![Fuji Electric AR22VQR/VQL Quick Start Manual Download Page 5](http://html1.mh-extra.com/html/fuji-electric/ar22vqr-vql/ar22vqr-vql_quick-start-manual_2341957005.webp)
■
Specifications (indoor use)
Item
Performance
Rated insulation voltage Ui
250 V AC/DC
Durability
Mechanical
250,000 operations
Electrical
100,000 operations (AC-12, DC-13, DC-12)
Operating cycles per hour
900 operations/hour (On-load factor: 40%)
Withstand voltage
Between live section and grounding: 2,000V AC, 1 minute
Between opposite polarity live sections: 2,000V AC, 1 minute
Insulation resistance
Between live section and grounding: 100M
:
or more (500V DC megger)
Between opposite polarity live sections: 100M
:
or more (500V DC megger)
Rated impulse withstand voltage Uimp
2.5 kV
Conditional short-circuit current
1000 A
Short-circuit protective device
gG10A (IEC60269 fuse)
Pollution degree
3 (panel inside: 2)
Vibration
Malfunction: maximum double amplitude: 0.7 mm (maximum: 50 m/s
2
), frequency: 10 to 500 Hz
Durability: maximum double amplitude: 0.7 mm (maximum: 50 m/s
2
), frequency: 10 to 500 Hz
*1
Shock
Malfunction: 150 m/s
2
Durability: 1000 m/s
2
*2
Operational ambient temperature
Non illuminated type: -20 to +60°C, illuminated type: -20 to +50°C (no icing or no condensation)
Storage temperature
-40 to +80°C (no icing or no condensation)
Relative humidity
45 to 85%RH (-5 to +40°C) (no icing or no condensation)
Degree of protection of operator (displaying) section
IP65 (dust-proof, water jet proof): IEC 60529
Degree of protection of terminal section
IP2X (when wired)
Connectable wire
Stranded wire: up to 1.25 mm
2
, 24 to 16 AWG-CU
Solid wire: up to ø1.2 mm, 24 to 16 AWG-CU
*1
: The feature is decided based on the test condition for EN60947-5-5 (1998).
*2
: Except when the switch is mounted upside down.
■
Contact ratings
●
TÜV (EN60947-5-1), CCC (GB14048.5), and JIS C 8201-5-1
Conventional free air thermal current
(rated thermal current)
Ith
Rated operational voltage
Ue
Rated operational current Ie
AC
DC
AC-15 (Inductive load)
AC-12 (Resistive load)
DC-13 (Inductive load)
DC-12 (Resistive load)
5 A
24 V
–
–
1.0 A
2.0 A
120 V
3.0 A
5.0 A
–
–
125 V
–
–
0.22 A
0.4 A
240 V
1.5 A
3.0 A
0.1 A
0.2 A
●
UL/CSA
standards
• AC (cosø = 0.35)
• DC (T
0.95
= 6P, maximum: 300 ms)
Contact rating
Conventional free
air thermal current
120 V
240 V
Contact rating
Conventional free air
thermal current
Making current & breaking current
Code
(rated thermal current) Making current Breaking current Making current Breaking current
Code
(rated thermal current) 125 V
250 V
B300
5 A
30 A
3 A
15 A
1.5 A
R300
1 A
0.22 A
0.11 A
●
NECA C 4521
Conventional free air thermal current
(rated thermal current)
Ith
Rated operational voltage
Ue
Rated operational current Ie
AC
DC
AC-15 (Inductive load)
AC-12 (Resistive load)
DC-13 (Inductive load)
DC-12 (Resistive load)
5 A
24 V
–
–
1.0 A
2.0 A
110 V
3.0 A
5.0 A
0.22 A
0.4 A
220 V
1.5 A
3.0 A
0.1 A
0.2 A
■
Contact reliability
FUJI has confirmed that the product can be used in 1mA circuit conditions
at 5V AC or DC.
The operable range, however, may vary depending on the operational
ambient conditions and type of load.
Type of lamp
Luminous color Operational lamp
voltage
Current consumption
LED lamp
Red
24 V AC/DC
7.5 mA AC, 7.5 mA DC
Note: The LED lamp of these products cannot be replaced.
■
Lamp rating and current consumption
■
Dimensions, mm
●
AR22VQR
●
AR22VQL
●
AR22VPR
●
AR30VPR / VPL
Side indicator (green)
42
42
ø40
47.5
32
Ring packing
Washer
Terminal screw M3.5
Terminal cover
Panel thickness
1 to 6
Nut
ø42
Side indicator (green)
ø40
47.5
32
Ring packing
Washer
Terminal
cover
Panel thickness
1 to 6
Nut
ø42
Side indicator (green)
ø65
47.5
32
Ring packing
Washer
Terminal
cover
Panel thickness
1 to 6
Nut
56
43
ø44
Nut
Ring packing
Terminal
cover
Panel thickness
1 to 6
ø44