background image

ADR E

13

GB  

The air stream should therefore be directed 

outwards to withstand the load. Approximate-
ly  15° is a suitable angle. Generally speaking, 
the higher the load, the greater the angle is 
needed.

Basic setting fan speed

Set the fan speed using the fan speed controls 
so that the air speed 1 metre above the floor 
is 3-4 m/s. Note that the airflow direction and 
speed may need further fine adjustment de-
pending on the loading of the door.

Service, repairs and maintenance

For all service, repair and maintenance first 
carry out the following:
1. Disconnect the power supply.
2. The service hatch is opened by slackening 

off the screws on the underside of the unit 
as illustrated on page 2.

Maintenance

Since the fan motors and other components 
are maintenance free, no maintenance other 
than regular cleaning is necessary. This can 
vary depending on local conditions, howe-
ver undertake cleaning at least twice a year. 
Grille, impeller and elements can be vacuum 
cleaned or wiped using a dry cloth.

 

Avoid 

the use of strong alkaline or acidic cleaning 
agents.

Overheating

The air curtain unit with electric heater is 
equipped with an overheat protector. If it is 
deployed due to overheating, reset as follows:
1. Disconnect the electricity with the fully 

isolated switch.

2. Allow the electrical coil to cool.
3. Determine the cause of overheating and 

rectify the fault.

4. Reconnect the power and start the unit.

All motors are equipped with an integral ther-
mal safety cut-out. This will operate, stopping 
the air curtain should the motor temperature 
rise too high. The cut-out will automatically 
reset when the motor temperature has retur-
ned to within the motor’s operating limits.

Fan replacement

1. Determine which of the fans is not functio-

ning.

2. Disconnect the cables to the relevant fan.
3. Remove the screws securing the fan and lift 

the fan out.

4. Install the new fan in reverse order to the 

above.

Replacing the electric coil

1. Mark and disconnect the cables to the elec-

tric coil.

2. Remove the mounting screws securing the 

coil in the unit and lift the coil out.

3. Install the new coil in   reverse order to 

the above.

Trouble shooting

If the fans are stationary, check the following:
1. Operating power supply to the unit; check 

fuses, circuit-breaker, time switch/thermo-
stat (if any) that starts and stops the unit.

2. That the air flow selector is correctly set.
3. That the position limit switch is working (if 

installed).

4. That the intake grille is not dirty.

If there is no heat, check the following:
1. Power supply to electric heater coil; check 

fuses and circuit-breaker (if any).

2. That the heat demand exists; check ther-

mostat settings and actual temperature.

3. That the output selector (if any) is set cor-

rectly.

4. That the intake grille is not dirty.

If the fault cannot be rectified, please contact 
a qualified service technician.

Safety cut-out

(applies to units with electric heater)

If the installation is protected by means of a 
safety cut-out, which trips when the appliance 
is connected, this may be due to moisture 
in the heating element. When an appliance 
containing a heater element, has not been 
used for a long period and is stored in a damp 
environment, moisture can enter the element.

This should not be seen as a fault, but is 

Summary of Contents for Thermozone ADR 200 E

Page 1: ...Thermozone ADR 200 300 E 8 SE 12 GB ...

Page 2: ...ADR E 35 35 720 40 L 2 40 330 260 L 70 160 200 460 260 260 M8 Service opening Access neccessary Type L mm ADR210E 310E 1000 ADR215E 315E 1500 ADR220E 320E 2000 To open 1 2 ...

Page 3: ... gallerhållarna i fästena i ADR och lägg försik tigt i gallret Vik ner låsdelen till den snäpper fast lås fast med skruv 5 Unscrew the screws holding the inlet grille Keep the grille Lossa skruvarna till insugsgallret Spara gallret 2x 2x 6 2x a Use the holders 2x mounted on the grille to hang the grille Använd fästena 2x som sitter i gallret för att hänga gallret Fold in the grille make sure the s...

Page 4: ...L nr NO HxWxD mm CB32N 87 511 85 54 910 92 155x87x50 ADEA 87 514 70 49 360 04 89x89x26 ADEAEB 87 514 72 49 360 05 ADEAIS 87 514 76 49 360 07 75x75x27 ADEAGD 1 MDC RTI2 85 811 44 54 910 90 150x80x43 ADEA Accessories CB32N MDC MDCDC included ...

Page 5: ... C3 C1 C6 C7 C2 S4 C F3 60º C F2 80º C F4 50º Trafo I II I II III Wind indicator Fuse M M 1 M 1 1 230V 230V 400V3 C F5 40º 0 0 C Thermozone ADR200E ADR300E 230V 2 3 4 5 6 1 2 3 4 5 6 7 L N 1 CB32N Hi Lo RTI2 7 8 9 1011 230V Motor and control ADR200E ADR300E CB32N 6x0 5mm2 6x0 5mm2 6x0 5mm2 2 PE ADR200E ADR300E 2 PE 4x0 5mm2 2 PE RTI2 400V3 Heat 400V3 Heat ...

Page 6: ...II Wind indicator Fuse Thermozone ADR200E ADR300E M M 1 M 1 1 230V 230V 400V3 2 3 4 5 6 1 2 3 4 5 6 7 L N 1 CB32N Hi Lo RTI2 MDC N L DC DC 12 11 14 22 21 24 32 31 34 Door contact 7 8 9 1011 C F5 40º 230V Motor and control ADR200E ADR300E CB32N 6x0 5mm2 6x0 5mm2 6x0 5mm2 2 PE ADR200E ADR300E 2 PE MDC Door contact 5x0 5mm2 4x0 5mm2 2x0 5mm2 2 PE 2 PE RTI2 400V3 Heat 400V3 Heat ...

Page 7: ... 230V 400V3 C F5 40º ADEAEB ADEAR 1 2 L N 4 5 8 9 20 21 31 41 50 11 51 81 80 83 82 84 86 85 87 G2 G1 G4 G3 G5 C2 C1 C3 C6 C7 30 40 6 6 4 5 8 7 9 11 10 230V ADEAOS ADEAIS Thermozone ADR200E ADR300E ADEAGD MDCDC 230V Motor and control ADR200E ADR300E ADEAEB ADEAGD 10x0 5mm2 10x0 5mm2 10x0 5mm2 2 PE 400V3 Heat 400V3 Heat ADR200E ADR300E 2 PE ADEAR ADEAIS ADEAOS MDCDC 8x0 5mm2 2x0 5mm2 2x0 5mm2 2x0 5m...

Page 8: ...tt service luckan är åtkomlig och kan öppnas helt Aggregatet har 6 stycken 9 st för 2 meters modellen fasta muttrar på ovansidan i storlek M8 för takmontage med gängad stång Se skis ser på s 2 3 Elinstallation Elanslutning skall utföras av behörig installa tör och i enlighet med denna bruksanvisning samt gällande föreskrifter 1 Serviceluckan öppnas genom att lossa skru varna på aggregatets undersi...

Page 9: ...äkten enligt ovanstående i omvänd ordning Byte av elbatteri 1 Lossa kablarna till elbatteriet 2 Lossa fästskruvarna som låser batteriet i aggregatet och lyft ut batteriet 3 Montera det nya batteriet enligt ovanstående i omvänd ordning Felsökning Om fläktarna inte blåser kontrollera följande 1 Att manöverspänning finns fram till aggre gatet kontrollera säkringar arbetsbrytare eventuellt kopplingsur...

Page 10: ... 53 60 230V 2 3 A 400V3 17 5 A 56 ADR320E 0 12 18 1750 2630 3500 31 20 15 45 55 62 230V 3 9 A 400V3 26 A 81 1 Dt temperaturhöjning på genomgående luft vid maximal värmeeffekt och lågt medium högt luftflöde 2 Förutsättningar Avstånd till aggregat 5 m Riktningsfaktor 2 Ekvivalent absorptionsyta 200 m2 Kapslingsklass ADR E IP23 strilsäkert utförande Säkerhet Säkerställ att området kring apparatens in...

Page 11: ...t styrkort ADEAEB IP55 för externt montage ADEAEB måste kompletteras med styrkort ADEAGD för kompatibilitet med ADR Det behövs en ADEA till varje öppning men den kan styra flera luftridåer IP30 MDC magnetisk dörrkontakt med tidrelä Startar luftridå eller ökar fläkthastigheten från låg till högfart när dörr öppnas Då dör ren stängs fortsätter aggregatet att gå under inställd tid 2 s 10 min Speciell...

Page 12: ...g When the space is limited the telescopic inlet outlet extension may be removed The lower part of the air curtain is then mounted level with the false ceiling For the protection of wider doorways seve ral units can be mounted next to each other Ensure that the service hatch is accessible and can be fully opened The unit has 6 9 on 2 metre models M8 fixed nuts on the upper side for ceiling instal ...

Page 13: ...should the motor temperature rise too high The cut out will automatically reset when the motor temperature has retur ned to within the motor s operating limits Fan replacement 1 Determine which of the fans is not functio ning 2 Disconnect the cables to the relevant fan 3 Remove the screws securing the fan and lift the fan out 4 Install the new fan in reverse order to the above Replacing the electr...

Page 14: ...f passing air at maximum heat output and low medium high airflow 2 Conditions Distance to unit 5 m Direction factor 2 Equivalent absorption area 200 m2 Protection class ADR E IP23 simply rectified by connecting the appliance to the mains supply via a socket without a safety cut out so that the moisture can be driven out of the element The drying time can vary from a few hours to a few days As a pr...

Page 15: ...d ADEAEB IP55 for external installation ADEAEB must be supplemented with a control card ADEAGD for compatibility with ADR One ADEA is needed for each opening but it may control several air curtains IP30 MDC magnetic door contact with time delay Starts the air curtain or increases the fan speed from low to high speed when the door is opened When the door is closed the unit continues running for the...

Page 16: ...nited Kingdom Frico Limited Tel 44 0 121 322 0854 72 Cheston Road Fax 44 0 121 322 0858 B7 5EJ info uk frico se UK Birmingham www frico co uk United Kingdom Russia Frico repr office in Russia Tel 7 495 238 63 20 Lavrov per 6 7 495 676 44 48 RU 109044 Moscow Fax 7 495 676 44 48 Russia frico trankm ru www frico se China Frico repr office in China Tel 86 21 62569900 Rm 702 Mod Comm Build Fax 86 21 62...

Reviews: