PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation
or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the
forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3 way valve and opening the

low-pressure valve slightly.

(2) Close the valve stem of 2 way valve completely.
(3) Start the cooling operation or following forced cooling operation.

When using the remote control unit
Press the TEST RUN button after starting the cooling operation by the remote control unit.
The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so on.)
Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve when the reading on the compound pressure gage becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5) Stop the operation.

• Press the START/STOP button of the remote control unit to stop the operation.
• Press the MANUAL AUTO button when stopping the operation from indoor unit side.
  (It is not necessary to press on keeping for more than 10 seconds.)

 

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above  248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat insula-
tion around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if the
expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 68 °F).

 

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation with 2 way or 3 way valve open. This may cause abnormal
pressure in the refrigeration cycle that leads to breakage and even injury.

Summary of Contents for MW24C3F

Page 1: ...unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drippin...

Page 2: ...trol box cover 2 Fasten the Inter unit wire harness and power supply to the conduit holder using the lock nut 3 Connect inter unit wire harness and power supply to the terminal Refer to the wiring dia...

Page 3: ...usty 3 Do not install the unit where people pass 4 Take your neighbors into consideration so that they are not dis turbed by air blowing into their windows or by noise 5 Providethespaceshowninthefigur...

Page 4: ...ormal noise and vibration during operation 2 Will noise wind or drain water from the unit disturb the neighbors 3 Is there any gas leakage REMOTE CONTROL UNIT INSTALLATION 1 REMOTE CONTROL UNIT HOLDER...

Page 5: ...cer CONNECTING THE PIPING CONNECTION 1 Install the outdoor unit wall cap supplied with the optional installation set or procured at the site to the wall pipe 2 Connect the outdoor unit and indoor unit...

Page 6: ...3 way valve when the reading on the compound pressure gage becomes 0 05 0 MPa 0 5 0 kg cm2 5 Stop the operation Press the START STOP button of the remote control unit to stop the operation Press the...

Page 7: ...4 Shape the loop wire properly place it on the terminal board and tighten securely with the terminal screw using a screwdriver B For strand wiring 1 Cut the wire end with a wire cutter or wire cuttin...

Page 8: ......

Reviews: