background image

9

10.Evacuate the system to an absolute holding

pressure of 200 microns or less.

NOTE: This procedure can be speeded up
by the use of heat lamps, or by breaking the
vacuum with refrigerant or dry nitrogen at
5,000 microns.  Pressure system to 5 PSIG
and leave in the system a minimum of 10
minutes.  Recover refrigerant, and proceed
with evacuation to a pressure of 200
microns or a minimum of 10%.

11. Break the vacuum by charging the system

from the high side with the correct amount
of refrigerant specified.  This will prevent
boiling the oil out of the crankcase.

NOTE:  If the entire charge will not enter
the high side, allow the remainder to enter
the low side in small increments while
operating the unit.

12.Restart the unit several times after allowing

pressures to stabilize.  Pinch off the process
tubes, cut and solder the ends.  Remove the
pinch off tool, and leak check the process
tube ends.

SPECIAL PROCEDURES IN THE CASE OF
COMPRESSOR MOTOR BURN-OUT

1. Recover all refrigerant and oil from the

system.

2. Remove the compressor, capillary tube and

filter drier from the system.

3. Flush the evaporator, condenser and all

connecting tubing with dry nitrogen, or
equivalent, to remove all contamination from
the system.  Inspect the suction and
discharge lines for carbon deposits.
Remove and clean if necessary.

4. Reassemble the system, including a new

drier-strainer and capillary tube.

5. Proceed with processing as outlined under

hermetic component replacement.

HERMETIC COMPONENT REPLACEMENT

The following procedure applies when replacing
components in the sealed refrigeration circuit or
repairing refrigerant leaks.  (Compressor,
condenser, evaporator, capillary tube,
refrigerant leaks, etc.)

1. Recover the refrigerant from the system at

the process tube located on the high side of
the system by installing a line tap on the
process tube.  Apply the gauge from the
process tube to EPA approved gauges from
the process tube to the EPA approved
recovery system.  Recover the CFC’s in the
system to at least 5%.

2. Cut the process tube below the pinch off in

the suction side of the compressor.

3. Connect the line from the nitrogen tank to

the suction process tube.

4. Drift dry nitrogen through the system and

unsolder the more distant connection first.
(Filter drier, high side process tube, etc.)

5. Replace the inoperative component, and

always install a new filter drier.  Drift dry
nitrogen through the system when making
these connections.

6. Pressurize the system to 30 PSIG with

proper refrigerant and boost the refrigerant
pressure to 150 PSIG with dry nitrogen.

7. Leak test the complete system with the

electric halogen leak detector, correcting
any leaks found.

8. Reduce the system to zero gauge pressure.

9. Connect the vacuum pump to the high side

and low side of the system with deep
vacuum hoses, or copper tubing. (Do not
use regular hoses.)

Summary of Contents for 2001 Hazardgard SH14J30A-1

Page 1: ...AMERICA S BEST AIR CONDITIONER 2001 HAZARDGARD ROOM AIR CONDITIONER Service Parts Manual Models SH14J30A 1 SH14J30A A SH20J30A 1 SH20J30A A HG2001 8 01...

Page 2: ...Ambient By Pass Valve 8 Sealed Refrigeration System Repairs 8 Hermetic Component Replacement 9 Special Procedure in the case of Compressor Motor Burn Out 9 Rotary Compressor Special Troubleshooting Se...

Page 3: ...0J30A 1 SH20J30A A BTUH 14000 14000 19000 18800 E E R Btu watt 8 0 8 0 8 5 8 5 Volts 230 208 230 208 Hertz Phase 60 1 60 1 Amperes 7 8 8 5 9 9 10 8 Total Watts 1750 1750 2235 2210 Fuse Breaker Size 15...

Page 4: ...g as one hour for the compressor to cool sufficiently for the internal overload to close COMPRESSOR WINDING TEST See Figure 1 Remove the compressor terminal box cover and disconnect the wires from the...

Page 5: ...on terminal of the capacitor and the black lead The motor should run at high speed CHECKING COMPRESSOR EFFICIENCY The reason for compressor inefficiency is normally due to broken or damaged suction an...

Page 6: ...ortant to the successful operation of the unit is the position of the sensing bulb in relation to the evaporator See Figure 7 RANGE Thermostat Part No 618 225 02 60 F 2 to 90 F 4 FIGURE 7 SENSING BULB...

Page 7: ...ted circuit board to the TRIAC causing it to switch on starting the compressor If the compressor fails to start and the compressor has been tested by the direct start method and the thermostat tests s...

Page 8: ...e by pass valve outlet which connects to the suction process tube When the low side pressure reaches approximately 50 psig the valve will begin to open and the tube will get hot This method will deter...

Page 9: ...emble the system including a new drier strainer and capillary tube 5 Proceed with processing as outlined under hermetic component replacement HERMETIC COMPONENT REPLACEMENT The following procedure app...

Page 10: ...only into the low side The introduction of liquid into the low side without the use of a capillary tube will cause damage to the discharge valve of the rotary compressor ROTARY COMPRESSOR SPECIAL TRO...

Page 11: ...Heat sink triac shorted PROBLEM POSSIBLE CAUSE TO CORRECT Turn to highest temperature setting to see of unit will cycle off Disconnect power to the unit Remove cover of thermostat and check if contac...

Page 12: ...ge at compressor terminals If voltage is satisfactory replace compressor Check windings for continuity and resistance Direct test compressor If direct test fails replace compressor Thermostat contacts...

Page 13: ...and remove old sealer from base pan and shroud Apply new sealer reinstall and check Clean with steam or detergent Adjust fan blade to 1 2 clearance from condenser coil Evaporator drain pan cracked or...

Page 14: ...14 WIRING DIAGRAM FOR SH14J30A SH20J30A...

Page 15: ...15 Hazardgard Cabinet Parts...

Page 16: ...16 Hazardgard Chassis Parts...

Page 17: ...803 47 Capacitor 25 7 5 MFD 440 Volt 1 1 8 618 298 00 Holder Thermostat 1 1 1 1 613 891 00 Connector E M T 1 1 1 1 618 212 00 Harness Wire Compressor 1 1 1 1 618 208 01 Harness wire Fan Motor 1 1 1 1...

Page 18: ...rd 1 1 1 1 22 605 420 03 Fan Blade 1 1 22 605 420 04 Fan Blade 1 1 23 606 106 03 Blower Wheel 1 1 23 606 106 01 Blower Wheel 1 1 24 618 033 00 Inner Wall 1 1 24 618 047 00 Inner Wall 1 1 25 618 025 00...

Page 19: ...Side 2 2 41 618 198 03 Angle Wingboard Side 2 2 42 606 103 03 Gasket Vinyl 1 1 1 1 608 460 16 Bag Assembly Hardware 1 1 1 1 617 173 01 Gasket Chassis Foam 1 1 1 1 618 116 20 Carton Shipping 1 1 618 1...

Page 20: ...Friedrich Air Conditioning Co 4200 North Pan Am Expressway P O Box 1540 San Antonio Texas 78295 1540 USA Tel 210 357 4400 Fax 210 357 4480 Printed in the U S A HG02001 8 01 Certified Parts Use Factor...

Reviews: