5.4 Information on Each Parameter
5.4.1Method of Setting Condition Data
This section shows a typical example of setting the peak hold parameter.
The same method applies to other parameters.
Indication
Name
Setup options
Default
value
PVH
Peak hold setup
PH (peak hold)/VH (valley hold)/PVH (peak-valley hold)
PH
RANG Measurement range setup
*1
*1
AVG
Number of averaging operations
setup
1/2/4/8/10/20/40/80
1
MAV
Number of moving average
operations setup
OFF/2/4/8/16/32
OFF
S.UD
Step width setup
1(1digit)/2(2digit)/5(5digit)/0(10digit)
1
BLNK
Indication blank setup
OFF/B-3/B-2/B-1/ON
OFF
UNIT
Unit setup
C/F
C
BAUD Baud rate setup
9600/4800/2400/384(38400)/192(19200)
9600
DATA Data length setup
7(7bit)/8(8bit)
7bit
P.BIT
Parity bit setup
E (even number), O (odd number), N (none)
E
S.BIT
Stop bit setup
2(2bit)/1(1bit)
2
T-
Delimiter setup
CR.LF(CR+LF)/CR
CRLF
ADR
Equipment ID setup
01 to 99
00
A.OUT Analog output setup
OFF/0-1(0 to 1V)/0-10(0 to 10V)/1-5(1 to 5V)/4-20(4 to 20mA)
OFF
B.UP
Digital zero backup setup
OFF/ON
OFF
LINE
Linearization setup
OFF/ON
CLR
I.SEL
Input selection
OC (open collector)/LGC (logic)/MAG (magnet)
O.C
TR T
Tracking zeroing time setup
00 to 99
00
TR V
Tracking zeroing width setup *2 00 to 99
01
SNSR Sensor power setup
10(10V)/05(5V)
10
P
Power on delay time setup
OFF/ON
OFF
PRO
Protect setup
OFF/1 to 30
OFF
U-NO. Unit number indication setup
OFF/ON
ON
S-HI
HI side judgment value setup
-9999 to 9999
1000
S-LO
LO side judgment value setup
-9999 to 9999
500
H-HI
HI side hysteresis setup
-9999 to 9999
0
H-LO
LO side hysteresis setup
-9999 to 9999
0
FSC
Full scale indication value setup -9999 to 9999
*1
FIN
Full scale input value setup
-9999 to 9999
*1
OFS
Offset indication value setup
-9999 to 9999
*1
OIN
Offset input value setup
-9999 to 9999
*1
PS
Pre-scaling value setup
0.001 to 5.000
1.000
PPR
Frequency division setup
1 to 100
1
DLHI
Digital limiter HI value setup
-9999 to 9999
9999
DLLO Digital limiter LO value setup
-9999 to 9999
-9999
AOHI
Analog output HI indication
setup
-9999 to 9999
9999
AOLO Analog output LO indication
setup
-9999 to 9999
0
DEP
Decimal point indication position
setup
None/place of 10
0
/place of 10
1
/place of 10
2
/place of 10
3
None
*2
*2
ZERO Zero input value
-0.300 to 2.000
0.000
SPIN
Span input value
1.000 to 3.000
2.000
SPAN Span indication
0 to 9999
9000
Condition data
Comparator data
Scaling data
Multi-display unit
Single display unit
or
(1) Press the Mode and Enter keys together
during measurement.
(2) Press the Mode key to change to the peak
hold setup mode.
(3) For a single display unit, press the Mode key
to change to the parameter information indication.
(The display automatically changes to this
indication in about 1 second, except right after
COND is indicated.)
(4) Press the Increment key a few times to set to
Valley Hold.
(5) Press the Enter key to return to measurement
mode. (Pressing the Mode key changes to the
next parameter).
5.4.2 Method of Setting Comparator Data
This section explains comparator data and shows a typical example of setting
the HI side judgment value. The same method applies to all other parameters.
Note: The setup conditions are HI side judgment value > LO side judgment
value, HI side judgment value LO side judgment value + LO side
hysteresis, and LO side judgment value HI side judgment value-HI
side hysteresis. If these conditions are not satisfied, an error indica-
tion appears and the display returns to the HI side judgment value
setup.
5.4.3
Method of Setting Scaling Data
This section explains comparator data and shows a typical example of
setting the full scale indication parameter. The same method applies to all
other parameters.
Note: For the Digital limiter, values larger than the DLHI setpoint are
not indicated even if signals greater that the value set in the DLHI
parameter are input (for DLLO parameter, values smaller than the
DLLO setpoint are not indicated).
HI
GO
GO
LO
GO
HI side hysteresis
range
Indicated value
HI side judgment value
LO side judgment value
LO side hysteresis
range
Judgment
900
500
0
1000
300
150
200
HI side judgment value : 900
HI side hysteresis value
200
:
: 300
150
:
LO side hysteresis value
LO side judgment value
Multi-display unit
Single display unit
or
(1) Press the Mode and Enter keys together
during measurement.
(2) Press the Shift key a few times to display the
comparator data menu.
(6) Press the Enter key to return to the
measurement mode (Pressing the Mode key
changes to the next parameter).
(5) Press the Shift key (change digit) and press
the Increment key (change numeric value) to set
to 10.
&
Note:The decimal point in the selected digit
flashes.
(3) Press the Mode key a few times to display the
parameter to be set.
(4) For a single display unit, press the Mode key
to change to the parameter information indication.
(The display automatically changes to this
indication in about 1 second, except for parameter
S-HI right after COM is indicated.)
Note: For the process signal measuring unit, set the full scale input value
to 5.000 for the 1 V range and to 20.00 for the 2 A range, and set the
offset input value to 1.000 for the 1 V range and to 4.00 for the 2
A range.
The following explains the frequency measuring unit. (The same method
applies to the full scale indication parameter.)
Note: For the frequency measuring unit, set the relationship between the
input and indication using the PS and PPR parameters (parameters
of FSC, FIN, OFS, and OIN are not indicated).
The following explains the scaling of analog output (The same method
applies to the full scale indication parameter.)
Note: For analog output scaling, set the indication value for an output
current of 20 mA in the AOHI parameter and set the indication
value for an output current
o
f 4 mA in the AOLO parameter (for 4-
20 mA output).
Indication
Input
5000
10V
Input voltage : 0 to 10V
0 to 5.000
:
Indication
FSC : 5000
FIN
: 9999
OFS : 0
OIN
: 0
DLHI : 3000
DLLO : -2000
DEP : The place of 10
3
is lit.
0
DLLO
DLHI
3000
-2000
Multi-display unit
Single display unit
or
(1) Press the Mode and Enter keys together
during measurement.
(2) Press the Shift key a few times to change to
the scaling data menu.
(6) Press the Enter key to return to the
measurement mode (Pressing the Mode key
changes to the next parameter).
(5) Press the Shift key (change digit) and press
the Increment key (change numeric value) to set
to 10.
&
Note:The decimal point in the selected digit
flashes.
(3) Press the Mode key a few times to display the
parameter to be set.
(4) For a single display unit, press the Mode key
to change to the parameter information indication.
(The display automatically changes to this
indication in about 1 second, except for parameter
FSC right after MET is indicated.)
Indication :
4 to 20mA
0.0 to 500.0
:
Output
AOHI : 5000
AOLO : 0
Output
Indication
20mA
5000
4mA
0
5.4.4Method of Setting Calibration Data
5.4.4.1 Actual Load Calibration
Actual load calibration means that calibration is carried out by applying actu-
ally measured pressure to a sensor such as a load cell connected to the meter.
5.4.4.2 Equivalent Calibration
Equivalent calibration means that calibration is carried out according to the
ratings (specifications) of such a sensor as a load cell. It is not necessary to
connect the sensor or to apply pressure to the sensor.
Multi-display unit
Single display unit
or
(1) Press the Shift, Increment, and Enter keys
together during measurement.
(2) Press the Mode key to change to the actual
load calibration mode.
(6) Press the Enter or Mode key to return to the
measurement mode.
(5) Press the Shift key (change digit) and
Increment key (change numeric value) to set
8000.
&
Note:The decimal point in the selected digit
flashes.
(3) Press the Mode key while applying pressure
that will cause the display to show zero.
(4) For a single display unit, press the Mode key
to change to the parameter information indication.
or
(1) Press the Shift, Increment, and Enter key together
during measurement.
(2) Press the Increment key to select the equivalent
calibration mode.
(12) Press the Enter or Mode key to return to the
measurement mode.
(11) Press the Shift key (change digit) and the
Increment key (change numeric value) to set 2000.
&
Note:The decimal point in the selected digit flashes.
(4) Press the Shift key to display the zero-input setup
mode.
(10) For a single display unit, press the Mode key to
display the parameter information indication.
(3) Press the Mode key to move to the equivalent
calibration mode.
&
(5) Press the Shift key (change digit) and the
Increment key (change numeric value) to set 0.004.
Note:The decimal point in the selected digit flashes.
Note:For a single display unit, the unit
automatically returns to ZERO indication if there is
no key operation for about 8 seconds. In such a
case, press the Mode key to return to the numerical
value indication.
(6) Press the Mode key to change to the span input
value setup mode.
&
(7) For a single display unit, press the mode key to
display the parameter information indication.
(8) Press the Shift key (change digit) and the
Increment key (change numeric value) to set 1.002.
(9) Press the Mode key to change to the span
indicating value setup mode.
Multi-display unit
Single display unit
Instruction Manual for FD5000 Series
6/12
Instruction Manual for FD5000 Series
7/12
Determining the revolution speed (rpm) using the rotary encoder set to 30 pulses per minut
(1)Determine the measurement range by calculating the maximum frequency.
The figure below shows an example where the revolution rises to a maximum speed o
about 100 rpm.
30
×
100
÷
60
Revolution speed per second
Number of pulses per revolution at the
rotary encoder
=
50
Number of pulses per second
(3)The display unit shows 500 if 50 Hz pulse input is measured under range 11 (when
PS=1 and PPR=1 by default). Therefore, the parameters should be set as PS=2 and
PPR=1 so that the decimal point is positioned in the 10
1
digit(100.0 is is indicated 50 Hz
input).
(2)Since the number of pulses determined in (1) is 50 per second (50 Hz), set the range
range 11(for how to set the range, see the section on setting condition data).