AR 300 E/W
10
Type
Output*3
[°C]
Airflow
[m³/h]
∆
t*¹,*³
[°C]
Sound
level*²
[dB(A)]
Voltage
[V]
Amperage
[A]
Weight
[kg]
AR310W
16
1000/2000
30/23
43/58
230V~
2,1 A
42
AR315W
23
1400/2800
31/24
43/59
230V~
2,9 A
58
AR30W
33
2000/4000
31/25
46/62
230V~
4,2 A
78
Technical specifications |
Thermozone AR 300 W with water heat
2
Protection class AR 300 E/W above false ceiling: IP44, below false ceiling: IP20
Technical specifications |
Thermozone AR 300 E with electrical heat
3
Type
Output
steps
[ kW]
Airflow
[m³/h]
∆
t*¹
[°C]
Sound
level*²
[dB(A)]
Voltage
Amperage
(control)
Voltage
Amperage
(heat)
Weight
[kg]
AR310E09
0/4.5/9
1000/2000
27/14
43/59
230V~ / 2,1A
400 V3~ / 13 A
42
AR315E1
0/7/13.5
1400/2800
29/15
43/60
230V~ / 2,9A
400 V3~ / 19,5 A
58
AR30E1
0/9/18
2000/4000
27/14
46/63
230V~ / 4,2A
400 V3~ / 26 A
78
GB
*1)
∆
t = temperature rise of passing air at maximum heat output and lowest/highest airflow.
*2) Conditions: Distance to the unit: 5 metres. Directional factor: 2. Equivalent absorption area: 200 m2.
*3) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.