![Frost Fighter IDF 350LPNG Installation - Operation/Maintenance Instructions And Parts List Download Page 10](http://html1.mh-extra.com/html/frost-fighter/idf-350lpng/idf-350lpng_installation-operation-maintenance-instructions-and-parts-list_2339965010.webp)
SEQUENCE OF OPERATION
1-Flip toggle switch to either manual or thermostat position.
2-Red LED light on ignition controller will come on for 1 second
3-Burner fan motor will start, unit will pre-purge for 45 seconds
4-Spark ignitor energized for 4 seconds, gas solenoid valves will open during 4 second TFI ( trial
for ignition)The unit has three trials for ignition before lockout.
5-Burner lights, ignitor stops and flame current is sensed by ignition controller.
6-When heat exchanger reaches certain temperature ( temperature setting on fan switch) the fan
switch will make and start supply fan.
7-When unit is shut off, burner will shut down and supply fan will run until heat exchanger
temperature is below fan switch set point.
LP/NG TROUBLE SHOOTING GUIDE
*ALWAYS CHECK FOR SUFFICIENT POWER, GAUGE CORD, POLARITY AND GAS
PRESSURE .POWER AND GAS SUPPLY MUST ALWAYS BE SHUT OFF/DISCONNECTED
BEFORE REMOVING OR REPLACING ANY COMPONENTS ON THE HEATER*
1-UNIT WILL NOT START
A- Check for 115 volts AC across terminals 1 and 2. If no voltage check power source.
B- Check for power across terminals 2 and 3. If no power, inspect toggle switch or
thermostat, replace if faulty
C- Check the thermal overloads on burner supply fan motor. Reset by pushing the red
button on motor housing.
D- Ensure proper connection to burner fan. If power is at connection, and neutral wire
secure, replace burner motor.
2-RED LED LIGHT DOES NOT FLASH ON START UP
A- Check for power across terminals 2 and 4. If no power remove high limit cover and check
for power on high limit. If no power there inspect air switch and tubing. Adjust and/or replace as
necessary. If high limit powered on one side only, replace high limit.
B- Check power at 2 amp fuse. Replace if faulty.
C- Check across 120v side of transformer for power. On 24v side, should be 24v. If not
replace transformer.
D- Check across 5 amp fuse for power. Replace if faulty.
E- Check L1 connection to terminal 4, ensure good connection.
F- Ensure proper ground at gas primary.
G- Bad controller, check LED for steady on or flashing codes.
H-If LED light stays on during pre-purge cycle, replace ignition controller.
3-BURNER WILL NOT IGNITE.
A- Always make sure gas supply pressure is 14” (½ lb) or less as over that amount could
cause damage to manifold regulator.
B Check gas pressure at 1/8” tap on elbow of manifold. Ensure pressure is correct (1.2” for
IDF200, 1.8” for IDF350 and 3.0” for IDF500). If no pressure there, remove cover and check for 24v
across solenoid valve wires. If voltage present, replace solenoid valve.
C- If no voltage, at solenoid valve, check gas primary control to ensure wired and grounded
properly. If wired properly, and still no voltage to solenoid replace gas primary.
D- Remove the electrode assembly form burner housing. Shut off all manual gas valves
then reset the unit. Install jumper wire between terminals 3 and 4. Lay electrode assembly across
top of burner housing. Carefully check for spark across the ignition gap after 34 second pre-purge.
If no spark, check for 120VAC at ignition transformer. If power there, replace transformer, no
power, replace gas primary. If spark is arcing at another point other tan tip of spark rod, ensure
spark rod is in correct position. If it is then replace spark rod. After test remove jumper from
terminals 3 and 4.
8
Summary of Contents for IDF 350LPNG
Page 12: ...10...