2.4.4.9. Porucha E6 (pouze pro 100AR, 140AR s 1 fází)
E6 display
PFC module protection
Check whether the
connecting line between
main board and the PFC
module is connected tightly
Yes
Check whether the voltage
range of P-N on IPM
module is normal?
DC277-
410V
No
Check whether the
inductance of PFC module
is good? If the inductance is
good, the resistance of the
two ports is 0
Yes
Replace the inductance
No
Connect it tightly, check
normal or not
Replace the outdoor main board
Yes
Yes
No
No
Replace the PFC module
Trouble is solved
Yes / No
Ano / Ne
E6 display
Zobrazeno E6
PFC module protection
Ochana modulu PFC
Check whether the connecting line between main board and
the PFC module is connected tightly
Zkontrolujte zda propojení mezi hlavní deskou a PFC
modulem je řádně propojeno
Connect it tightly, check normal or not
Řádně je propojte, zkotrolujte, zda je vše v normálu
Check whether the voltage range of P-N on IPM module is
normal? DC277-410V
Zkontrolujte napěťový rozsah na P
-N na IPM modulu, je
v pořádku? Stejnosměrné napětí 277 až 410V
Replace the outdoor main board
Vyměňte hlavní desku venkovní jednotky
Check whether the inductance of PFC module is good? If
the inductance is good, the resistance of the two ports is 0
Zkontrolujte indukčnost na PFC modulu, je v pořádku?
Jestliže je indukčnost v pořádku, odpor na jejích dvou
výstupech je roven nule
Replace the inductance
Vyměňte indukčnost
Replace the PFC module
Vyměňte PFC modul
Trouble is solved
Problém je vyřešen