Note: The supply voltage must be consistent with the rate voltage of the air conditioner.
Electrical work
1. If there is serious safety problem
about the power supply, the
technicians should refuse to install
the air conditioner and explain to the
client until the problem is solved.
2. Power voltage should be in the
range of 90%~110%of rated
voltage.
3. The creepage protector and main
power switch with a 1.5 times
capacity of Max. Current of the unit
should be installed in power circuit.
4. Ensure the air conditioner is
grounded well.
5. According to the attached
Electrical Connection Diagram
located on the panel of the
outdoor unit to connect the wire.
6. All wiring must comply with local
and national electrical codes and
be installed by qualified and
skilled electricians.
7. An individual branch circuit
used only for
this air conditioner
must be
available. See the
following table
for suggested wire
sizes and fuse
specifications:
Electric safety regulations for the initial Installation
Electrical work
INPUT RATED AMP
Switch / Fuse
POWER SUPPLY
SIZE
CAPACITY
< 9000 Btu's
9000 Btu's < capacity < 12000 Btu’s
> 12000 Btu's
115V~/ 60Hz
115V~/ 60Hz
208/230V~/ 60Hz
15A/15A
20A/20A
20A/20A
AWG WIRE
14
14
12
18