![Frico PA2500 Original Instructions Manual Download Page 18](http://html.mh-extra.com/html/frico/pa2500/pa2500_original-instructions-manual_2332200018.webp)
PA2500
18
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +32 °C
Water temperature: 60/40 °C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA2510W
Max
1300
6,4
50,0
0,16
7,1
4,7
28,6
0,06
1,2
Min
900
4,5
45,0
0,07
1,8
3,7
30,0
0,05
0,8
PA2515W
Max
2100
10,5
45,0
0,17
11,3
9,2
30,8
0,11
5,4
Min
1250
6,6
40,0
0,08
3,0
6,6
33,5
0,08
3,0
PA2520W
Max
2600
13,1
45,0
0,21
20,3
11,5
31,0
0,14
9,8
Min
1800
9,1
40,0
0,11
6,5
9,1
32,9
0,11
6,5
See www.frico.se for additional calculations.
*
1
) Recommended outlet air temperature for good comfort and optimized output.
*
2
) Nominal output at given supply and return water temperature.
Supply water temperature: 55°C
Room temperature: +18 °C
Outlet air temperature: +29 °C
Water temperature: 55/35°C
Room temperature: +18 °C
Type
Fan
position
Airflow
[m
3
/h]
Output
[kW]
Return
water
temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
Output *
2
[kW]
Outlet
air temp.
[°C]
Water
flow
[l/s]
Pressure
drop
[kPa]
PA2510W
Max
1300
6,4
50,0
0,34
29,3
3,5
25,9
0,04
0,7
Min
900
4,2
44,0
0,09
2,7
2,6
26,6
0,03
0,5
PA2515W
Max
2100
10,3
46,0
0,28
27,5
7,3
28,2
0,09
3,7
Min
1250
6,1
39,0
0,09
4,1
5,2
30,3
0,06
2,1
PA2520W
Max
2600
12,7
46,0
0,34
48,7
9,3
28,5
0,11
6,9
Min
1800
8,5
39,0
0,13
8,8
7,4
30,0
0,09
4,6
Output charts water PA2500