19
Fronius IG
Plus V
Field adjustable trip points
208 V
240 V
277 V
Nominal AC output voltage,
208
240
277
Line-to-Line, [V]
Operating AC voltage range
183-229
211-264
-
default, Line-to-Line, [V]
Adjustment range for
105-248
121-287
-
voltage, Line-to-Line, [V]
Voltage trip limit accuracy,
1.0
1.0
-
Line-to-Line [% of nominal value]
Operating AC voltage range,
106-132
106-132
244-305
Line-to-Neutral, [V]
Adjustment range for voltage,
61-143
61-143
138-324
Line-to-Neutral, [V]
Adjustment range for voltage
0.016-4.25 0.016-4.25 0.016-4.25
clearing time [s]
Voltage trip limit accuracy,
1.0
1.0
1.0
Line-to-Neutral [% of nom. value]
Nominal output frequency [Hz]
60
60
60
Operating frequency
59.3-60.5
59.3-60.5
59.3-60.5
range [Hz]
Adjustment range for
57.0-60.48 57.0-60.48 57.0-60.48
frequency [Hz]
Adjustment range for frequency
0.016-300
0.016-300
0.016-300
clearing time [s]
Frequency trip limit accuracy [ms] 16.66
(1)
16.66
(1)
16.66
(1)
Detection time [ms]
25
(2)
25
(2)
25
(2)
Reconnect time default [s]
300
300
300
Adjustment range for reconnect
5-900
5-900
5-900
time [s]
(1)
16.66 ms are equivalent to 1 cycle
(2)
25 ms are equivalent to 1.5 cycles