: ...d current This function sets the no load exciting current of motor 1 in Amperes Factory setting depends on the inverter size P07 Motor 1 R1 setting This function sets the primary resistance R1 of moto...

Page 6: ...Function This function is used to setup the function that will be displayed in the LED display during operation The alternatives related with the PID controller are 10 PID process command value 12 PID...

Page 7: ...ommand 1 3 Enable terminal command up down control 4 Command via communication link When setting J02 to 1 we have to specify the source of this command In order to do so we have to program one of the...

Page 8: ...gned for pump applications These function codes specify the data for the slow flowrate stop in pump control a feature that stops the inverter when there is no water consumption Slow flowrate stop func...

Page 9: ...f the system is 4 Bar Measure or estimate the time lag between the process control and the feedback signal of the process It is important to anticipate on the time lag of the process or instability ca...

Page 10: ...ment To check that PID command and or PID feedback signals are connected properly to the inverter select option 4 I O CHECK from the Multifunction Keypad TP G1 menu and then go to the fifth screen pus...

Page 11: ...ime 1 E40 7 00 7 bar max E41 0 00 0 bar min E43 10 PID set point value PID parameters J01 1 PID active forward operation J02 0 PID set value from keypad E62 5 PID feedback value by current input C1 J0...

Page 12: ...parameters J01 1 PID active forward operation J02 1 PID set point by PID process command 1 E62 3 PID process command 1 assigned to terminal 12 E63 5 PID feedback value assigned to terminal C1 J03 PID...

Reviews: