920-075-09
General Specifications
V
ert-I-Pak
®
Model Identification Guide
Electrical Data
MODEL:
V(E,H)A09
V(E,H)A12
V(E,H)A18
Voltage (V)
230 / 208
230 / 208
230 / 208
Refrigerant
R-22
R-22
R-22
Chassis Width
23.125"
23.125"
23.125"
Chassis Depth
23.125"
23.125"
23.125"
Chassis Height **
32.25"
32.25"
32.25"
Shipping W x D x H
26.00" x 28.50" x 35.00"
26.00" x 28.50" x 35.00"
26.00" x 28.50" x 35.00"
Supply Duct Collar ***
10"
10"
10"
Drain Connection
3/4" FPT
3/4" FPT
3/4" FPT
Min. Circuit Amps
See Chassis Nameplate
CFM Indoor
See Charts 2 & 3 (Page 10)
Max. Duct ESP
.3 in. water
.3 in. water
.3 in. water
NOTES:
** Height includes 2" duct collar & isolators under unit.
*** Factory collar accepts 10" flex duct.
ELECTRIC HEATER SIZE
A Series
25 = 2.5 KW
34 = 3.4 KW
50 = 5.0 KW*
75 = 7.5 KW**
MODEL NUMBER
V E A 09 K 34 RT H
ENGINEERING CODE
OPTIONS
RT = Standard Remote Operation
* Not available on 9000 BTU models.
** 24000 BTU only.
VOLTAGE
K = 208/230V-1Ph-60Hz
NOMINAL CAPACITY
A Series (Btu/h)
09 = 9,000
12 = 12,000
DESIGN SERIES
A = 32"/47" Cabinet
SERIES
V=Vertical Series
18 = 18,000
24 = 24,000
E =Cooling with electric heat
H =Heat Pump
Refer to electrical data chart for heater/unit compatibility.
Voltage ( V) 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208
LRA - Comp. (A)
21
21
21
24.0
24.0
24.0
47
47
47
Cooling Current (A) 4.4/4. 9 4.4/4. 9
4.4/4.9
5.5/6.1
5.5/6.1 5.5/6.1 9.2/10.2 9.2/10.2 9.2/10.2
MIN. Ckt. Amps (A)
15
20
30
15
20
30
15
20
30
Power Connection
HARD WIRED
HARD WIRED
HARD WIRED
V(E,H)A09K25V(E,H)A09K34V(E,H)09K50V(E,H)A12K25V(E,H)A12K34V(E,H,)A12K50V(E,H)A18K25
V(E,H)A18K50
V(E,H)A18K34
Model
Chassis Specifications
Important: all 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis
electrical requirements. See page 8 - Figure 5 for unit wiring and wall thermostat wiring. See page 8 for wire size. Use
HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with nec and local codes.