Trouble shooting  

If the fans are not working or do not blow properly, 
check the following: 

•  The functions and settings of the built-in 

control system. 

•  That the intake grille/filter is not dirty. 
 

If there is no heat, check the following: 

•  The functions, internal sensor and settings 

of the built-in control system. 

  

Replacing motor or impeller 

1. Remove the front.  
2. Remove gable end. 
3. Remove the screw between motor and fan.   
4. Disconnect the cables to the motor. 
5. Remove the screws securing the motor and 

lift it out together with the impeller.

6. Install the new motor and/or the new 

impeller as above in reverse order.  

Replacing heating elements/heating 
package (E) 

1. Mark and disconnect the cables to the 

heating elements/package 

2. Remove the mounting screws securing the 

heating elements/package in the unit and 
lift the heaging elements/package out.

3. Install the new heating elements/package in 

reverse order to the above.  

Replacing the water coil (W) 

1. Shut off the water supply to the unit. 
2. Disconnect the connections to the water 

coil.

3. Remove the mounting screws securing the 

coil in the unit and lift the coil out. 

4. Install the new coil in reverse order to the 

above. 

Draining the water coil (W) 

The drain valve is on the underside of the coil 
on the connector side. It can be accessed via 
the front hatch.
 

Maintenance 

 Unit with water heating

The appliance filter should be cleaned 
regularly to ensure the air curtain effect and 
the heat emission from the device. How often 
depends on local circumstances. A clogged 
filter is not a risk, but the appliance function 
can fail.  
1. Disconnect the power supply. 
2. The front hatch is removed by removing 

the screws on the top of the unit and then 
detach the bent edge at the bottom. (Fig.3)

3. Remove the filter and vacuum clean or 

wash it. If the filter is clogged or damaged, it 
may need to be changed. 

  

All units:  

Since fan motors and other components are 
maintenance free, no maintenance other than 
cleaning is necessary. The level of cleaning 
can vary depending on local conditions. 
Undertake cleaning at least twice a year. Inlet 
and exhaust grilles, impeller and elements 
can be vacuum cleaned or wiped using a 
damp cloth. Use a brush when vacuuming 
to prevent damaging sensitive parts. Avoid 
the use of strong alkaline or acidic cleaning 
agents. 

Overheating  

The air curtain unit with electric heater is 
equipped with an overheat protector. If it is 
deployed due to overheating, reset as follows: 
1. Disconnect the electricity with the fully 

isolated switch. 

2. Determine the cause of overheating and 

rectify the fault. 

3. Remove the front hatch.
4. Press the red button located inside the 

air curtain unit, at the inner gable of the 
terminal box. 

5. Reattach the front hatch and connect the 

unit again.

 
All motors are equipped with an integral 
thermal safety cut-out. This will operate, 
stopping the air curtain should the motor 
temperature rise too high. The cut-out 
will automatically reset when the motor 
temperature has returned to within the 
motor’s operating limits.
 

Temperature control 

See control pages. 

Summary of Contents for 2210CA

Page 1: ...PA2200C 20 SE 27 EN Original instructions 33 NO 40 DE 48 ES 55 FR 63 IT 71 NL 79 PL 86 RU 92 FI...

Page 2: ...setzung der verwendetenTexte in englischer Sprache siehe die entsprechenden Sprachseiten DE Las p ginas introductorias contienen b sicamente im genes Consulte la traducci n de los textos en ingl s que...

Page 3: ...345 min 500 min 500 min 500 157 157 157 90 5 10 20 40 22 210 165 184 1026 1536 2026 1050 1560 2050 Cu 15 53 71 40 min 500 min 500 157 157 Cu 15 PA2200C 3 PA2200C Gland Knock out Knock out Knock out Gl...

Page 4: ...PA2200C 4 Fig 3 Open the unit A B C TX20...

Page 5: ...30 mm 60 mm min 60 PA2200C 5 Fig 4 Fig 5 Minimum distance...

Page 6: ...min 500 mm 20 35 75 210 33 8 3x 5 10 162 PA2200C 6 Fig 6 Mounting with wall brackets Mounting with wall brackets A B C PA2210 2 pcs PA2215 2 pcs PA2220 3 pcs D...

Page 7: ...25 DN25 VLSP32 DN32 VOT15 DN15 VOT20 DN20 VOT25 DN25 PA2200C 7 PA2DR PA34TR15 PA2210C PA2215C 1 m PA34TR20 PA2220C 1 m PA2P15 PA2210C PA2215C 1 m PA2P20 PA2220C 1 m PA2PF15 PA2210C PA2215C PA2PF20 PA2...

