FR200 Series Vector control inverter
- 104 -
This parameter sets the maximum output frequency when Y2/HO terminal is selected as
high-speed pulse output.
F07.10
HO output filtering time
Range:0.000
~
10.000s
Default:0.010s
Set the filtering time of HO high-speed pulse output. Filtering can change the change rate of
output pulse frequency. The longer the filtering time is, the lower the change rate of output pulse
frequency would be.
Group F08 Parameters of Motor 1
Set the parameters according to the motor nameplate no matter whether V/F control or vector
control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor
auto-tuning accuracy depends on the correct setting of motor nameplate parameters.
F08.08
Stator resistance R1 of
async motor 1
Range:0.001
~
65.535Ω
Default: Model defined
F08.09
Rotor resistance R2 of
async motor 1
Range:0.001
~
65.535Ω
Default: Model defined
F08.10
Leakage inductance L1 of
async motor 1
Range:0.001
~
65.535mH
Default: Model defined
F08.11
Mutual inductance L2 of
asynchronous motor 1
Range:0.1
~
6553.5mH
Default: Model defined
F08.12
No-load current of async
motor 1
Range:0.1
~
1500.0A
Default: Model defined
F08.13
Field weakening coeff 1 of
async motor 1
Range:0.0
~
100.0%
Default:87%
(
1.1
)
F08.14
Field weakening coeff 2
of async motor 1
Range:0.0
~
100.0%
Default:75%
(
1.6
)
F08.15
Field weakening coeff 2
of async motor 1
Range:0.0
~
100.0%
Default:70%
(
3
)
The parameters in F08.08 to F08.15 are asynchronous motor parameters. These parameters are
unavailable on the motor nameplate and are obtained by means of motor auto-tuning. Only F08.08 to
F08.10 can be obtained through static motor auto-tuning. Through complete motor auto-tuning,
encoder phase sequence and current loop PI can be obtained besides the parameters in F08.08 to
F08.12.Each time "Rated motor power" (F08.01) or "Rated motor voltage" (F08.02) is changed, the AC
drive automatically restores values of F08.08 to F08.12 to the parameter setting for the common
standard Y series asynchronous motor.
If it is impossible to perform motor auto-tuning onsite, manually input the values of these
parameters according to data provided by the motor manufacturer.
F08.30
Autotuning of motor 1
Range:0
~
2
Default: 0
0: No auto-tuning
Auto-tuning is prohibited.
1: Asynchronous motor static auto-tuning
It is applicable to scenarios where complete auto-tuning cannot be performed because the
asynchronous motor cannot be disconnected from the load.Before performing static auto-tuning,
properly set the motor type and motor nameplate parameters of F08.00 to F08.07 first. The AC drive
will obtain parameters of F08.08 to F08.10 by static auto-tuning.Set this parameter to 1, and press
RUN. Then, the AC drive starts static auto-tuning.
2: Asynchronous motor complete auto-tuning
To perform this type of auto-tuning, ensure that the motor is disconnected from the load. During
the process of complete auto-tuning, the AC drive performs static auto-tuning first and then
accelerates to 80% of the rated motor frequency within the acceleration time 4. The AC drive keeps
running for a certain period and then decelerates to stop within deceleration time 4
F08.01
Power rating of motor 1
Range:0.1
~
1000.0kW
Default: Model defined
F08.02
Rated voltage of motor 1
Range:60
~
660V
Default: Model defined
F08.03
Rated current of motor 1
Range:0.1
~
1500.0A
Default: Model defined
F08.04
Rated frequency of motor 1
Range:20.00
~
Fmax
Default: Model defined
F08.05
Rated speed of motor 1
Range:1
~
60000rpm
Default: Model defined