Frico 161049 Original Instructions Manual Download Page 6

PAEC4000

6

Output charts water PAEC4000

Imperial chart

*

1

) Recommended outlet air temperature for good comfort and optimized output. 

*

2

) Nominal output at given supply and return water temperature. 

Supply water temperature:176 °F

 

Room temperature: +64 °F

 

Outlet air temperature: +95 °F*

1

Water temperature: 176/140 °F

 

Room temperature: +64 °F

 

Type

Fan 

 

position

Airflow

 

 

 

[cfm]

Output  

 

[MBH]

Return 

 

water 

temp. 

[°F]

Water 

 

flow

 

 

[US gal/h]

Pressure 

drop

 

 

[kPa]

Output*

2

 

 

 

[MBH]

Outlet

 

air 

temp. 

[°F]

Water 

 

flow

 

 

[US gal/h]

Pressure 

drop

 

 

[kPa]

PAEC4010W-NA

max

1530

50.9

88

69.4

2.7

96.9

122

330.0

40.5

PAEC4015W-NA

max

2000

65.9

84

86.6

1.6

137.2

127

466.1

30.6

PAEC4020W-NA

max

2855

96.6

86

130.3

1.6

193.2

127

657.2

26.9

PAEC4025W-NA

max

3090

104.4

81

133.2

2.0

223.5

131

760.9

42.0

Supply water temperature: 140 °F

 

Room temperature: +64 °F

 

Outlet air temperature: +95 °F*

1

Water temperature: 140/104 °F

 

Room temperature: +64 °F

 

Type

Fan 

 

position

Airflow

 

 

 

[cfm]

Output  

 

 

[MBH]

Return      

water 

temp. 

[°F]

Water 

 

flow

 

 

[US gal/h]

Pressure 

drop

 

 

[kPa]

Output*

2

 

 

 

[MBH]

Outlet

 

air 

temp. 

[°F]

Water 

 

flow

 

 

[US gal/h]

Pressure 

drop

 

 

[kPa]

PAEC4010W-NA

max

1530

52.6

99

156.9

11.5

56.3

99

190.2

16.2

PAEC4015W-NA

max

2000

68.6

95

183.6

6.2

79.9

100

269.2

12.2

PAEC4020W-NA

max

2855

96.6

95

257.8

5.5

112.3

100

379.5

10.7

PAEC4025W-NA

max

3090

105.5

95

257.8

6.5

132.1

104

447.0

17.2

*

1

) Recommended outlet air temperature for good comfort and optimized output. 

*

2

) Nominal output at given supply and return water temperature. 

Supply water temperature:80 °C

 

Room temperature: +18 °C

 

Outlet air temperature: +35 °C*

1

Water temperature: 80/60 °C

 

Room temperature: +18 °C

 

Type

Fan 

 

position

Airflow

 

 

 

[m

3

/h]

Output  

 

 

[kW]

Return 

water 

temp. 

[°C]

Water 

 

flow

 

 

[l/s]

Pressure 

drop

 

 

[kPa]

Output*

2

 

 

 

[kW]

Outlet

 

air temp. 

 

 

[°C]

Water

 

flow

 

 

[l/s]

Pressure 

drop

 

 

[kPa]

PAEC4010W-NA

max

2600

14.9

31

0.07

2.7

28.4

50

0.35

40.5

PAEC4015W-NA

max

3400

19.3

29

0.09

1.6

40.2

53

0.49

30.6

PAEC4020W-NA

max

4850

28.3

30

0.14

1.6

56.6

53

0.69

26.9

PAEC4025W-NA

max

5250

30.6

27

0.14

2.0

65.5

55

0.80

42.0

Supply water temperature: 60 °C

 

Room temperature: +18 °C

 

Outlet air temperature: +35 °C*

1

Water temperature: 60/40 °C

 

Room temperature: +18 °C

 

Type

Fan 

 

position

Airflow

 

 

 

[m

3

/h]

Output  

 

 

[kW]

Return 

water 

temp. 

[°C]

Water 

 

flow

 

 

[l/s]

Pressure 

drop

 

 

[kPa]

Output*

2

 

 

 

[kW]

Outlet

 

air temp. 

 

 

[°C]

Water

 

flow

 

 

[l/s]

Pressure 

drop

 

 

[kPa]

PAEC4010W-NA

max

2600

15.4

37

0.17

11.5

16.5

37

0.20

16.2

PAEC4015W-NA

max

3400

20.1

35

0.19

6.2

23.4

38

0.28

12.2

PAEC4020W-NA

max

4850

28.3

35

0.27

5.5

32.9

38

0.40

10.7

PAEC4025W-NA

max

5250

30.9

35

0.27

6.5

38.7

40

0.47

17.2

Metric chart

Summary of Contents for 161049

Page 1: ...ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program The AM...

Page 2: ...NA 8 24 4650 82 30 1000 6 0 600V3 24 84 PAEC4025E30 600VNA 10 30 5600 83 38 1173 7 5 600V3 30 106 Type Output 4 kW Airflow 1 m3 h Sound power 2 dB A Motor power W Voltage motor V Amperage motor A Wate...

Page 3: ...C4000E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and...

Page 4: ...NA 27 82 2800 82 30 1000 6 0 600V3 24 185 PAEC4025E30 600VNA 34 102 3300 83 38 1173 7 5 600V3 30 234 Type Output 4 MBH Airflow 1 cfm Sound power 2 dB A Motor power W Voltage motor V Amperage motor A W...

Page 5: ...00E and PAEC4000A shown herein are licensed to bear the AMCA Seal The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and com...

Page 6: ...6 6 2 79 9 100 269 2 12 2 PAEC4020W NA max 2855 96 6 95 257 8 5 5 112 3 100 379 5 10 7 PAEC4025W NA max 3090 105 5 95 257 8 6 5 132 1 104 447 0 17 2 1 Recommended outlet air temperature for good comfo...

Page 7: ...s EN Les pages de pr sentation contiennent principalement des images Pour la traduction des textes en anglais consultez la page correspondante la langue souhait e Las p ginas introductorias contienen...

Page 8: ...80 Q 36 1 44 R 1572 62 88 PAEC4015x S 2062 82 48 PAEC4020x T 2572 102 88 PAEC4025x U 1515 60 60 PAEC4015x V 2004 80 16 PAEC4020x W 2515 100 60 PAEC4025x X 23 0 92 Y 40 1 60 Z 611 24 44 611 L 295 36 40...

Page 9: ...position with the front hatch hook Fig 2 Control card SIRe is integrated in the air curtain at delivery SIRe Fig 1B When the front has been removed it it important to be sure it is firmly seated in th...

Page 10: ...PAEC4015x PAEC4020x PAEC4025x Ref Metric mm Imperial in Product type A 127 5 08 PAEC4010 15 20 25x B 102 4 08 PAEC4010 15 20 25x C 235 9 40 PAEC4010 15 20 25x D 750 30 00 PAEC4010x E 1260 50 40 PAEC40...

Page 11: ...15x 2 pcs 400 15 75 Fig 6 PA34WB20 PAEC4020x 3 pcs 400 15 75 Fig 6 PA34WB30 PAEC4025x 4 pcs 400 15 75 Fig 6 PAWBL15 PAEC4015x 2 pcs 560 22 05 Fig 6 PAWBL20 PAEC4020x 3 pcs 560 22 05 Fig 6 PAWBL30 PAEC...

Page 12: ...tric Length Imperial PA34CB15 PAEC4010 15x 4 pcs PA34CB20 PAEC4020x 6 pcs PA34CB30 PAEC4025x 8 pcs PA34WS15 PAEC4010 15x 4 pcs 3 m 9 8 ft PA34WS20 PAEC4020x 6 pcs 3 m 9 8 ft PA34WS30 PAEC4025x 8 pcs 3...

Page 13: ...24x2516 3 48x16 96x100 64 Type Product type Length Metric mm Length Imperial in PA4XT10 PAEC4010x 130 200 5 20 8 00 PA4XT15 PAEC4015x 130 200 5 20 8 00 PA4XT20 PAEC4020x 130 200 5 20 8 00 PA4XT25 PAEC...

Page 14: ...PAEC4000 14 Accessories Note The air curtain must be secured in the wall or ceiling Fig 11 See separate manual for PA4JK PA4VDW PA4JK...

Page 15: ...000 PA4HEVDW PAEC4000 AXP300 PAEC4000 Accessories Type Product type Length Metric Length Imperial PA34EF10 PAEC4010W PA34EF15 PAEC4025W PA34EF20 PAEC4020W PA34EF25 PAEC4025W DTV200S PAEC4000W FHDN20 P...

Page 16: ...0 m 32 8 ft SIReCC615 15 m 49 2 ft SIReCC640 40 m 131 2 ft SIReCC403 3 m 9 8 ft SIReCC405 5 m 16 4 ft SIReCC410 10 m 32 8 ft SIReCC415 15 m 49 2 ft Accessories SIReACY SIReAAY SIReRTX SIReWTA SIReCC S...

Page 17: ...H1 H2 N Id SIRe B1EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M 4010WA 4025WA 4020WA 4015WA 208V1 PE L1 L2 AREC400...

Page 18: ...EC Room C2 C1 Actuator 230V Supply 230V PE L N Heating L N L Trafo K2 K1 4010E 4015E 4010E 4015E TS1 TS2 Motor protection 0 10V GND PWM L N Motor Internal sensor M M M M L1 L2 L3 L1 K2 L2 K2 L3 K2 L1...

Page 19: ...Trafo K 2 K 1 K 2 K 1 4020E 4025E 2 X 208V3 TS 2 TS 1 Moto r p rotec tio n 0 10 V GND P WM L N Moto r Inte rna l se n so r M M M M 208V3 L1L2 L3 4025E 4020E 4020 6 motors 4025 7 motors L1 K 2 L2 K 2...

Page 20: ...oom C2 C1 A ctuato r 230V S upply230V PE L N He ating L N L Trafo K 2 K 1 4010E 4015E TS1 TS2 Motor protec tio n L N Motor Internal sensor M M M M 6 0 0 48 0V 230V Transformer 2 x 10A FUSE L1 L2 L3 2...

Page 21: ...0V PE L N Heating L N L Trafo K2 K1 K2 K1 4025E 4020E 4020E 4025E 2 X 600V3 480V3 TS2 TS1 TS3 TS4 Motor p rotection 0 10V GND PWM L N Motor Internal sensor M M M M 600V3 480V3 600 480V 230V Transforme...

Page 22: ...les Veuillez vous assurer que la tension d alimentation de l unit correspond la tension de secteur locale La tension d alimentation de l unit et les calibres maximums sont indiqu s sur l tiquette de d...

Page 23: ...ountings is available for both wall and ceiling installations se accessories pages Mounting with wall brackets 1 Remove the plastic covers on the wall brackets Fig 6A 2 Mount the brackets on the wall...

Page 24: ...d control card see fig 2 SIRe is supplied pre programmed with quick fit connections Modular cables are connected to the control board See manual for SIRe Unit without heating or with water heating Con...

Page 25: ...top of the unit horizontal mounting or on the reverse vertical mounting via connections DN20 3 4 external thread Flexible hoses are available as an accessory see accessories pages The connections to...

Page 26: ...nce is connected this may be due to moisture in the heating element When an appliance containing a heater element has not been used for a long period or stored in a damp environment moisture can enter...

Page 27: ...3 years and less than 8 years shall only switch on off the appliance provided that it has been placed or installed in its intended normal operating position and they have been given supervision or ins...

Page 28: ......

Page 29: ......

Page 30: ...13 December 2021 Main o ce Frico AB Tel 46 31 336 86 00 Industriv gen 41 SE 433 61 S vedalen mailbox frico se Sweden www frico net For latest updated information and information about your local conta...

Reviews: