Rittal Liquid Cooling Package
"Row" operating modes, the air temperature is the sup-
ply air to the servers.
15.3.2
Activating the heaters
To activate the heaters, proceed as follows:
Assign the "YES" value to the "Resistance present"
entry in the "Ha25" menu.
Fig. 48:
"Ha25" menu
In order to reduce the heaters ON-OFF and stabilise as
much as possible the air temperature, the electric heat-
ers will be switched on at (set-point – Diff ON) and
switched off at (set-point – Diff ON + Diff OFF): Diff ON
and Diff OFF parameters can be set in the mask Gfc30.
Set the desired values for the "Diff ON" and "Diff OFF"
parameters in the "Gfc30" menu.
Fig. 49:
"Gfc30" menu
The thermal protection is done within an additional small
box placed externally to the main electrical box.
Fig. 50:
Additional box for the thermal protection of the electri-
cal heaters
15.3.3
Technical specifications
15.4
Dehumidification
15.4.1
General information
At installation locations where high humidity generally
prevails, there is the danger that water condenses inside
the IT cabinet. This can cause short-circuits and other
damage to the installed devices. Excessive humidity can
also lead to rust and corrosion.
To prevent this, the LCP DX can be equipped with a de-
humidification function, whereby a humidity sensor is
mounted on the inlet side of the device and a tempera-
ture sensor is mounted behind the evaporator. The
"Electrical heaters" option must also be installed (see
section 15.3 "Electrical heaters").
15.4.2
Activating the dehumidification
To activate the heaters, proceed as follows:
Assign the "YES" value to the "Enable" entry in the
"Ha30" menu.
Technical specifications
Power supply
1-phase 230 VAC /
50…60 Hz
Current consumption
9.1 A
Power consumption
2 kW
Tab. 28:
Technical specifications of the electrical heaters