Modbus Adress 2
DIP Switch 1
2
3
4
5
6
Position
0
1
0
0
0
0
Modbus Adress 3 (value 1 + 2 = 3)
DIP Switch 1
2
3
4
5
6
Position
1
1
0
0
0
0
Modbus Adress 4
DIP Switch 1
2
3
4
5
6
Position
0
0
1
0
0
0
Modbus Adress 7 (value 1 + 2 + 4 = 7)
DIP Switch 1
2
3
4
5
6
Position
1
1
1
0
0
0
Modbus Adress 20 (value 4 + 16 = 20)
DIP Switch 1
2
3
4
5
6
Position
0
0
1
0
1
0
Terminating Res-
istors
The system might work without terminating resistors. Due to interferences, the use of ter-
minating resistors according to the following schemes are recommended.
Activate the Fronius Smart Meter terminat-
ing resistor (R 120 Ohm) by switching pin
7 to ON (1).
13
EN-US