background image

Ductless_Dual_Zone_Heat_Pump_Submittal_11

Ductless Split Systems

Wall Mounted, Heat Pump Single-zone 

Refrigeration line sets

Insulated line sets are available for all Friedrich split systems in 

15 ft. and 35 ft. lengths. Each line set is equipped with flare nuts 

on both ends. Both liquid and suction lines are insulated. Line 

sets can be joined together with field supplied double female 

connectors. Each system requires one line set for each indoor 

unit installed. On multi-zone systems, line sets should be ordered 

based on individual indoor unit capacities not total system 

capacity.  For example, a M18DYF uses 2 line sets for 9,000 Btu 

units, not 1 for the 18,000 Btu product.

NOTE: All models have low ambient 

capabilities built-in. Capacity is 

reduced as 0 degrees Fahrenheit is 

approached.
NOTE: All R410A models have 1/2˝ 

UNF 20 thread per inch charging and 

vacuuming ports. An adapter must be 

used for 1/4˝ gauges. Adapter part 

number 67270018 is available through 

Friedrich parts distributors.
Due to continuing research in 

new energy-saving technology, 

specifications are subject to change 

without notice.

Specifications

PERFORMANCE RATINGS

SYSTEM MODEL NO.

M18DYF

M21DYF

M24DYF

INDOOR MODEL

2 x MW09Y3FM

MW09Y3FM

MW12Y3FM

2 x MW12Y3FM

OUTDOOR MODEL

MR24DY3F

MR24DY3F

MR24DY3F

Capacity Cooling

Btu

9500 ea.

9500

12000

12000 ea.

CapaCity Cooling Min - Max

Btu

5100-11300 ea.

5100-11300 ea.

5100-13600 ea

5100-13600 ea

SenSible Heat Ratio

0.77

0.77

0.77

0.77

CapaCity Heating @ 47°F

Btu

11000 ea.

11000 ea.

14000

14000 ea.

CapaCity Heating Min - Max

Btu

5100-13000 ea.

5100-13000 ea. 5100-15400 ea.

5100-15400 ea.

CapaCity Heating @ 17°F

Btu

9500 ea.

9500 ea.

11000

10500 ea.

HSpF

9.0

9.0

9.0

SeeR

16.5

16.5

16.5

eeR

12.2

11.2

10.4

eneRgy StaR

YES

NO

NO

MoiStuRe ReMoval

Pts/h

2.9 ea.

2.9 ea

3.7 ea.

3.7 ea.

aiRFlow (Quiet, low, Med, HigH)

CFM

185,220,260,295

185,220,260,295 215,250,305,355

215,250,305,355

Sound Rating - indooR

dB-A

27,29,33,37

27,29,33,37

30,34,39,42

30,34,39,42

Sound Rating - outdooR

dB-A

52

52

52

opeRationg Range (Heating)

°F

0 - 115 (14 - 75)

0 - 115 (14 - 75)

0 - 115 (14 - 75)

eSt. yeaRly opeRating CoSt 

$128

$152

$152

$184

eleCtRiCal data (all indooR unitS ReCeive poweR FRoM outdooR unit; valueS liSted aRe total)
poweR SouRCe

230/(208)-60-1

230/(208)-60-1

230/(208)-60-1

Min. aMpaCity

A

15

15

15

Cooling wattS

W

1600

1900

2300

Max. td FuSe/bReakeR

A

20

20

20

ReFRigeRation SySteM
ReFRigeRant

R410A

R410A

R410A

CoMpReSSoR type

Inverter

Inverter

Inverter

ConneCtionS

Flare

Flare

Flare

liQuid line o.d.

in

1/4

"

1/4

"

1/4

"

1/4

"

SuCtion line o.d.

in

3/8

"

3/8

"

3/8

"

3/8

"

FaCtoRy pReCHaRge

ft

98'

98'

98'

Max. line lengtH

ft

Each unit:82  Total:98

Each unit:82  Total:98

Each unit:82  Total:98

Max. HeigHt diFFeRenCe

ft

33'

33'

33'

diMenSionS & weigHt
indooR unit
w x H x d

in

31 1/8

"

 x 10 7/8

"

 x 8 1/2

"

 ea.

31 1/8

"

 x 10 7/8

"

 x 8 1/2

"

 ea.

31 1/8

"

 x 10 7/8

"

 x 8 1/2

"

 ea.

net weigHt

lbs

21 ea.

21

21

21 ea.

SHipping weigHt

lbs

26 ea.

26

26

26 ea.

outdooR unit
w x H x d

in

35 3/8

"

 x 32 5/8

"

 x 13

"

35 3/8

"

 x 32 5/8

"

 x 13

"

35 3/8

"

 x 32 5/8

"

 x 13

"

net weigHt

lbs

136

136

136

SHipping weigHt

lbs

154

154

154

USED WITH:

LENGTH-FT. LIQUID SUCTION

KIT#

All 9000 and 

12000 Btu

indoor units

15'

1/4

3/8

T32150

35'

1/4

3/8

T32350