FSH EcoLock HL1260 Installation Manual Download Page 2

 

 

        

2

                                                      

         

Oct 2015 

 

FSH HL1260 Installation Manual 

Power Input

 

11-30VDC 

Power Consumption

 

Minimum 1A Regulated Power Supply recommended 
Locking/unlocking cycle current is 0.25 to 1A depending on the load. 
After locking/unlocking the current drops down to ~0.015A(15mA) 

Monitoring switch specifica-
tion

 

Bolt changeover switch             30VDC 0.1A Max 
Door position reed switch          30VDC 0.35A Max 

Wiring Requirements  
PTL (Fail Safe)

 

 

Three Wire Configuration (Recommended)

 

Black    0v 
Red   

Continuous Positive 11-30VDC 

Blue   

Access control. Connect to positive to activate the hook. 

Two Wire Configuration (Not Recommended)

 

Black    0v 
Red and blue are connected together. 

Wiring Requirements 
PTO (Fail Secure) 

Three Wire Configuration (Recommended)

 

Black    0v 
Red   

Continuous Positive 11-30VDC 

Blue   

Access control. Connect to positive to activate the hook. 

(Strike plate magnet must be present) 

Two Wire Configuration

 

There is no 2 wire configuration for PTO (Fail Secure) operation 

Wiring

 

Bolt Position Monitoring

 

(unlocked position)

 

White    

-(NO) 

Purple   

-(COM) 

Orange       -(NC) 

Wiring

 

Door Position Monitoring

 

 

Green -Reed switch 
Green -Reed switch 
Normally Open, with door open 
The door has to be closed to activate the Door Position Monitoring. The lock has 
to be within 3mm to activate the DPS. 

Durability

 

Meeting Australian Standard  AS4145.2 - 2008 

400.000 operating cycles 
Durability D7 

Operating Temperature

 

-20 to +60 degree Celsius. 

Maximum Door Gap

 

3mm between faceplate and strike plate.  

Door Gap Adjustment 

The activation gap between the door and frame is adjustable to compensate 
for varying door materials door  

Mounting options 

1.  Recess mounted - as supplied with lock and strike plate 
2.  Surface Mount - Lock or strike plate fits into the surface mount  box 

(HL1260BOX), two required for surface mounting lock and striking plate. 

Certifications

 

CE, C-Tick, 

4.  TECHNICAL DATA 

Accessories 

   

HL1260-SM 

Surface mount box (single) for HL1260 lock OR faceplate. NOTE: 2 required for full  
surface mounting option 

Spare Parts 

   

HL1260-FP 

Standard Strike Plate for HL1260 

5.  ACCESSORIES AND ORDERING INFORMATION 