background image

11

EQUIPMENT REQUIRED

 1.  Voltmeter

 2.  Ammeter

 3.  Ohmmeter 

  4. 

E.P.A. Approved Refrigerant Recovery System.

  5. 

Vacuum Pump (capable of 200 microns or less vacuum.)

 6.  Acetylene Welder

  7. 

Electronic Halogen Leak Detector (G.E. Type H-6 or 

equivalent.)

  8. 

Accurate refrigerant charge measuring device such as:

 

 

a. Balance Scales - 1/2 oz. accuracy

 

 

b. Charging Board - 1/2 oz. accuracy

  9. 

High Pressure Gauge - (0 - 400 lbs.)

 10. 

Low Pressure Gauge - (30 - 150 lbs.)

 11. 

Vacuum Gauge - (0 - 1000 microns)

EQUIPMENT MUST BE CAPABLE OF:

  1. 

Recovery CFC’s as low as 5%.

  2. 

Evacuation from both the high side and low side of the 

system simultaneously.

  3. 

Introducing refrigerant charge into high side of the 

system.

  4. 

Accurately weighing the refrigerant charge actually 

introduced into the system.

  5. 

Facilities for fl owing nitrogen through refrigeration 

tubing during all brazing processes.

HERMETIC COMPONENT REPLACEMENT

The following procedure applies when replacing components 

in the sealed refrigeration circuit or repairing  refrigerant 
leaks. (Compressor, condenser, evaporator, capillary tube, 
refrigerant leaks, etc.)

  1. 

Recover the refrigerant from the system at the process 

tube located on the high side of the system by installing 
a line tap on the process tube. Apply gauge from 
process tube to EPA approved  gauges from process 
tube to EPA approved recovery system. Recover 

CFC’s in system to at least 5%.

  2. 

Cut the process tube below pinch off on the suction 

side of the compressor.

  3. 

Connect the line from the nitrogen tank to the suction 

process tube.

  4. 

Drift dry nitrogen through the system and un-solder 

the more distant connection fi rst. (Filter drier, high side 
process tube, etc.)

  5. 

Replace inoperative component, and always install a 

new fi lter drier. Drift dry nitrogen through the system 
when making these connections.

 

HERMETIC COMPONENT REPLACEMENT cont’d

  6. 

Pressurize system to 30 PSIG with proper refrigerant and 

boost refrigerant pressure to 150 PSIG with dry nitrogen.

  7. 

Leak test complete system with electric halogen leak 

detector, correcting any leaks found.

  8. 

Reduce the system to zero gauge pressure.

  9. 

Connect vacuum pump to high side and low side of 

system with deep vacuum hoses, or copper tubing. 

(Do not use regular hoses.)

 10. 

Evacuate system to maximum absolute holding 

pressure of 200 microns or less. NOTE:  This 
process can be accelerated by use of heat lamps, 
or by breaking the vacuum with refrigerant or dry 
nitrogen  at  5,000  microns.  Pressure  system  to  5 
PSIG and leave in system a minimum of 10 minutes. 
Release refrigerant, and proceed with evacuation of 
a pressure of 200 microns or less.

 11. 

Break vacuum by charging system from the high side 

with the correct amount of liquid refrigerant specifi ed. 

This will prevent boiling the oil out of the crankcase, 

and damage to the compressor due to over heating.

NOTE:

  If the entire charge will not enter the high side, allow 

the remainder to enter the low side in small increments while 
operating the unit.

12.  

Restart unit several times after allowing pressures 

to stabilize. Pinch off process tubes, cut and solder 
the ends. Remove pinch off tool, and leak check the 
process tube ends.

SPECIAL PROCEDURE IN THE CASE OF COMPRESSOR 
MOTOR BURNOUT

  1. 

Recover all refrigerant and oil from the system.

  2. 

Remove compressor, capillary tube and fi lter drier from 

the system.

  3. 

Flush evaporator condenser and all connecting 

tubing  with  dry  nitrogen  or  equivalent,  to  remove 
all contamination from system. Inspect suction and 
discharge line for carbon deposits. Remove and clean 
if necessary.

  4. 

Reassemble the system, including new drier strainer 

and capillary tube.

  5. 

Proceed with processing as outlined under hermetic 

component replacement.

ROTARY COMPRESSOR SPECIAL  TROUBLESHOOTING 

AND SERVICE

Basically, troubleshooting and servicing rotary compressors 
is the same as on the reciprocating compressor with only 
one main exception:

 

 

NEVER, under any circumstances, charge a rotary 

compressor through the LOW side. Doing so would 
cause permanent damage to the new compressor.

Summary of Contents for SM21L30-A

Page 1: ...ervice Manual Room Air Conditioners RAC Svc 06 3 06 2006 Cool SUPER HIGH EFFICIENCY Temp Hour Fan Only Clock Start Stop MoneySaver PM Vent shut Exhaust Fan Speed Timer On Off Set Hour Power On Off Mod...

Page 2: ...Filter Discharge Air Evaporator Coil Blower Wheel Capillary Tube Condenser Fan Blade Outdoor Grille Sleeve Condenser Coil Compressor Basepan Front Cover System Switches Reversing Valve some models Fr...

Page 3: ...warranty is not applicable to 1 Air filters or fuses 2 Products on which the model and serial numbers have been removed 3 Products which have defects or damage which results from improper installation...

Page 4: ...s and debris Clean both areas with an antibacterial and antifungal cleaner Rinse both items thoroughly with water and ensure that the drain outlets are operating correctly Check the sealant around the...

