Troubleshooting  

If the fans are not running or do not perform 

properly, check the following: 

•  The power supply.  

• 

That the intake grille/filter is not dirty. 

•  That the motor's safety cut-out has not been 

deployed.

•  Functions and settings of the FC control 

system, see the FC manual.  

 

If there is no heat, check the following: 

•  Functions and settings of the FC control 

system, see the FC manual.  

 

For units with a water coil, also check the 

following:

•  That the water coil is air free.

• 

That there is sufficient water flow and 

pressure.

•  That incoming water is heated adequately.

  

If the fault cannot be rectified, please contact a 

qualified service technician. 

Replacing the PC board 

1. The PC board is located in the terminal box 

on the unit's long side.  

2. Mark and disconnect the cables to the PC 

board.  

3. Unhatch the board from its PCB snap-in 

spacers and lift out.  

4. Install the new PC board as above in reverse 

order. 

Safety cut-out 

All motors are equipped with an integrated 

safety cut-out. This will operate, stopping the 

air curtain should the motor temperature rise 

excessively or the electronics fail or overheat. 

The cut-out will automatically reset when the 

motor temperature has returned to within the 

motor’s operating limits. Failure or damage to 

electronics components may require repair or 

replacement of such components or the entire 

product.  

 

Fan replacement 

1. Determine which of the fans is not 

functioning.

2. Disconnect the cables from the relevant fan.

3. Remove the screws securing the fan and lift 

the fan out.

4. Install the new fan as above in reverse order.

Packaging

Packaging materials are chosen with 

consideration to the environment and are 

therefore recyclable.  

 

Handling of product at end of working 

life

This product may contain substances necessary 

for the functionality of the product but 

potentially dangerous for the environment. The 

product should not be disposed of mixed with 

general household waste but delivered to a 

designated collection point for environmental 

recycling. Please contact the local authority 

for further details of your nearest designated 

collection point.  

 

Safety  

• 

Keep the areas around the air intake and 

exhaust grilles free from possible obstructions!

 

• 

The unit must not be fully or partially covered as 

overheating can result in a fire risk! 

 

• 

Lifting equipment must be used to lift the unit.

 

• 

This appliance can be used by children aged 

from 8 years and above and persons with 

reduced physical, sensory or mental capabilities 

or lack of experience and knowledge if they 

have been given supervision or instruction 

concerning use of the appliance in a safe way 

and understand the hazards involved. Children 

Replacing the water coil (W) 

A horizontally mounted unit must be 

demounted and placed on a suitable working 

level before accessing the water coil. The unit 

must be lifted by the holes in the motor section. 

NOTE: The unit can not be lifted by its mid 

section as the outlet grille might be damaged. 

1. Disconnect the power supply. 

2. Shut off the water supply to the unit. 

3. Disconnect the connections to the water coil. 

4. If horizontally mounted, demount the unit.  

5. Loosen the motor section on the unit's top 

(horizontal), back (vertical) by removing its 

screws.  

6. Fold the section towards the cable side. 

NOTE: Be careful to prevent the section from 

falling.  

7. Remove the mounting screws securing the 

coil in the unit and lift out.

8. Install the new coil in reverse order to the 

above. 

Summary of Contents for Tatra

Page 1: ...Tatra 14 EN 18 SE Original instructions 22 NO 26 FR 31 DE 36 NL 41 ES 46 IT 51 PL 56 RU 61 FI DK 66 ...

Page 2: ... Voor een vertaling van de gebruikte Engelse teksten zie de pagina s van de resp taal NL Las páginas introductorias contienen básicamente imágenes Consulte la traducción de los textos en inglés que las acompañan en las páginas del idioma correspondiente ES Le pagine introduttive contengono prevalentemente immagini Per le traduzioni dei testi scritti in inglese vedere le pagine nelle diverse lingue...

Page 3: ...6028 2750 L mm TA6017 TA6FF 1710 TA6022 TA6FF 2260 TA6028 TA6FF 2810 Vertical mounting Horizontal mounting 60 625 L 551 507 G1 DN25 G1 DN25 59 507 230 61 61 230 551 625 181 L TA6FF Floor frame 2 DN25 1 outside thread 2 DN25 1 outside thread FC FC ...

Page 4: ...atra 4 Horizontal mounting 300 Minimum distance Item number Type Consists of 397713 TA6AB 4 x appliance brackets 382973 TA6ABE 2 x appliance brackets TA6AB Appliance brackets L Distance appliance brackets x4 L mm TA6017 1600 TA6022 2150 TA6028 2700 2 x Tatra ...

Page 5: ...660 580 400 320 230 60 Item number Type Consists of 397712 TA6WK 2 x wall brackets 4 x appliance brackets 4 x threaded rods M10 1000 mm nuts 382975 TA6WKE 1 x wall bracket 2 x appliance brackets 2 x threaded rods M10 1000 mm nuts x4 x4 x2 1004 617 807 Horizontal mounting ...

Page 6: ...A6CK 2 x ceiling brackets 4 x appliance brackets 4 x threaded rods M10 1000 mm nuts 382977 TA6CKE 1 x ceiling bracket 2 x appliance brackets 2 x threaded rods M10 1000 mm nuts x4 x4 x2 Horizontal mounting 55 1100 109 1100 1026 870 636 500 266 105 131 61 55 211 109 ...

Page 7: ...tical mounting 300 Minimum distance Note The air curtain must be secured in the wall or ceiling TA6FF Floor frame TA6TB Top bracket Joining brackets x2 included in delivery Max 6 6 m Mounting on top of each other ...

Page 8: ... 8 547 480 Ø 11 x 6 305 235 441 416 380 20 60 TA6FF Floor frame TA6TB Top bracket max 425 min 112 287 190 145 80 35 23 5 max 425 min 112 Item number Type 280021 TA6FF 382758 TA6TB Ø 11 x 6 Vertical mounting ...

Page 9: ...tem number Type Consist of Dimension 264883 TA6EF 1 pcs Ø480 x 100 mm 330955 FH1025 2 pcs DN25 1000 mm TA6EF Accessories 2 FH1025 SDM VPFC Valve systems Item number Type DN Flow range l s 238293 VPFC15LF DN15 0 012 0 068 238294 VPFC15NF DN15 0 024 0 13 238295 VPFC20 DN20 0 058 0 32 238296 VPFC25 DN25 0 10 0 60 238297 VPFC32 DN32 0 22 1 03 See separate manual TAC AV ...

Page 10: ...9x39x23 mm 74695 FCOTX 39x39x23 mm 74699 FCLAP 89x89x26 mm 74702 FCWTA for water heated units 17495 FCDC 74718 FCBC05 5 m 74719 FCBC10 10 m 74720 FCBC25 25 m 74721 FCSC10 10 m 74722 FCSC25 25 m 74703 FCTXRF for FC Smart FC Pro 89x89x26 mm Accessories FCDA FC Direct FCSA FC Smart FCPA FC Pro FCBA FC Building FCLAP See separate manual for FC FCBC10 FCDC FCCF FCLAP FCBC10 FCDC FCCF FCLAP FCTXRF FCBC1...

Page 11: ...Tatra 1 Ambient no heat TA6000 A IP44 Item number Type Output kW Airflow 1 m3 h Sound power 2 dB A Sound pressure 3 dB A Motor W Amperage motor A Weight kg 247348 TA6017A 0 3400 9900 87 4471 920 4 0 55 247349 TA6022A 0 5100 13400 87 45 71 1230 5 5 71 247350 TA6028A 0 6100 17500 93 53 77 1540 6 7 88 2 Water heat TA6000 W IP44 Item number Type Output 5 kW Output 6 kW Airflow 1 m3 h t 4 5 C t 4 6 C W...

Page 12: ...1O2 PE A1 A2 GND GND B1B2 D1 D2 ON OFF Termination 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND 0 10V L N PE GND 0 10V L N PE GND 0 10V PE GND L N TA6000 A M M M M M 230V Tatra 12 TA6000 A Wiring diagrams for control system in the FC manual TA6017 3 motors TA6022 4 motors TA6028 5 motors ...

Page 13: ...et sensor A1 A2 GND GND B1 B2 D1 D2 ON OFF Termination 12V HI LO GND 12V HI LO BUS 1 BUS 2 GND Actuator 24V WTA E1 E2 0 10V L N PE GND 230V 0 10V L N PE GND 0 10V PE GND L N TA6000 W M M M M M Tatra 13 TA6000 W Wiring diagrams for control system in the FC manual TA6017 3 motors TA6022 4 motors TA6028 5 motors ...

Page 14: ...and maintenance The FC terminal box is placed on the unit s long side and must be fully accessible after installation Horizontal mounting The air curtain is installed horizontally with the outlet air grille facing downwards as close to the door as possible Tatra can be mounted on the wall or on the ceiling Mounting with wall brackets A complete kit for wall mounting is available containing wall br...

Page 15: ...on which should be preceded by an isolator switch with a contact separation of at least 3 mm should only be wired by a competent electrician and in accordance with the latest edition of IEE wiring regulations The air curtain has an integrated PC board which is connected to the selected external control system FC FC must be ordered separately The PC board is located in the terminal box on the unit ...

Page 16: ... with consideration to the environment and are therefore recyclable Handling of product at end of working life This product may contain substances necessary for the functionality of the product but potentially dangerous for the environment The product should not be disposed of mixed with general household waste but delivered to a designated collection point for environmental recycling Please conta...

Page 17: ...ded that it has been placed or installed in its intended normal operating position and they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children aged from 3 years and less than 8 years shall not plug in regulate and clean the appliance or perform user maintenance CAUTION Some parts of this product can become very hot ...

Page 18: ......

Page 19: ...2022 10 19 CH HH Main office Frico AB Tel 46 31 336 86 00 Industrivägen 41 SE 433 61 Sävedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net ...

Reviews: