Status codes –
Class 9
Class 9 status codes only affect the Fronius Solar Battery. These are only displayed on
the system monitoring page and are not shown on the inverter display.
Code
Description
Behaviour
Remedy
975
Software on device is incon-
sistent
The inverter is not feeding
any energy into the grid
Update inverter firmware; *)
976
Unregistered battery module
detected
Battery operation not pos-
sible, feed-in resumes
Enter activation key for battery
module; *)
977
Incorrect number of battery
modules connected to
Fronius Solar Battery
Too many modules detec-
ted: Battery operation not
possible
Too few modules detected:
Error message output,
operation resumes
978
Communication error
between Fronius Symo
Hybrid and Fronius Solar Bat-
tery
Battery operation not pos-
sible, feed-in resumes
Check wiring; **)
979
Communication error
between Fronius Symo
Hybrid and Fronius Solar Bat-
tery
Battery operation not pos-
sible, feed-in resumes
Displayed in standby mode, if
not in standby mode - check
wiring; **)
980
No communication between
Fronius Symo Hybrid and
Fronius Solar Battery
Battery operation not pos-
sible, feed-in resumes
Switch on Fronius Solar Battery;
check wiring; **)
981
Software version of Fronius
Solar Battery is inconsistent
Battery operation not pos-
sible, feed-in resumes
*)
983
Communication error
between battery controller
and battery modules
Battery operation not pos-
sible, feed-in resumes
Check wiring in Fronius Solar
Battery; check numbers of indi-
vidual battery modules; check
termination plug
984
Battery controller has
stopped Charge mode
Battery operation not pos-
sible, feed-in resumes
Check error message on
Fronius Solar Battery display; *)
985
Undervoltage at Fronius
Solar Battery
Fronius Solar Battery has
tripped due to under-
voltage. Battery operation
not possible, feed-in
resumes
*)
986
Overtemperature at Fronius
Solar Battery
Fronius Solar Battery has
tripped due to overtemper-
ature. Battery operation
not possible, feed-in
resumes
Reduce ambient temperature;
switch off Fronius Solar Battery
and activate it again after wait-
ing an appropriate amount of
time; *)
987
Undertemperature at Fronius
Solar Battery
Fronius Solar Battery has
tripped due to undertem-
perature. Battery operation
not possible, feed-in
resumes
Increase ambient temperature;
switch off Fronius Solar Battery
and activate it again after wait-
ing an appropriate amount of
time; *)
988
Communication error
between Fronius Symo
Hybrid and Fronius Smart
Meter
No meter data available
Battery operation not pos-
sible, feed-in resumes
Check wiring; **)
128
Summary of Contents for Symo Hybrid 3.0-3-S
Page 2: ......
Page 10: ...10 ...
Page 11: ...General information 11 ...
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 35: ...Operation 35 ...
Page 36: ...36 ...
Page 66: ...66 ...
Page 67: ...Fronius system monitoring 67 ...
Page 68: ...68 ...
Page 80: ...80 ...
Page 81: ...Current data services and settings offered by Fronius system monitor ing 81 ...
Page 82: ...82 ...
Page 119: ...Troubleshooting and maintenance 119 ...
Page 120: ...120 ...
Page 133: ...Appendix 133 ...
Page 134: ...134 ...