Page 5: ...ring Major change 2nd Digit C Casement Q Q Star S Small Chassis M Medium Chassis L Large Chassis H HazardGard 3rd and 4th Digit Approximate BTU HR Cooling Heating BTU Hr capacity listed in the Speci c...

Page 6: ...4 35 0 32 0 208 230 15 ES12L33 A 56 25 121 167 65 15 28 83 256 4 8 15 1 21 0 28 0 208 230 20 ES16L33 A 49 32 130 179 50 8 34 75 279 7 4 15 1 35 0 32 0 208 230 20 YS09L10 A 60 20 116 164 71 18 17 89 2...

Page 7: ...ord and be within reach of service cord Do NOT alter the service cord or plug Do NOT use an extension cord Refer to the table above for proper receptacle and fuse type ELECTRIC SHOCK HAZARD Turn off e...

Page 8: ...y improving the torque characteristics of the fan motor and compressor motor ELECTRONIC CONTROLS TESTING THE ELECTRONIC CONTROLS CHECK FILTER light will come on after 250 hours of use Touch CHECK FILT...

Page 9: ...estored to the unit there is a twoseconddelaybeforethefancomesonandapproximately three minutes delay before the compressor is activated providing that the mode was set for cooling and the set point te...

Page 10: ...dy 2 Heat must be added to or removed from a substance before a change in state can occur 3 Flow is always from a higher pressure area to a lower pressure area 4 The temperature at which a liquid or g...

Page 11: ...ressure to 150 PSIG with dry nitrogen 7 Leak test complete system with electric halogen leak detector correcting any leaks found 8 Reduce the system to zero gauge pressure 9 Connect vacuum pump to hig...

Page 12: ...compressor eventuallycausingamechanicalfailurewithinthecompressor This mechanical failure can manifest itself as valve failure bearing failure and or other mechanical failure The speci c type of failu...

Page 13: ...run 10 to 15 minutes check the gauge pressures Gauges connected to system with an undercharge will have low head pressures and substantially low suction pressures UNDERCHARGED REFRIGERANT SYSTEMS NOTE...

Page 14: ...compressor is running in a deep vacuum no load Much of the area of the condenser will be relatively cool since most or all of the liquid refrigerant will be storedthere The following conditions are ba...

Page 15: ...roke or not enough ow to maintain pres sure differential Check unit for correct operating pressures and charge Raise head pressure If no shift use valve with smaller port Body damage Replace valve Hot...

Page 16: ...t run Inoperative system switch Test switch replace if inoperative Broken loose or incorrect wiring Refer to applicable wiring diagram Open capacitor Test capacitor replace if inoperative Fan speed sw...

Page 17: ...y tube De ice coil Check temp differential delta T across coil Touch test coil return bends for same temp Test for low running current Problem Possible Cause Action Compressor runs continually does no...

Page 18: ...bulb Place jumper across t stat terminals to check if unit operates If unit operates replace t stat Loose or broken parts in t stat Check as above Incorrect wiring Refer to appropriate wiring diagram...

Page 19: ...hort cycles T stat differential too narrow Replace t stat Plenum gasket not sealing allowing discharge air to short cycle t stat Check gasket Reposition or replace as needed Restricted coil or dirty l...

Page 20: ...ace defrost control Defrost control contacts stuck If contacts remain closed between terminals 2 3 of the defrost control after preselected time interval has passed replace control Defrost control bul...

Page 21: ...eck temperature rise across coil Refer to speci cation sheet for correct temperature rise Reversing valve failing to shift completely bypassing hot gas De energize solenoid coil raise head pressure en...

Page 22: ...Compressor Undercharged Overcharged Refrigerant System Restriction Reversing Valve not Fully Seated Low Air ow Across Outdoor Coil Outdoor Ambient Too High for Operation in Heating Low Suction Pressu...

Page 23: ...23 MODEL SC06H10D...

Page 24: ...24 MODELS XQ05L10 A B XQ06L10 A B C D XQ08L10 A B XQ10L10 A B XQ12L10 A B...

Page 25: ...25 MODELS KS10L10 A RS10L10 A KS12L10 A KS12L30 A KS15L10 A RS15L10 A RS16L30 A RM18L30 A KM18L30 A KM21L30 A RM24L30 A KM24L30 A...

Page 26: ...26 MODELS SS08L10 A B SS10L10 A B SS12L10 A B SS12L30 A B SS14L10 A B SS16L30 A B SM18L30 A B SM21L30 A B SM24L30 A B...

Page 27: ...27 MODEL SL36L30 A...

Page 28: ...28 MODEL SL28L30 A...

Page 29: ...29 MODELS SL36L30 B...

Page 30: ...30 MODEL EQ08L11 A...

Page 31: ...31 MODELS ES12L33 A ES16L33 A EM18L34 A EM24L35 A...

Page 32: ...32 MODEL EL36L35 A...

Page 33: ...33 MODEL YS09L10 A YS09L10 B...

Page 34: ...34 MODELS YS13L33 A YM18L34 A...

Page 35: ...35 MODELS YL24L35 A...

Page 36: ...6 3 06 Friedrich Air Conditioning Co Post Office Box 1540 San Antonio Texas 78295 1540 4200 N Pan Am Expressway San Antonio Texas 78218 5212 210 357 4400 FAX 210 357 4480 www friedrich com Printed in...

Reviews: