5 | Installation
52
M2050222_en | Installation instructions Lambdamat LM 1500 KOM
▪ The diaphragm pressurised expansion tank must conform to EN 13831 and hold at least
the maximum expansion volume of the heated water in the system, including a water
seal
▪ Its size must comply with the design information in EN 12828 - Appendix D
▪ Ideally it should be installed in the return line. Follow the manufacturer’s installation
instructions
5
We recommend installing some sort of monitoring device (such as a thermometer)
5.8.2 Thermal discharge safety device with zone valve
r
Install the 2-way zone valve (A) in the fresh water pipe between the thermal discharge
safety device (B) and the boiler’s safety heat exchanger (C)
Ä
Fit the 2-way zone valve (A) with the supplied double nipple directly to the
discharge safety device (B). The remaining pipework is to be provided by the
customer.
IMPORTANT: Pay attention to the flow direction of the discharge safety device (B)!
r
Remove the stop from the rotary drive
Ä
The stop is no longer required
r
Place the rotary drive on the zone valve in such a way that the flat area of the pin fits
into the drive housing
r
Turn the rotary drive clockwise by approx. 90° until both torque supports (E) of the
drive match the bores (F) on the zone valve