![Frigicoll Kaysun KFC-S-2T-250D Technical Manual Download Page 17](http://html1.mh-extra.com/html/frigicoll/kaysun-kfc-s-2t-250d/kaysun-kfc-s-2t-250d_technical-manual_2333551017.webp)
DC Fan Coil Unit
16
KFC-SE-2T-500D
EWT
ΔT
Indoor temperature (D.B.)
16
18
20
22
TH
WF
WPD
TH
WF
WPD
TH
WF
WPD
TH
WF
WPD
℃
℃
kW
m
3
/h
kPa
kW
m
3
/h
kPa
kW
m
3
/h
kPa
kW
m
3
/h
kPa
40
5
4.78
0.83
19.6
4.31
0.75
16.36
3.84
0.66
13.41
3.37
0.58
10.73
6
4.64
0.67
13.63
4.17
0.6
11.33
3.7
0.53
9.23
3.24
0.47
7.32
8
4.37
0.47
7.51
3.9
0.42
6.17
3.43
0.37
4.95
2.96
0.32
3.85
10
4.08
0.35
4.6
3.61
0.31
3.72
3.13
0.27
2.93
2.65
0.23
2.21
12
3.79
0.27
2.98
3.3
0.24
2.37
2.82
0.2
1.81
2.32
0.17
1.23
45
5
5.91
1.03
27.81
5.44
0.94
24.02
4.97
0.86
20.51
4.5
0.78
17.27
6
5.78
0.84
19.5
5.31
0.77
16.8
4.84
0.7
14.29
4.37
0.63
11.98
8
5.51
0.6
10.95
5.04
0.55
9.37
4.57
0.49
7.91
4.1
0.44
6.56
10
5.24
0.45
6.86
4.76
0.41
5.82
4.29
0.37
4.86
3.81
0.33
3.98
12
4.95
0.36
4.58
4.47
0.32
3.85
4
0.29
3.18
3.52
0.25
2.56
50
5
7.05
1.22
37.08
6.57
1.14
32.77
6.09
1.06
28.73
5.62
0.98
24.95
6
6.92
1
26.13
6.44
0.93
23.05
5.96
0.86
20.16
5.49
0.8
17.46
8
6.65
0.72
14.85
6.18
0.67
13.04
5.7
0.62
11.35
5.23
0.57
9.77
10
6.39
0.55
9.43
5.91
0.51
8.24
5.43
0.47
7.12
4.96
0.43
6.09
12
6.11
0.44
6.41
5.63
0.41
5.57
5.15
0.37
4.78
4.68
0.34
4.05
55
5
8.18
1.42
47.33
7.7
1.34
42.52
7.22
1.26
37.97
6.74
1.17
33.68
6
8.05
1.17
33.48
7.57
1.1
30.03
7.09
1.03
26.78
6.62
0.96
23.71
8
7.79
0.85
19.17
7.31
0.79
17.14
6.83
0.74
15.23
6.36
0.69
13.43
10
7.53
0.65
12.28
7.05
0.61
10.95
6.57
0.57
9.69
6.09
0.53
8.5
12
7.26
0.53
8.44
6.77
0.49
7.49
6.29
0.46
6.6
5.82
0.42
5.76
60
5
9.31
1.62
58.52
8.83
1.54
53.22
8.34
1.45
48.18
7.86
1.37
43.4
6
9.19
1.33
41.5
8.7
1.26
37.7
8.22
1.19
34.09
7.74
1.12
30.67
8
8.93
0.97
23.9
8.44
0.92
21.66
7.96
0.87
19.53
7.48
0.81
17.52
10
8.67
0.75
15.41
8.18
0.71
13.93
7.7
0.67
12.53
7.22
0.63
11.2
12
8.4
0.61
10.67
7.92
0.57
9.61
7.43
0.54
8.62
6.95
0.5
7.68
KFC-SE-2T-900D
EWT
ΔT
Indoor temperature (D.B.)
16
18
20
22
TH
WF
WPD
TH
WF
WPD
TH
WF
WPD
TH
WF
WPD
℃
℃
kW
m
3
/h
kPa
kW
m
3
/h
kPa
kW
m
3
/h
kPa
kW
m
3
/h
kPa
40
5
7.42
1.28
17.28
6.69
1.16
14.45
5.97
1.03
11.84
5.25
0.91
9.47
6
7.2
1.04
11.97
6.47
0.93
9.95
5.75
0.83
8.1
5.02
0.73
6.42
8
6.74
0.73
6.53
6.01
0.65
5.36
5.29
0.57
4.3
4.56
0.49
3.33
10
6.27
0.54
3.96
5.54
0.48
3.2
4.8
0.42
2.51
4.06
0.35
1.89
12
5.78
0.42
2.54
5.04
0.36
2.01
4.29
0.31
1.53
3.52
0.25
1.09
45
5
9.2
1.6
24.66
8.47
1.47
21.34
7.75
1.34
18.24
7.02
1.22
15.37
6
8.98
1.3
17.22
8.26
1.19
14.86
7.53
1.09
12.65
6.81
0.98
10.61
8
8.54
0.93
9.6
7.81
0.85
8.22
7.08
0.77
6.94
6.36
0.69
5.76
10
8.09
0.7
5.96
7.35
0.64
5.06
6.62
0.57
4.23
5.89
0.51
3.46
12
7.62
0.55
3.96
6.88
0.5
3.32
6.14
0.44
2.74
5.4
0.39
2.2
50
5
10.98
1.91
33
10.25
1.78
29.23
9.52
1.65
25.67
8.8
1.53
22.33
6
10.77
1.56
23.19
10.04
1.45
20.49
9.31
1.35
17.95
8.58
1.24
15.57
8
10.33
1.12
13.09
9.6
1.04
11.51
8.87
0.96
10.03
8.14
0.88
8.64
10
9.89
0.86
8.26
9.15
0.79
7.22
8.42
0.73
6.25
7.69
0.67
5.35
12
9.43
0.68
5.58
8.7
0.63
4.85
7.96
0.58
4.16
7.23
0.52
3.53
55
5
12.77
2.22
42.26
12.03
2.09
38.05
11.29
1.97
34.05
10.56
1.84
30.27
6
12.55
1.82
29.81
11.82
1.71
26.79
11.08
1.61
23.94
10.35
1.5
21.23
8
12.12
1.32
16.98
11.39
1.24
15.21
10.65
1.16
13.54
9.92
1.08
11.96
10
11.69
1.02
10.82
10.95
0.95
9.66
10.21
0.89
8.56
9.48
0.82
7.52
12
11.24
0.81
7.39
10.5
0.76
6.57
9.77
0.71
5.79
9.03
0.65
5.06
60
5
14.55
2.53
52.38
13.8
2.41
47.75
13.07
2.28
43.33
12.33
2.15
39.12
6
14.34
2.08
37.05
13.59
1.97
33.73
12.86
1.87
30.57
12.12
1.76
27.56
8
13.91
1.52
21.23
13.17
1.43
19.28
12.43
1.35
17.43
11.7
1.27
15.66
10
13.48
1.17
13.63
12.74
1.11
12.34
12
1.05
11.12
11.27
0.98
9.96
12
13.04
0.95
9.39
12.3
0.89
8.48
11.56
0.84
7.61
10.83
0.79
6.79
Abbreviations:
Δt:
Temperature Difference (
℃
)
TH:
Total Heating Capacity (kW)
WF:
Water Flow(m
3
/h)
WPD: