background image

13

 10. 

Evacuate system to maximum absolute holding pres-
sure of 200 microns or less. NOTE:  This process can 
be speeded up by use of heat lamps, or by breaking 
the vacuum with refrigerant or dry nitrogen at 5,000 
microns. Pressure system to 5 PSIG and leave in 
system a minimum of 10 minutes. Release refriger-
ant, and proceed with evacuation of a pressure of 
200 microns or less.

 11. 

Break vacuum by charging system from the high side 
with the correct amount of refrigerant specifi ed. This 
will prevent boiling the oil out of the crankcase.

 

 

NOTE:  If the entire charge will not enter the high 
side, allow the remainder to enter the low side in 
small increments while operating the unit.

 12. 

Restart unit several times after allowing pressures 
to stabilize. Pinch off process tubes, cut and solder 
the ends. Remove pinch off tool, and leak check the 
process tube ends.

SPECIAL PROCEDURE IN THE CASE OF MOTOR
COMPRESSOR BURNOUT

  1. 

Recover all refrigerant and oil from the system.

  2. 

Remove compressor, capillary tube and fi lter drier 
from the system.

  3. 

Flush evaporator condenser and all connecting 
tubing with dry nitrogen or equivalent, to remove 
all contamination from system. Inspect suction and 
discharge line for carbon deposits. Remove and 
clean if necessary.

  4. 

Reassemble the system, including new drier strainer 
and capillary tube.

  5. 

Proceed with processing as outlined under hermetic 
component replacement.

ROTARY COMPRESSOR SPECIAL 
TROUBLESHOOTING AND SERVICE

Basically, troubleshooting and servicing rotary compres-
sors is the same as on the reciprocating compressor with 
only a few exceptions.

  1. 

Because of the spinning motion of the rotary, the 
mounts are critical. If vibration is present, check the 
mounts carefully.

  2. 

The electrical terminals on the rotary are in a differ-
ent order than the reciprocating compressors. The 
terminal markings are on the cover gasket. Use your 
wiring diagram to insure correct connections.

REFRIGERANT CHARGE

  1. 

The refrigerant charge is extremely critical. Mea-
sure charge carefully - as exact as possible to the 
nameplate charge.

  2. 

The correct method for charging the rotary is to 
introduce liquid refrigerant into the high side of the 
system with the unit off. Then start compressor and 
enter the balance of the charge, gas only, into the 
low side.

 

 

The introduction of liquid into the low side, without 
the use of a capillary tube, will cause damage to 
the discharge valve of the rotary compressor.

 

 

NOTE:   All inoperative compressors returned to 
Friedrich must have all lines properly plugged with 
the plugs from the replacement compressor.

Summary of Contents for WallMaster WE10B33A-B

Page 1: ...30B C WS16B30A C WE10B33A B WE13B33B B WE16B33A B WY10B33A B WY13B33A B WM Svc Prts 07 3 07 Service Parts Manual WallMaster Thru the Wall Temp Hour Cool MoneySaver Fan Only Clock Start Time Stop Time...

Page 2: ...Data 6 Electrical Data 7 Functional Component Definitions 8 Electronic Controls 9 Rotary Controls 10 Refrigeration Sequence of Operation 11 Sealed Refrigeration Repairs 12 13 Refrigerant Charging 13...

Page 3: ...nada This warranty is not applicable to 1 Air filters or fuses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper in...

Page 4: ...d debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly Check the sealant around the sle...

Page 5: ...ER 6th DIGIT VOLTAGE 1 115 Volts 3 230 208 Volts 7th DIGIT 0 Straight Cool Heat Pump Models ELECTRIC HEAT MODELS 3 3 KW Heat Strip Nominal 8th DIGIT Major Change Serial Number Decade Manufactured L 0...

Page 6: ...4 35 2 281 1300 15 WS16B30A 52 28 51 53 121 154 54 99 18 32 74 315 7 7 35 0 47 6 292 1421 15 WE10B33A 53 27 54 52 126 180 82 99 16 31 82 289 4 6 15 2 45 0 38 0 225 1074 20 WE13B33B 52 29 52 51 127 18...

Page 7: ...d and be within reach of service cord Do NOT alter the service cord or plug Do NOT use an extension cord Refer to the table above for proper receptacle and fuse type ELECTRIC SHOCK HAZARD Turn off ele...

Page 8: ...g diagrams and schematics in the back of this service manual Capacitor Reduces line current and steadies the voltage supply while greatly improving the torque characteristics of the fan motor and comp...

Page 9: ...ode Mode is active Pressing the TEMP HR button will display 00 Consecutive presses will scroll through all error codes logged Press the TEMP HR button to see the reverse order of all error codes logge...

Page 10: ...itch section as indicated on decorative control panel in Figure 7 Figure 7 System Control Panel NOTE Units will operate in constant fan in the cooling mode and auto fan in the heating mode Figure 8 Sy...

Page 11: ...nge in state can occur 3 Flow is always from a higher pressure area to a lower pressure area 4 The temperature at which a liquid or gas changes state is dependent upon the pressure The refrigeration c...

Page 12: ...Compressor condenser evaporator capillary tube refrigerant leaks etc 1 Recover the refrigerant from the system at the pro cess tube located on the high side of the system by installing a line tap on t...

Page 13: ...and discharge line for carbon deposits Remove and clean if necessary 4 Reassemble the system including new drier strainer and capillary tube 5 Proceed with processing as outlined under hermetic compon...

Page 14: ...oke or not enough flow to maintain pressure differential Check unit for correct operating pressures and charge Raise head pressure If no shift use valve with smaller port Body damage Replace valve Hot...

Page 15: ...run Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed swi...

Page 16: ...ary tube De ice coil Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does...

Page 17: ...bulb Place jumper across t stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram...

Page 18: ...short cycles T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty...

Page 19: ...ce defrost control Defrost control contacts stuck If contacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bulb...

Page 20: ...continuity of system switch Problem Possible Cause Action Cooling adequate but heating insufficient Heating capillary tube partially restricted Check for partially starved outer coil Replace heating...

Page 21: ...21 WIRING DIAGRAM MODELS WS08B10A C WS10B10A C WS14B10A C WS10B30A C WS13B30C...

Page 22: ...22 WIRING DIAGRAM MODELS WS16B30A C...

Page 23: ...23 WIRING DIAGRAM MODELS WE10B33A B WE13B33B B...

Page 24: ...24 WIRING DIAGRAM MODELS WE16B33A B...

Page 25: ...25 WIRING DIAGRAM MODELS WY10B33A B WY13B33A B...

Page 26: ...ES CHASSIS PARTS 47 48 46 46A 31 12 32 30 7 16 17 14 20 18 19 27 25 13 8 For Heat Cool Models Only 5 45 26 1 41 43 39 Electronic Control Box and Controls 2 41 39 43 6 1 44 Electro Mechanical Control B...

Page 27: ...OR 61871473 1 1 1 110 7 FAN MOTOR 61871474 1 1 110 8 HEATER 62101210 1 1 1 1 1 210 9 SOLENOID and REVERSING VALVE 25022032 1 1 240 REFRIGERATION SYSTEM PARTS WS08B10A C WS10B10A C WS14B10A C WS10B30A...

Page 28: ...31 GROMMET FAN MTR 60640500 3 3 3 3 3 3 3 3 3 3 3 999 32 NUT FAN MTR 91003000 3 3 3 3 3 3 3 3 3 3 3 999 39 PANEL CTRL MOUNT 62100002 1 1 1 1 1 1 1 1 1 1 1 999 41 BRACKET CONRTOL 62100802 1 1 1 1 1 1 1...

Page 29: ...SLEEVE PARTS 2 3 4 1 REF DESCRIPTION PART NO 1 SLEEVE ASSEMBLY 61603611 1 1 1 1 1 1 1 1 1 1 1 2 PANEL WEATHER INNER 61603201 1 1 1 1 1 1 1 1 1 1 1 3 GRILLE LOUVERED 61603011 1 1 1 1 1 1 1 1 1 1 1 4 PA...

Page 30: ...07 3 07 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed i...

Reviews: