background image

6

Water quality from an RO system is normally
determined with a TDS Meter, which measures

total

dissolved solids

in water, measuring conductivity.

The results are normally measured in parts per
million or milligrams per liter.

Fewer dissolved

solids results in higher quality water.

RO membranes are rated by the amount of
dissolved solids they reject, expressed as “rejection
percentage”.

For example if feed water contains

100 ppm of dissolved solids and the product water
after the membrane has 10 ppm of dissolved solids,
the rejection rate is 90%. The formula is as follows:

Percent rejection =

Feed water TDS – Product water TDS X 100%

Feed water TDS

Water production

Product water rate

Usable water production from an RO system is
designated

product water rate,

produced on a daily

basis. The rate is normally described in gallons per
day (gpd) or milliliters per minute (ml/min.).

Reject water rate

The flow of water to drain is designated as

reject

water rate,

as measured in gallons per day (gpd) or

milliliters per minute (ml/min.).

Using a graduated cylinder the formulas are:

Milliliters per minute X 0.38 = gallons per day
Ounces per minute X 11.2 = gallons per day

Reject ratio

The

reject ratio

is the amount of water produced

compared to the amount of water flowing to drain.
The formula is as follows:

Reject rate

Reject ratio =

Product rate

Percent recovery

The

percent recovery

is another way to measure

the amount of water produced compared to the
amount of water which is actually used.

The formula to determine

percent recovery

is as

follows:

Product water rate X 100%

Percent recovery =

Feed water rate

Note:

Product water rate is the sum of the feed

water flow rate and reject water flow rate.

Example:

Product water rate = 10 gpd
Reject water rate = 40 gpd
Feed water = 10 gpd + 40 gpd or 50 gpd

Percent recovery = 20%

Water pressure and temperature

Product

water

quality and

production

of

RO

systems

is

dependent

on

pressure

and

temperature. Typically, RO membranes are rated
at standard conditions of 77

F (25

C) and 60 psi

(4 bar) discharging to atmosphere. In general, the
higher the pressure differential and temperature,
increased quality and quantity of water is produced.
These factors should be considered when sizing
RO systems for a particular application.

John Guest® brand fittings

Many RO systems utilize John Guest brand fittings.
These

user-friendly

fittings

provide

superior

performance and may be provided with this system.
Proper use of these

push-in

fittings is shown below.

Along with these fittings, all tubing selected must be
of high quality and must be cut with a plastic tube
cutter or sharp razor with a clean, square cut.

Should a leak occur at a fitting, the cause is
generally defective tubing.

To fix a leak, relieve

pressure, release tubing, cut off at least 1/4" from
the end (square cut), reattach the tubing and
confirm the connection is leak free.

Each time a

new connection is made, it is advisable to cut off
1/4" from the end of the tubing using these fittings.

Conventional fittings

If John Guest fittings are not used, it is essential to
install

inserts

at the ends of all tube connections

when conventional fittings are used.

Summary of Contents for GTS-550S

Page 1: ... each particular installation 3 8 variable speed electric drill 1 8 1 2 bits 1 1 4 porcelain hole cutter if hole for second faucet is not provided Center punch and hammer 1 1 4 wood bit Concrete drill bits Phillips head and flat blade screwdrivers Adjustable wrench Crescent wrench Teflon tape Plastic tube cutter Air pressure gauge low pressure Air pump hand System location Your R O system may be i...

Page 2: ...not used check below to make sure the drill does not interfere with anything below Center punch a small indent at the desired faucet location 2 flat surface is required not exceeding 1 1 4 in thickness Drill the required pilot hole for the chassis punch and tighten nut to cut the desired hole size Clean up sharp edges The faucet should be positioned so it empties into the sink and the spout swivel...

Page 3: ...d in this position 5 Turn on water supply to pressure cold water line 6 Snug nut seal with wrench around valve stem 7 Connect tubing to feed water valve using brass compression nut insert and plastic sleeve Saddle valve installations with metal pipe 1 Turn off cold water supply 2 Drill 3 16 hole at desired location 3 At this point make sure piercing lance does not protrude beyond rubber gasket 4 A...

Page 4: ...es Tubing should follow contour of the cabinets Cut tubing to desired length using square cuts and proper cutting devise Make no sharp bends Keep tubing from the RO unit to the tank and faucet as short as practical for good flow Under sink installations following installation diagram and the following procedures 1 Connect tubing from faucet to RO unit 2 Connect tubing from tank to RO unit 3 Connec...

Page 5: ...oroughly rinse all soap before reassembly 5 Replace filter cartridges and membrane before sanitizing system Note The system should be sanitized before installing the activated carbon post filter cartridge Sanitizing instructions To sanitize system follow these procedures with the feed water valve closed 1 Close feed water valve 2 Open faucet to drain storage tank to sink 3 Remove pre filters membr...

Page 6: ...is actually used The formula to determine percent recovery is as follows Product water rate X 100 Percent recovery Feed water rate Note Product water rate is the sum of the feed water flow rate and reject water flow rate Example Product water rate 10 gpd Reject water rate 40 gpd Feed water 10 gpd 40 gpd or 50 gpd Percent recovery 20 Water pressure and temperature Product water quality and producti...

Reviews: