FRC

P. 4 / 4

TNFFRCDd-E

Fuji Electric France S.A.S.

46, rue Georges Besse - ZI du Brézet - F-63039 Clermont-Ferrand Cedex 2 - France

Tél: +33 4 73 98 26 98     Fax: +33 4 73 98 26 99     http://www.fujielectric.fr

1

2

3

+

4

SENSOR 

INPUT & 

OUTPUT

POWER 

SUPPLY

+

Flameproof Enclosure

Transmitter

IECEx/ATEX Flameproof

Sensor Assembly

External Earthing Terminal

Hazardous Location

Zone 1 and 2

Non-Hazardous Location

PS+

PS– 

*

2

*

1

INSTALLATION DIAGRAM for IECEx/ATEX FLAMEPROOF MODEL

ELECTRICAL DATA

Power Supply (+ and –)

Supply Voltage : 12 to 28 V
Output Current : 4 to 20 mA
(Burnout Current : 24 mA)

Sensor Circuit (1 to 4)

Input Signal : 1.0 V max

NOTES

*

1

 :

*

2

 :

*

1

Install per local installation codes.
IECEx or ATEX approved cable entries or stopping plugs required.

Sensor assembly must be IECEx or ATEX approved for appropriate hazardous location.

Summary of Contents for FRC

Page 1: ...1 Yes die cast aluminium 2 Yes stainless steel casting 2 SAFETY APPROVAL A None C IECEx ATEX flameproof for FRC1 FRC2 E ATEX intrinsically safe 3 LCD DISPLAY 0 None 1 LCD 4 WIRING CONDUIT 0 None for FRC0 1 1 2 NPT 2 M20 x 1 5 3 PG 13 5 WARNING Explosions could result in death or serious injury The enclosure cover must be fully engaged to meet flame proof requirements Do not remove the enclosure co...

Page 2: ...RC0 in an environment with a high relative humidity exceeding 0 to 95 RH or in a condens ing atmosphere install the unit inside an outdoor enclo sure Model FRC1 FRC2 FLAMEPROOF APPROVAL IECEx Certificate of Conformity IECEx CML 18 0140X Ex db IIC T4 T5 T6 Gb IEC 60079 0 IEC 60079 1 ATEX EU Type Examination Certificate CML 18ATEX1277X II 2G Ex db IIC T4 T5 T6 Gb Zone 1 EN 60079 0 EN 60079 1 Threade...

Page 3: ... to 4 Maximum Output Voltage Uo 6 4 V Maximum Output Current Io 30 mA Maximum Output Power Po 48 mW Maximum External Capacitance Co 20 μF Maximum External Inductance Lo 10 mH NOTES 1 2 In any safety barrier the output current of the barrier must be limited by a resistor R such that Io Uo R The safety barrier must be certified by an EU approved certification body to Ex ia IIC For Zone 1 and 2 Ex ib...

Page 4: ...embly External Earthing Terminal Hazardous Location Zone 1 and 2 Non Hazardous Location PS PS 2 1 INSTALLATION DIAGRAM for IECEx ATEX FLAMEPROOF MODEL ELECTRICAL DATA Power Supply and Supply Voltage 12 to 28 V Output Current 4 to 20 mA Burnout Current 24 mA Sensor Circuit 1 to 4 Input Signal 1 0 V max NOTES 1 2 1 Install per local installation codes IECEx or ATEX approved cable entries or stopping...

Reviews: