TGA300 Rev180405
25
Table 5. Calibration Codes Quick Reference Chart
CALIBRATION
Three programs are available after the calibration password code has been entered:
C1 - Discharge Pressure Sensor Zero Calibration
C2 - Intake Pressure Sensor Zero Calibration
C3 - Engine RPM Calibration
Refer to Table 5. Calibration Codes Quick Reference Chart.
Enter Calibration Password Code 1111
Note:
To exit the programming mode, press the
SILENCE
button when the
program code flashes in the
RPM
display.
1. Enter the password code 1111. (Refer to Programming Section.)
Result: When the correct password code is entered
C 1
flashes in the
RPM
display. The message display shows
D.PSI
.
2. Press the
PRESSURE
or
RPM
buttons when the program (C) code is
flashing to scroll through the program codes.
Refer to specific calibration section for detailed procedures.
Note:
If there is a failure during calibration the message display shows
SENSOR PROBLEM
.
3. Press the
SILENCE
button when the program (C) code is flashing to exit.
CODE DESCRIPTION
MESSAGE
DISPLAY
Press MENU
Button Again
Press MENU
Button Again
C1
Discharge Pressure
Sensor Zero Calibration
D.PSI
D.PSI
SET P=0?
D.PSI
D.PSI=0
C2
Intake Pressure Sensor
Zero Calibration
I.PSI
I.PSI
SET P=0?
I.PSI
I.PSI=0
C3
Engine RPM Calibration CAL.
ENG RPM
SET RPM
XXXX