FSK-RAP816-V2015.04
35
RhinoBus terminals or for modules that are plugged onto the main
control panel PCB.
IP Module
These options allow the IP Module to be configured.
Locations:
6401
- IP Address
6402
- Subnet Mask
6403
- Gateway Address
6404
- Port Number
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in the address or port. When finished press
Enter
to accept or
Clear
to cancel.
IP Address
A valid IP address must be assigned to the module. It must be
entered in dot-
decimal notation, e.g. “192.168.0.58”. Enter
Bypass
& 3
to
insert a “.”.
Subnet Mask
The subnet mask used on the network must be assigned to the
module. It must be entered in dot-decimal notation, e.g.
“255.255.255.0”. Enter
Bypass & 3
to
insert a “.”.
Gateway Address
The gateway address (normally the ADSL router) used on the
network must be assigned to the module. It must be entered in dot-
decimal notation, e.g. “192.168.0.1”. Enter
Bypass & 3
to insert a
“.”.
Port Number
A valid port number must be assigned to the module. It must be
entered as a decimal number, e.g. “8888”.
7. Communicator (Optional)
This section covers programming of the communicator options, for
systems fitted with an optional communicator (GSM or Dialler).
ARC 1-4: Telephone Number
This set of options allows the telephone number to be programmed
for each ARC.
Locations:
7001
to
7004
ARC 1 to 4: Telephone Number.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in the telephone number. When finished press
Enter
to accept or
Clear
to cancel.
ARC 1-4: Account Number
This set of options allows the account number to be programmed
for each ARC.
Locations:
7011
to
7014
ARC 1 to 4: Account Number.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in the account number. When finished press
Enter
to accept or
Clear
to cancel.
ARC 1-4: Protocol
This set of options allows the protocol type to be programmed for
each ARC.
Locations:
7021
to
7024
ARC 1 to 4: Protocol.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in 1 digit protocol option from the list below or press
i
to scroll
through list. When finished press
Enter
to accept or
Clear
to cancel.
0
Disabled
The selected ARC is disabled.
1
Contact ID
The selected ARC is configured for Contact ID protocol. When
triggered, the communicator will call the telephone number and
attempt to communicate with the alarm receiver using Contact ID
protocol.
2
Reserved
The option is reserved and should not be selected.
3
Reserved
The option is reserved and should not be selected.
4
SMS Text
The selected ARC is configured for SMS protocol. When triggered,
the communicator will send a SMS text message via the GSM
network to the number programmed ARC Telephone Number.
ARC 1-4: Protocol Options
This set of options allows the protocol options to be programmed
for each ARC.
Locations:
7031
to
7034
ARC 1 to 4: Protocol Options.
Entry Mode:
Enter 4 digit location followed by
Enter
, then use
key
1
to toggle options from the list below on or off. When finished
press
Enter
to accept or
Clear
to cancel.
1
Switch to Next ARC on failed Attempt
On: The communicator switches to the next ARC in the sequence,
if the current ARC attempt fails.
Off: The communicator continues dialling the selected ARC until all
its attempts have been used.
ARC 1-4: Call Sequence/Attempts
This set of options allows the call sequence to be programmed for
each ARC.
Locations:
7041
to
7044
ARC 1 to 4: Call Sequence/Attempts.
Entry Mode:
Enter 4 digit location followed by
Enter
, then key
in the call sequence number. When finished press
Enter
to accept
or
Clear
to cancel.
The call sequence is entered as a string of digits; each number
indicates the calling method:
1 = Reserved for future use
2 = Reserved for future use
3 = IP Module
4 = FSK Gateway
Summary of Contents for RHINO 816