Field Adjustable Trip Points
Fronius IG Plus USA
Fronius IG Plus V USA
Fronius CL USA

42,0410,1517    012011

USA

Grid connected inverters for
photovoltaic systems

Operating Instructions

Summary of Contents for CL USA

Page 1: ...Field Adjustable Trip Points Fronius IG Plus USA Fronius IG Plus V USA Fronius CL USA 42 0410 1517 012011 USA Grid connected inverters for photovoltaic systems Operating Instructions...

Page 2: ......

Page 3: ...ons contains different Warnings A Warning describes a hazard to equipment or personnel It calls attention to a procedure or practice which if not correctly performed or adhered to could result in dama...

Page 4: ......

Page 5: ...quipment location at all times In addition to the operating instructions all applicable local rules and regulations regarding accident prevention and environmental protection must also be followed All...

Page 6: ...company regulations regarding grid feed in Information from solar module manufacturer Intended Use For information about where the safety instructions and warning signs are located on the equipment pl...

Page 7: ...r is obliged to take proper action to rectify the situation Grid connection Devices with a high output 16 A can influence the voltage quality of the grid due to a high current input into the main supp...

Page 8: ...Electronic Equipment and its implementation as national law electrical equipment that has reached the end of its life must be collected separately and returned to an approved recycling facility Any de...

Page 9: ...40 V Delta 8 240 V 120 V Stinger 9 240 V 120 V Split Phase 9 480 V Delta 277 V WYE 9 Fronius CL Field Adjustable Trip Points in the public grid 10 General 10 208 V Delta 10 208 V Delta 120 V WYE 10 24...

Page 10: ...for displaying the operating status 3 Enter key for confirming a choice 4 Menu Esc key switching to the menu level Menu or exit from the setup menu Esc 5 Down Right key depending on the selection for...

Page 11: ...g on the mode of display chosen Important The Min and Max values may not corres pond to the absolute extreme values as the measured data are recorded at two second intervals appears with data readings...

Page 12: ...measured 13 output bar not active during setup adjustments indicates the power output fed into the grid at a given moment independent from the display mode chosen The screen displays of the maximum p...

Page 13: ...ing energy to the grid The display switches between UIL Max and UTRIP Max Unit P grid cycles Setting range 1 255 at 208 V 240 V 277 V grid voltage Factory setting 58 at 208 V 240 V 277 V grid voltage...

Page 14: ...eeded longer than the set time the inverter stops supplying energy to the grid The display switches between FREQIL Max and FREQTRIP Max Unit P grid cycles Setting range Factory setting 9 at 208 V 240...

Page 15: ...r monitoring voltage Upper limit voltage between phase and neu tral conductor Minimum neutral conductor monitoring voltage Lower limit voltage between phase and neu tral conductor Unit P grid cycles S...

Page 16: ...0 1 11 4 1 208 V Delta 120 V WYE Adjustable parameters UIL Max UIL Max UTRIP Max UIL Min UIL Min UTRIP Min FREQIL Min FREQIL Min FREQTRIP Min STARTINIT STARTTIME 120 V 120 V 120 V 1 2 0 1 2 0 120 2 0...

Page 17: ...240 V 120 V Split Phase 180 120 V 120 V 240 V L1 L2 N UIL UNMON Adjustable parameters UIL Max UIL Max UTRIP Max UIL Min UIL Min UTRIP Min FREQIL Min FREQIL Min FREQTRIP Min STARTINIT STARTTIME UNMON...

Page 18: ...0 V WYE Fronius IG Plus 11 4 3 Fronius IG Plus V 10 0 3 Fronius IG Plus V 11 4 3 Fronius CL 33 3 DELTA Fronius CL 44 4 DELTA Fronius CL 55 5 DELTA Adjustable parameters UIL Max UIL Max UTRIP Max UIL M...

Page 19: ...UIL Max UIL Max UTRIP Max UIL Min UIL Min UTRIP Min FREQIL Min FREQIL Min FREQTRIP Min STARTINIT STARTTIME 240 V Delta 2 4 0 V 2 4 0 V 240 V 1 2 0 1 2 0 120 L1 L2 L3 UIL Fronius IG Plus 11 4 3 Fronius...

Page 20: ...he Setup menu This access code will be provided by Fronius upon request 1 Press the Menu key MENU is displayed 2 Select the Setup mode using the Left or Right keys 3 Press the Enter key STANDBY is dis...

Page 21: ...ccess code 4 Press the Enter key The third digit flashes 5 Use the Up and Down keys to select a value for the third digit of the access code 6 Press the Enter key The fourth digit flashes 7 Use the Up...

Page 22: ...ter the access code continued The first parameter UIL Max in the setup menu for field adjus table trip points is displayed The setup menu for field adjus table trip points is now activated on the inve...

Page 23: ...6 Press the Enter key The second digit flashes 7 Repeat steps 5 and 6 for each digit of the parameter value untill the whole parameter value flashes 8 Press the Enter key The new value of the paramete...

Page 24: ...wn keys to select a value for the first digit 6 Press the Enter key The second digit flashes 7 Use the Up and Down keys to select a value for the second digit 8 Press the Enter key The third digit fla...

Page 25: ...pted the display swit ches between FREQIL Min and FREQTRIP Min 16 Press the Esc key to exit the setup menu for field adustable trip points The inverter starts the startup phase with the grid synchroni...

Page 26: ...voltage 0 016 4 25 0 016 4 25 0 016 4 25 clearing time s Voltage trip limit accuracy 1 0 1 0 1 0 Line to Neutral of nom value Nominal output frequency Hz 60 60 60 Operating frequency 59 3 60 5 59 3 60...

Page 27: ...l V Adjustment range for voltage 0 016 4 25 0 016 4 25 0 016 4 25 clearing time s Voltage trip limit accuracy 1 0 1 0 1 0 Line to Neutral of nom value Nominal output frequency Hz 60 60 60 Operating fr...

Page 28: ...range for voltage 0 016 4 25 0 016 4 25 0 016 4 25 clearing time s Voltage trip limit accuracy 1 5 1 5 1 5 Line to Neutral of nom value Nominal output frequency Hz 60 60 60 Operating frequency 59 3 60...

Page 29: ...ww fronius com USA A Fronius Worldwide www fronius com addresses Fronius USA LLC Solar Electronics Division 10421 Citation Drive Suite 1100 Brighton MI 48116 E Mail pv us fronius com http www fronius...