background image

2.4.2 EVAPORATOR

1. Remove the cabinet.

2. Discharge the refrigerant by using a refrigerant

recovery system.

3. Remove the air guide upper. (Refer to Section

2.2.1)

4. After discharging the refrigerant completely,

unbraze the interconnecting tube at the condenser 

connections.

5. Remove the evaporator.

6. Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1. Remove the cabinet.

2. Discharge the refrigerant by using a refrigerant

recovery system.

3. Remove the air guide upper. (Refer to Section

2.2.1)

4. After discharging the refrigerant completely,

unbraze the interconnecting tube of the capillary

tube.

5. Remove the capillary tube.

6. Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration cycle. 

1. When replacing the refrigerating cycle, be sure to

discharge the refrigerant by using a refrigerant

recovery system.

2. After discharging the unit completely, remove the

desired components, and unbraze the pinch-off

tubes. 

3. Solder service valves into the pinch-off tube ports,

leaving the valves open. 

4. Solder the pinch-off tubes with service valves.  

5. After completing the above procedures, the valve

must be closed and left in place on the system for

any subsequent procedures.

6. Evacuate as follows: 

6-1. Connect the vacuum pump, as illustrated in 

figure 21A. 

6-2. Start the vacuum pump. Slowly open manifold

valves A and B with two full turns counter-

clockwise and leave the valves closed. 

The vacuum pump is now pulling through

valves A and B up to valve C by means of

manifold and the entire system. 

CAUTION :

If high vacuum equipment is used,

just crack valves A and B for a few minutes, then

open slowly with the two full turns counter-clock-

wise. This will keep oil from foaming and being

drawn into the vacuum pump. 

6-3. Operate the vacuum pump for 20 to 30 min-

utes, until 600 micron vacuum is obtained. 

Close valves A and B and observe vacuum

gauge for a few minutes. 

A rise in pressure would indicate a possible

leak or moisture remaining in the system. 

With valves A and B closed, stop the vacuum

pump. 

6-4. Remove the hose from the vacuum pump and

place it on the charging cylinder. See figure

23B. Open valve C. 

Discharge the line at the manifold connection. 

6-5. The system is now ready for final charging. 

7. Recharge as follows: 

7-1. Rotary compressor systems are charged from

the high-side. If the total charge cannot be put

in the high-side, the balance will be put in the 

suction line through the access valve which is

installed as the system is opened. 

7-2. Connect the charging cylinder as shown in fig-

ure 21B. With valve C open, discharge the

hose at the manifold connection. 

7-3. Open valve A and allow the proper charge to

enter the system. Valve B is still closed. 

7-4. If more charge is required, the high-side will

not take it. Close valve A. 

7-5. With the unit running, open valve B and add

the balance of the charge. 

a. Do not add the liquid refrigerant to the low-

side. 

b. Watch the low-side gauge, allow pressure to

rise to 30 lbs. 

c. Turn off valve B and allow the pressure to

drop. 

d. Repeat steps B and C until the balance of

the charge is in the system. 

7-6. When the unit is operating correctly, use the

pinch-off tool with the unit still running and the

clamp on the pinch-off tube. Using a tube cut-

ter, cut the pinch-off tube about 2 inches from

the pinch-off tool. Use sil-fos solder and solder

the pinch-off tube closed. Turn off the unit,

allow setting for a while and then test the leak-

age of the pinch-off connection. 

11

Summary of Contents for ZQ06C10

Page 1: ...Room Air Conditioner Service and Parts Manual CP06 ZQ06 05 06 CP06C10 ZQ06C10...

Page 2: ...AN 7 2 2 3 MOTOR 8 2 2 4 AIR GUIDE 8 2 3 ELECTRICAL PARTS 8 2 3 1 OVERLOAD PROTECTOR 8 2 3 2 COMPRESSOR 9 2 3 3 CAPACITOR 9 2 3 4 THERMOSTAT 9 2 3 5 ROTARY SWITCH 9 2 3 6 POWER CORD 10 2 4 REFRIGERANT...

Page 3: ...S FOR THE SIMPLE INSTALLATION AND SERVICE BUILT IN ADJUSTABLE THERMOSTAT WASHABLE ONE TOUCH FILTER COMPACT SIZE 1 2 SPECIFICATIONS MODELS ITEMS COOLING CAPACITY BTU h 5 400 6 400 POWER SUPPLY Phase V...

Page 4: ...NEY SAVER 2 The fan stops when the compressor stops cooling Approximately every 3 minutes the fan will turn on and sample the room air to determine if more cooling is needed TEMPERATURE SETTING 1 Thes...

Page 5: ...n operation without cooling Hi Cool Cooling with high speed fan operation Lo Cool Cooling with low speed fan operation This automatically controls the temperature of the indoor air Turn the knob so th...

Page 6: ...denser See Figure 3 4 Lift the cabinet from the unit 5 Re install by referring to the procedures above 2 1 3 CONTROL BOARD 1 Disconnect the unit from the power source 2 Remove the front grille Refer t...

Page 7: ...ction 2 1 2 4 Remove the control board Refer to Section 2 1 3 5 Remove the air guide upper Refer to Section 2 2 1 6 Remove 2 screws that secure the base pan to condenser See Figure 7 7 Remove screw th...

Page 8: ...2 1 2 4 Remove the control board Refer to Section 2 1 3 5 Remove the air guide upper Refer to Section 2 2 1 6 Remove the compressor turbo fan fan and shroud Refer to Section 2 2 2 7 Remove the motor R...

Page 9: ...terminals 4 Remove the screw which fastens the capacitor clamp 5 Remove all the leads of capacitor terminals 6 Re install the components by referring to the removal procedure above See Figure 15 2 3...

Page 10: ...uring the clip with cord to the control board 8 Pull the power cord 9 Re install by referring to procedures above 2 4 REFRIGERANT CYCLE 2 4 1 CONDENSER 1 Remove the cabinet Refer to Section 2 1 2 2 Di...

Page 11: ...slowly with the two full turns counter clock wise This will keep oil from foaming and being drawn into the vacuum pump 6 3 Operate the vacuum pump for 20 to 30 min utes until 600 micron vacuum is obta...

Page 12: ...proof seal leak detector tubing cutter hand tools to remove components and service valve B A B A B A COMPOUND GAUGE SEE INSETS BELOW CAPILLARY TUBE EVAPORATOR LOW PRESSURE SIDE COMPRESSOR CONDENSER HI...

Page 13: ...low a clear vertical opening of 13 from the bot tom of the sash to the window stool 2 If storm window presents interference fasten a 2 wide wood strip to the inner window sill across the full width of...

Page 14: ...rackets behind the inner window sill with the short side of bracket as shown Use the 2 screws TYPE A provided b The bracket helps to hold unit securely in place Be sure to place bracket edge flush aga...

Page 15: ...pening using 4 screws TYPE B to secure them as shown in Figure 31 5 INSTALL THE SASH SEAL AND SASH LOCK a Cut the sash seal TYPE E to the window width Stuff the sash seal between the glass and the win...

Page 16: ...F EXTENSION CORDS Because of potential safety hazards we strongly discourage the use of an extension cord However if you wish to use an extension cord use a CSA certified UL listed 3 wire grounding ex...

Page 17: ...AIR MOTOR COMPRESSOR ROOM AIR HEAT LOAD CAPILLARY TUBE LIQUID REFRIGERANT LIQUID OUTLET VAPOR INLET COMPLETE LIQUID BOIL OFF POINT SUCTION LINE COOL LOW PRESSURE VAPOR LIQUID PRESSURE DROP DISCHARGE...

Page 18: ...ce of inlet outlet air 55 59 F 13 15 C Replacement of unit if the unit is beyond repair Check outdoor coil heat exchanger and fan operation Check heat load increase Check cold air circulation for smoo...

Page 19: ...ompressor capacitor Replacement of compressor Motor damaged Irregular motor insulation Irregular motor resistance Check of circuit breaker and fuse Gas leakage of feeler bulb of thermostat Check contr...

Page 20: ...an blade hitting shroud or blower wheel hitting scroll Re align assembly Units using slinger ring condenser fans must have 0 22 0 25 inch clearance to the base If necessary shim up the bottom of the f...

Page 21: ...diagram correct the connections Thermistor Check the TEMP control If not at the lowest number set TEMP control to this setting and restart the unit Check the continuity of the thermistor Replace the t...

Page 22: ...crease causing the compressor to cycle Straighten the fins or replace the coil Capacitor Test the capacitor Wiring Check the terminals If loose repair or replace Refrigeration system Check the system...

Page 23: ...USE 1 POWER CORD ASS 6411A20048V 1 2 FAN MOTOR 4681A10002V 4681A10002U 3 COMPRESSOR 2520UCEA003 2520AA1C71A 4 THERMISTOR THERMOSTAT 6323A20003D 2H01109H 5 CAPACITOR 6120AR2359V 6 OVERLOAD PROTECTOR 67...

Page 24: ...602 354210 349480 352380 149980 559011 346811 554030 W48602 130910 550140 554160 567502 352115 552102 352111 352113 35211A 135313 152302 135312 132111 2 132111 1 147581 264110 238310 W0CZZ 249950 2687...

Page 25: ...82 1 135313 352390 135312 130410 359012 W48602 354210 349480 352380 149980 559011 346811 554030 W48602 130910 266003 264110 269310 W0CZZ 249950 135500 550140 554160 567502 352115 352111 352113 35211A...

Page 26: ...A C ESCUTCHEON CONTROL BOX ASSEMBLY SINGLE THERMISTER POWER CORD ASSEMBLY SWICTH ROTARY REMOTE CONTROLLER PWB PCB ASSEMBLY DISPLAY THERMOSTAT MOTOR ASSEMBLY SINGLE ORIFICE TUBE ASSEMBLY SUCTION SINGL...

Page 27: ...27 MEMO...

Page 28: ...e Box 1540 4200 N Pan Am Expressway San Antonio Texas 78295 1540 210 357 4400 FAX 210 357 4490 FRIEDRICH AIR CONDITIONING CO Visit our web site at www friedrich com P NO 3828A20927A Use Factory Certif...

Reviews: