Freedom Won eTower Installation Manual Download Page 7

eTower Installation Manual Revision 0 

 

            P a g e  

6 | 23

 

 

2.2.8

 

RS485 dual interface inter-module communication bus RJ45 
plugs 

This RS485 bus is used to link the communications of all parallel connected modules in the 

tower so that relevant data can be received by Address Number 01 Module (Module 01), 

which is in turn relayed from Module 01 to the inverter over CAN Bus or RS485. There are 

two ports on each module so that the communication cables can be “daisy chained” across 

all the modules. These cables are standard ethernet cables, and one is included with each 

module that is made to the exact right length to jump from one module to the next adjacent 

module whether mounted on the pedestals or in a 19” rack.  

2.2.9

 

Digital Output Dry Contacts (DCT) 

The 

Digital Output “Dry” Contacts (DCT) include DO1 (pins 1 and 2) and DO2 (pins 3 and 4), 

which are normally closed potential free contacts. DO1 opens when the battery has any 

type of fault protection enforced. DO2 opens the battery raises a low State of Charge alarm. 

Do not exceed 2A though these contacts. If a higher current is required to drive your 

external device use an interposing relay that is controlled by the battery and in turn controls 

your external device that requires more than 2A.  

2.2.10

 

Reset Button 

Reset Button – When the battery is in a dormant state the reset button can be pressed with 

a suitably narrow object to “wake up” the BMS. If the battery is in a fault or alarm state, the 

reset button may be pressed to clear the alarm or fault to restore normal operation. The 

button must be pressed for about five seconds to initiate a reset – while holding the reset 

button down, the SoC indicator LED’s should cycle right to left and then left to right. Once 

this initial LED sequence begins you can let go of the button.  

2.2.11

 

Positive Terminal 

The positive terminal is equipped with two fastening points supplied with M6x16mm bolts 

to accommodate interconnecting busbars and cable lugs. Busbars must be staggered to 

alternate between left and right terminals when connecting towers of two or more 

modules. See Figure 2.3 showing a four-module eTower.  The top module is fitted with two 

35mm

2

 cables to accommodate the maximum power capability of the battery stack. One 

cable lug is fitted onto the same terminal as the busbar and the other cable lug onto the 

second terminal.  

 

 

 

 

Summary of Contents for eTower

Page 1: ...nical and Installation Assistance Contact Please contact your Freedom Won Distributor or Reseller Installer for technical and installation support A directory of Distributors and Reseller Installers i...

Page 2: ...provide direct support that specifically relates to the battery interfacing with supported third party inverter brands 2 Product Description The eTower range presently includes only the e5000 module w...

Page 3: ...ded in Figure 2 1 and described below Additional detail is provided in Section 2 2 Tabulation Descriptions from Figure 2 1 1 Fixing threads for 19 rack mount brackets if required 2 Carrying handles 3...

Page 4: ...side of the module near the front as indicated that match the 19 rack mount brackets available from Freedom Won on request The primary installation arrangement is intended to be stacking the modules...

Page 5: ...33 2 49 8 Light on Light on Light on Light off Light off Light off Light on Light on Flash Light off Light off Light off 49 8 66 4 Light on Light on Light on Light on Light off Light off Light on Lig...

Page 6: ...address are to be set as shown in Table 2 2 For a system without the ability to interface between the battery and the inverter all dip switches must be left switched off Table 2 2 Dip Switch Position...

Page 7: ...t is required to drive your external device use an interposing relay that is controlled by the battery and in turn controls your external device that requires more than 2A 2 2 10 Reset Button Reset Bu...

Page 8: ...eTower Installation Manual Revision 0 P a g e 7 23 Figure 2 3 Four Module eTower...

Page 9: ...eedom Won Inverter Interfacing Guide The eTower is packaged with a cable suitable for use with the Voltronic range of inverters such as the Axpert For assistance with other inverter types running on R...

Page 10: ...N Bus Communication Cable In this photo the battery is shown with a CAN Bus cable which is connected to a CAN Bus compatible inverter system This cable is part of the included accessories See 2 2 14 2...

Page 11: ...eTower Installation Manual Revision 0 P a g e 10 23...

Page 12: ...eTower Installation Manual Revision 0 P a g e 11 23...

Page 13: ...ly used when setting up the inverter for the minimum cut off is 48V however this will not typically be reached if operating down to 90 Depth of Discharge DoD The BMS will command the compatible connec...

Page 14: ...incorporates the safe LiFePO4 lithium cell design it is unfortunately classified along with all lithium batteries as dangerous goods Class 9 Miscellaneous and UN 3480 When shipped by sea the package m...

Page 15: ...the pedestal is not suitable for a given application the eTower may also be installed with the terminals facing upwards preferably not directly on the floor but on a stand or shelf or wall mount brac...

Page 16: ...short circuit The DC cable cross sectional area is based on an acceptable voltage drop with the inverter being mounted on the wall adjacent to the eTower with a maximum cable run of 5m note however t...

Page 17: ...d with a CAN messaging profile that is developed for the inverter or charge controller being used This profile must be specifically developed for each inverter model or model range To date Freedom Won...

Page 18: ...ammed to operate at 250kbps if this BAUD rate must be used 6 4 Parallel Configurations It is permissible to connect multiple eTower e5000 modules in parallel It may however be more cost effective to p...

Page 19: ...continuous discharge currents for the eTower in configurations of one to four are provided in Table 2 1 The charge current limit should be observed for the current limit settings of the inverter s Th...

Page 20: ...o a consideration for the user in terms of battery service life The recommended voltage for forcing the inverter back to grid power in a self consumption setup without communication is 52 0V for appro...

Page 21: ...us equipped Victron inverters GX devices 1 x Type 1 inverter interface CAN Bus cable 1 8m length for connecting compatible CAN bus equipped Type 1 inverters e g Sunsynk Growatt Solis Goodwe 1 x Voltro...

Page 22: ...pacity at the end of this period or cycle count The BMS records the number of cycles used If you suspect that your eTower is delivering substantially below its minimum performance please contact your...

Page 23: ...maximum voltage value Try reducing the charge voltage setting on the inverter by to 55 5V and reset the battery by pressing the reset button for 6 seconds 3 The alarm light comes on at low SoC This co...

Reviews: