Page 1
0
General Data - Low Noise Ceiling Concealed
FCU (DC Motor) 50/60Hz
Note:
1)
Nominal cooling capacity is based on the following condition:
a) Water temperature: 7.0°C (inlet) / 12.0°C (outlet)
b) Air entering condition: 27.0°C DB / 19.5°C WB
2)
Air volume is tested under entering air condition of 20.0°C DB and dry coil condition.
3)
All the units’ airflow value stated is at high speed.
4)
Sound pressure level is based on 11.5 dB(A) anechoic room background noise.
5)
Extended drain pan is optional upon request
6)
The manufacturer reserves the rights to make changes to the above specification without prior notice.
Model
FCRQ
400C
500C
600C
800C
Air Flow
High
CMH
680
850
1020
1360
CFM
400
500
600
800
Medium
CMH
510
640
780
1030
CFM
300
376
459
606
Low
CMH
340
450
560
740
CFM
200
265
330
435
Total Cooling Capacity
High
W
4020
4850
6010
7950
Medium
W
3540
4070
5050
6670
Low
W
2925
3200
4385
5570
Sensible Cooling Capacity
High
W
2970
3485
4455
5475
Medium
W
2500
2860
3790
4540
Low
W
1995
2160
3070
3665
External Static Pressure
Pa
30
Filter
Type
Washable Type
Material
Nylon
Thickness
8mm
Fan
Type
Centrifugal Forward Curved Blades
Quantity
2
2
2
3
Material
Galvanized Steel
Drive
Direct-drive
Motor
Type
Permanent Magnet DC Brushless Motor
Insulation Class
Class B
Power Supply
V/Ph/Hz
220~240/1/50~60
Quantity
1
1
1
2
Rated Power Input
at ESP: 30 Pa
W
41
61
76
92
Cooling Coil
Type
Seamless Copper Tubes Mechanically Bonded to
Aluminium Hydrophilic Fins and Collars
Max. Working
Pressure
MPa
1.6
Pipe Connection
mm(in)
DN20 (3/4") - Female Threaded
Water Flow Rate
l/s
0.20
0.24
0.30
0.40
Water Pressure Drop
kPa
30
30
40
35
Net Weight
kg
17
18
20
26
Dimension
Length
mm
905
985
1185
1465
Width
mm
490
490
515
515
Height
mm
250
250
275
275
High Sound Pressure Level
at ESP: 30 Pa (H)
dB (A)
41
43
43
46
Medium Sound Pressure Level at ESP: 30 Pa (M)
dB (A)
32
35
39
37
Low Sound Pressure Level
at ESP: 30 Pa (L)
dB (A)
23
26
30
28
Condensate Drain Size
mm(in)
DN20 (3/4") - Male Threaded