PTAC - Heat Pump and Electric Heat models_Full Back

Rearward Slope 

Front Panel 

Outside Wall 

1/4" Slope

Inside Wall 

Chassis

Acccessory 

Wall Sleeve 

Acccessory 

Outdoor Grille

16"

42"

Specifications  

subject to change.

Product Dimensions

Height
Width
Depth
Max. Wall Thickness

Manufacturer 

Wall Sleeve Part Number

General Electric

Amana
Trane

Friedrich

16"
42"
13-13/16"
13-13/16"

Metal Sleeve RAB71

Plastic Sleeve RAB77
Metal Sleeve WS900B
Metal Sleeve SLV149
T-Series Metal 11-1/2-in. Deep 

Wall Sleeve 
Standard-Depth Wall Sleeve 

16 X 42 X 13-3/4-in. PXWS

Wall Cutout Dimensions

Height 
Width

16-5/16"
42-3/16"

Plug Type (NEMA)

6-20P

PTAC Specifications

 Product Shipping Weight (approx.) – 131 Lbs.

 An electrical supply with grounded three-prong receptacle is 

required. The power supply circuit must be installed in accordance 

with current edition of National Electrical Code (ANSI/NFPA 70)  

and local codes & ordinances.  

 Voltage Rating – 230V / 208V / 60 Hz / 20 Amps

 Amps @ 230/208V Volts = (Cool) 3.7 / 3.9 Amps / (Backup Electric 

Heater) 13.2 / 12.2 Amps / (Heat Pump) 3.4 / 3.8 Amps

 Always consult local and national electric codes.

 Recommended Circuit Breaker – 20 Amps

 Unit equipped with 230/208V 3-wire power supply cord, NEMA plug 

type 6-20P, approximately 66" long.

 In order for condensate water to drain properly inside the unit, the 

sleeve must be installed properly: Level from right to left with a slight 

1/4" rearward pitch from the indoor side to the outdoor side as shown 

in the illustration above. Refer to the Installation Instructions on the 

web. 

New Installation

 For new installation, Frigidaire® PTAC Sleeves are available and 

recommended for proper installation. See accessories pages for 

sleeve options.*

 PTAC installation requires 13-13/16" maximum wall thickness.

Replacement Installation

 When replacing existing PTAC with new unit, refer to Product 

Installation Guide on web to identify existing wall-sleeve manufacturer 

and size compatibility. If proper installation and slope are suspect, 

then correct installation of Frigidaire® PTAC Sleeve options 

recommended. 

 For any sleeve retrofit application, be sure that the foam seals 

(factory-installed on the tube sheets) provide a good seal between 

the grille and the outdoor coil tube sheets. These foam seals provide 

a barrier that stops air from the inside mixing with air on the outside 

(known as air recirculation).

 Using Frigidaire® wall sleeve with Non-Frigidaire grille requires 

installation of an Accessory Baffle Kit, which ensures a good seal 

between the unit and exterior grille to prevent air recirculation. Air 

recirculation is a large contributor to performance loss and premature 

damage to major components. 

Note:  For planning purposes only. Refer to Product Installation Guide  

on the web at frigidaire.com for detailed instructions.

*See accessories pages attached for optional accessories. 

USA

 • 

10200 David Taylor Drive

 • 

Charlotte, NC 28262

 • 

1-866-942-1567

 • 

frigidaire.com

 

CANADA

 • 

5855 Terry Fox Way

 • 

Mississauga, ON L5V 3E4

 • 

1-866-942-1567

 • 

frigidaire.ca

FRP90PTT2R 06/11 

© 2011 Electrolux Home Products, Inc. 

Printed in the U.S.A.

PTAC

FRP90PTT2R    

Air Conditioner / Heat Pump / Backup Electric Heater 

Summary of Contents for PTAC FRP90PTT2R

Page 1: ...ts Effortless Operation Simple intuitive room controls are easy for guests to operate ensuring a relaxing more comfortable stay Features like Effortless Restart and Ready Select controls reduce maintenance calls Effortless Temperature Control Frigidaire air conditioners maintain the preset room temperature so the room remains comfortable at all times and helps control energy levels SilentDesign So...

Page 2: ...h of Power Cord Circuit Breaker Plug Type NEMA Features Electronic Controls Front Desk Control Ready Fan Speeds Cool Fan Heat Noise Level Indoors High Med Low Quiet Start Up Low Voltage Start Up Random Restart Protection Effortless Auto Freeze Protection Energy Save 24 Hour On Off Timer Air CFM High Med Low Air Direction Control Air Intake Filter Type Filter Access Fin Coating Slide Out Chassis Co...

Page 3: ...ove Refer to the Installation Instructions on the web New Installation For new installation Frigidaire PTAC Sleeves are available and recommended for proper installation See accessories pages for sleeve options PTAC installation requires 13 13 16 maximum wall thickness Replacement Installation When replacing existing PTAC with new unit refer to Product Installation Guide on web to identify existin...

Page 4: ...PM High Med Low Air Direction Control UPC Code FEATURES Fin Coating Air Intake Low Voltage Start up Auto Fan Energy Saver 24 Hour On Off Timer Room Freeze Protection Random Restart Protection Quiet Start up Indoor Fan Speeds LED Display R410A 25 0 51 50 49 302 284 267 1030 970 890 Auxiliary 2 way 0 12505 27601 9 Normal Fresh or Recycled Yes Yes Yes Yes Yes Yes Yes 3 Yes PERFORMANCE BTU Cool BTU He...

Reviews: