WALLMASTER HEAT PUMP
HEATING PERFORMANCE: Change-over from heat pump operation to resistance
operation on models indicated is automatic at a preset outside ambient temperature
of approximately 35°F.
Calculate the heat loss of the space to be heated. As long as the heat loss does
not exceed the resistance heating capacity rating of the unit, the heating perfor-
mance will be satisfactory.
Note: all models will produce condensate. If condensate disposal is desired, an
optional drain kit is available.
DEFROST CONTROL: Initiated at 30°F (outdoor coil temperature) and terminated
at 43°F (outdoor coil temperature). During defrost, the compressor stops and the
electric heat starts, then operates with the fan to maintain indoor comfort. Below
43°F, the unit remains in electric heat mode.
DEFROST DRAIN: Drain automatically opens at approximately 50°F to prevent
condensate from freezing inside drain pan.
WallMaster Heat Pump heating information
(
shown in
red)
indicates heat pump heating performance. WallMaster Electric Heat heating information
(shown in red)
indicates electric heat strip performance. For WallMaster Heat Pump electric heating performance refer to corresponding WallMaster Electric Heat model.
Plug Face/ Circuit Rating
WallMaster
Model Number
Uni-Fit
Model Number
Circuit Rating
Breaker
or T-D Fuse
Plug Face
(NEMA#)
Power Cord
Length (ft.)
Wall
Outlet
Appearance
WS08C10, WS10C10,
WS12C10
US08C10, UE08C13
US10C10, US12C10
125V - 15A
5 - 15P
6
WS10C30, WS13C30,
WS15C30
US10C30, US12C30,
US14C30
250V - 15A
6 - 15P
4
WE10C33, WE13C33,
WE15C33, WY09C33, WY12C33
UE10C33, UE12C33
250V - 20A
6 - 20P
4
Power cords are located on front left of WallMaster models and on front right of Uni-Fit models.
All models use
environmentally
friendly R-410A
refrigerant.
R-410A
Estar
Model
Cooling
Capacity Btu
Heating
Capacity Btu
Volts
Rated
Cooling
Amps
Cooling
Watts
Heating
Amps
Heating
Watts
Energy
Efficiency
Ratio
EER
Estimated
Yearly
Operating
Cost
Moisture
Removal
Pints/HR
Room
Side Air
Circulation
CFM
Sleeve
Net
Weight
Lbs
WALLMASTER
Cool only
H
WS08C10
7800
NA
115
7.1
788
-
-
9.9
†
1.2
250
WSD
93
H
WS10C10
9700
NA
115
10.0
1032
-
-
9.4
$82
2.4
257
WSD
103
H
WS12C10
11900
NA
115
11.8
1266
-
-
9.4
$101
3.3
295
WSD
112
H
WS10C30
9500/9200
NA
230/208
4.5/4.7
989/958
-
-
9.6/9.6
$79
1.5
300
WSD
101
H
WS13C30
12600/12300
NA
230/208
6.3/6.7
1340/1309
-
-
9.4/9.4
$107
3.6
290
WSD
109
WS15C30
14500/14500
NA
230/208
8.3/8.2
1706/1706
-
-
8.5/8.5
$136
4.2
290
WSD
119
Heat Pump
H
WY09C33
9300/9000
7300/7300
230/208
4.4/4.7
989/957
3.8/4.0
839/793
9.4/9.4
$79
2.1
250
WSD
103
WY12C33
12000/11800
9350/9200
230/208
6.1/6.4
1395/1372
4.8/5.1
1062/1010
8.6/8.6
$111
2.6
275
WSD
111
Cool with Electric Heat
WE10C33
9500/9200
11000/9100
230/208
4.5/4.7
989/958
16.0/14.7
3550/2950
9.6/9.6
$79
1.5
300
WSD
121
WE13C33
12600/12300
11000/9100
230/208
6.3/6.7
1340/1309
16.0/14.7
3550/2950
9.4/9.4
$107
3.6
290
WSD
107
WE15C33
14500/14500
11000/9100
230/208
8.3/8.8
1706/1706
16.0/14.7
3550/2950
8.5/8.5
$136
4.2
290
WSD
116
UNI-FIT
Cool Only
H
US08C10
8000
-
115
7.5
830
-
-
9.6
$66
2.2
260
USC
73
H
US10C10
9800
-
115
9.6
1040
-
-
9.4
$83
3.2
285
USC
78
H
US12C10
11500
-
115
11.2
1220
-
-
9.4
$97
3.8
290
USC
80
H
US10C30
10000/9800
-
230/208
4.7/5.2
1060/1040
-
-
9.4/9.4
$85
3.2
285
USC
78
H
US12C30
11500/11200
-
230/208
5.6/6.0
1220/1190
-
-
9.4/9.4
$97
3.8
290
USC
80
H
US14C30
13000/12600
-
230/208
7.0/7.5
1530/1480
-
-
9.4/9.4
$122
4.0
310
USC
87
Cool with Electric Heat
UE08C13
8000
3850
115
7.5
830
10.7
1230
9.6
$66
2.2
260
USC
73
UE10C33
10000/9800
11200/9200
230/208
4.7/5.2
1060/1040
15.3/14.0
3500/2900
9.4/9.4
$85
3.2
285
USC
78
UE12C33
11500/11200
11200/9200
230/208
5.6/6.0
1220/1190
15.3/14.0
3500/2900
9.4/9.4
$97
3.8
290
USC
80
Due to continuing research in new energy-saving technology, specifications are subject to change without notice.
As an
E
nErgy
S
tar
®
partner, Friedrich Air Conditioning Co. has determined that the selected
E
nErgy
S
tar
®
models
meet the
E
nErgy
S
tar
®
guidelines for energy efficiency.
Estimated yearly operating cost based on a 2007 national average electricity cost of 10.65 cents per kWh.
† The estimated yearly operating cost of this model was not available at the time the range was published.
SPECIFICATIONS