Page 8: ...050 35 2 Water heat PA2200C W 3 Electrical heat PA2200C E 1 Ambient no heat PA2200C A 1 Lowest highest airflow of totally 3 fan steps 2 Sound power LWA measurements according to ISO 27327 2 2014 Insta...

Page 9: ...PA2210CA PA2215CA PA2220CA Right motor Left motor Only 2 m version PA2200C 9 PA2210CA PA2215CA PA2220CA...

Page 10: ...2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR M Blue Black Brown C Over heat cut out C C1 L2 PE L1 L N L3 400V 3N L2 PE L1 L N L3 230V 2210CE03 2210CE05 PA2210CE03 PA2210CE05 C3 Run...

Page 11: ...H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR M Blue Black Brown C Lo Mid Run Over heat cut out C C1 L2 PE L1 L N L3 230V 2210CE051 PA2210CE051 PA2200...

Page 12: ...R INTERNAL SENSOR IR C2 Over heat cut out C C1 L2 PE L1 L N L3 400V 3N Over heat C cut out PA2215CE08 PA2220CE10 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor On...

Page 13: ...out C C1 C1 low power C2 high power L2 PE L1 L N L3 400V 3N Over heat C cut out PA2210CE08 PA2215CE12 PA2220CE16 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor On...

Page 14: ...L PE 0 10V 0 10V HEAT ALARM WATER INTERNAL SENSOR IR PA2210CW PA2215CW PA2220CW M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor Only 2 m version C3 Run C2 Lo C1 M...

Page 15: ...M WATER INTERNAL SENSOR IR C2 Over heat cut out C C1 L2 PE L1 L N L3 400V 3N Over heat C cut out 230V 3 400V 3 a1 a2 b2 c2 c1 b1 a1 a2 b2 c2 c1 b1 L2 PE L1 L N L3 230V 3 PA2210CE05YD PA2215CE08YD M Bl...

Page 16: ...A2220CE10YD L2 PE L1 L3 400V3 L2 PE L1 L3 230V3 C4 C3 230V 3 400V 3 a1 a2 b2 c2 c1 b1 a1 a2 b2 c2 c1 b1 M Blue Black Brown C Right motor M Blue Black Brown C C3 Run C2 Lo C1 Mid Left motor C3 Run C2 L...

Page 17: ...PAMLK C NC NO Motor alarm pot free contact M Blue Black Brown C Lo Mid Run Left motor Only 2 m version 5A x 3 5A 16A N H1H2 N 1 On Off F1 F2 F3 on off 2 N L PE N L PE 0 10V 0 10V HEAT ALARM WATER INTE...

Page 18: ...53 1 0 07 2 9 13 6 40 2 0 17 13 5 min 1000 5 8 43 3 0 03 0 7 9 5 45 9 0 12 7 0 PA2220CW max 2400 13 9 55 4 0 10 2 7 17 7 39 7 0 22 11 1 min 1400 8 1 46 2 0 05 0 7 12 8 45 0 0 16 6 3 Supply water temp...

Page 19: ...1 6 See www frico se for additional calculations 1 Recommended outlet air temperature for good comfort and optimized output 2 Nominal output at given supply and return water temperature Supply water...

Page 20: ...lly heated units is 1800 mm For other minimum distances see fig 4 Mounting with wall brackets fig 6 1 Mount the brackets on the wall see fig 6A and dimension drawing fig 1 If the wall is uneven the br...

Page 21: ...pipes and subsequent water leakage during connection to water supply pipe work Dimensioning of external wiring shall comply with applicable regulations and local deviations may occur Minimum area Cont...

Page 22: ...rtain effect and the heat emission from the device How often depends on local circumstances A clogged filter is not a risk but the appliance function can fail 1 Disconnect the power supply 2 The front...

Page 23: ...ating also check the fol lowing Power supply to electric heater coil check fuses and circuit breaker if any That the overheat protection for the motors has not been deployed For units with water coil...

Page 24: ...etting dip switches Unit with water heating Dip switch 3 is used for PA2DR optional OFF Actuator SD230 remove the quick connector Black Brown Blue External on off Eg time switch External potential fre...

Page 25: ...minutes to vent out the heat if the temperature rises above 50 C again during the following 5 minutes overheating alarm is deployed The red LEDs flash and all the buttons are locked 1 Disconnect the e...

Page 26: ...o AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local contact www frico net Art no 208873...

Reviews: