Electrical Connections
• The extractor fan must be connected to a single
phase mains network, at the voltage and frequency
indicated on the extractor specification plate.
• The installation must have an omnipolar switch
with a contact separation of at least 3mm. The
circuit must be protected by either a 3 Amp fuse
or suitable 3A MCB.
• Earthing is not required as this extractor is a
class II double insulated appliance.
• The extractor must be connected permanently to
by a fixed installation cable secured in fixed
channeling. (Flex of two conductor wires of
minimum section 1mmÇ and maximum 1.5mmÇ).
• The 100 / 125 / 150mm fans have a two speed
motor, the 200mm fans have a three speed motor.
To make the Electrical Connection:
1. Loosen the 4 screws (1. K) and take off the
connection cover (M) (Fig. 2).
2. Perforate the flex holder (O) to allow the
power supply wires to pass through
(Fig. 2 & 3).
3. Make the connections as indicated
on the next page.